Specification for Pressure Switch


V Balaji A Neeleshwaran 08/02/2012 2 Pressure Switch up to 1 Mpa Gas (SF6) Thread type Male M16 Diaphragm / Bellow / Ultrasonic / LVDT IP 66 Explosion proof to gas group II a, bc, c as per IS 2148 -50C to 90C 20C 0.5g 1% FSR Adjustable Integrated with three micro switches, operating independently at different pressure level 230V ac @ 5A 110v dc @ 5A Switch Terminal connection wires This switch is to provide the signal to Main circuit during the falling pressure.

Rev
Device Range Application Connection Pressure Sensor IP Protection Flame proof Op. Temp Calibration Temp. Seismic Level Measuring Accuracy Dead band Consist of Micro Switch Output Function

1 of 2

Other Important Requirement

2 2.1

2.2

2.2.1

3 4

Since we are dealing with Export & major Power sector industries, we need your company track record like your major customer, which was major application these Pressure switch was used like Boiler, Pressing machine etc, as our requirement, this Pressure switch will be mounted on environmental of vibration and expose to high & low temperatures We need two variety of Pressure switch one type should be Normal Close (i.e.) Micro switch should Open Contacts for the below pressure settings Setting of the contacts: Switch 1 (Falling contact 1-2) 0,74 Mpa abs at 20C Breaking on falling pressure - Alarm Pressure Switch 2 (Falling contact 3-4) 0,71 Mpa abs at 20C Breaking on falling pressure - Lock-out Pressure Pme1 Switch 3 (Falling contact 5-6) 0.71 Mpa abs at 20C Breaking on falling pressure - Lock-out Pressure Pme2 Another type should be Normal Open (i.e.) Pressure switch should Close Contacts for the below pressure settings Setting of the contacts: Switch 1 (Falling contact 1-2) 0,54 Mpa Making on falling pressure - Alarm Pressure Switch 2 (Falling contact 3-4) 0,51 Mpa Making on falling pressure - Lock-out Pressure Pme1 Switch 3 (Falling contact 5-6) 0.51 Mpa Making on falling pressure - Lock-out Pressure Pme2 Setting of the contacts: Switch 1 (Falling contact 1-2) 0,64 Mpa abs Making on falling pressure - Alarm Pressure Switch 2 (Falling contact 3-4) 0,61 Mpa abs Making on falling pressure - Lock-out Pressure Pme1 Switch 3 (Falling contact 5-6) 0,61 Mpa abs Making on falling pressure - Lock-out Pressure Pme2 The three switches should be operate independently It will be appreciable, if the Pressure switch can be integrated with Dial gauge

2 of 2

Вам также может понравиться