A L C O A C O N D U C T O R A C C E S S O R I E S , I N C .

ALCOA T&D * * ENGINEERING * * * * * * * * * * * 70 YEARS IN CONDUCTOR MOTION CONTROL* * * * * * * * * * * * Vibration * * Recommendation LDP Consulting Engineers Itasca-Tonnee Curlew ACSS/TW 4605 Conductor CURLEW/ACSS/TW1033.5 Kcmil Type 13 Based on - Max Design Tension of 13431 Lb and NESC Heavy Load Zone - Max (Steady) Wind Speed: 20. Mi/Hr - Average Annual Minimum Temperature (AAMT):-30. Deg.F - Average Annual Temperature (AAT): 60. Deg.F - AFL Single Suspension (1 Layer A.R.): A.R.Length=100.0 In. A.R.Diameter= .310 In. Maximum Protectable Spanlengths Final Damper Clamp: Tnsn Over Cable Over AAT None A.R. -1-2-15818 552 763 1822 3645 1458 5960 494 705 1746 3492 1396 4887 771 982 2210 4421 1768 Damper Catalog Number: Damper Clamp (Bare) 1706-10 Damper Clamp ( A.R.) 1706-15 Note: Installation Torque for -10 Clamp 1/2 Installation Torque for -15 Clamp 5/8

Ruling Max Span Span Feet Feet 694 750 667 700 481 500

Intl Tnsn AAMT 6605 6848 5845

Damper Spacing(In.) A.R. (See Manual) -2-A- -B- -C- -D2916 30 27 30 31 2793 30 27 30 32 3537 27 25 27 29

Bolt is 25 LbF.Ft Bolt is 40 LbF.Ft

Note: Certain information such as the data, opinions or recommendations set forth herein or given by AFL representatives, is intended as a general guide only. Each installation of overhead electrical conductor, underground electrical conductor, and/or conductor accessories involves special conditions creating problems that require individual solutions and, therefore, the recipient of this information has the sole responsibility in connection with the use of the information. AFL does not assume any liability in connection with such information. 12-19-2002

Вам также может понравиться