3877-3 MECHANICAL & ELECTRICAL SERVICES 1 _______________________________________________________________________ _ Services

1. Electrical TNB Room Consumer HT Room Transformer Room LV Switch Room Electrical Riser 2. Telephone MDF Room Telephone Riser 3. 4. Generator Set Room 1500 kVA Security System ELV Riser Data Riser 5. Fire Protection Fire Pump Room (for sprinkler & hose reel pumps) Fire Control Room Sprinkler Tank 15000 (W) x 10000 (D) 3500 (W) x 3500 (D) RC Tank 1: 55m2 x 3500 (H) RC Tank 2: 47m2 X 3500 (H) Riser RC Tank: 31m2 X 3500 (H) To be located at Carpark Level 1 between Sprinkler Tank and Hose/Wet Riser Tank To be located near entry to building at Ground Floor. Can be combined with Security Room To be located flush with Fire Pump Room at Carpark Level 1. Tank to be compartmented inot 2 half To be located flush with Fire Pump Roomks at Carpark Level 1 Within every staircase/fire lobby escape 800 (W) x 750 (D) 1000 (W) x 750 (D) For CCTV, SMATV, PA & Card Access System For structure cabling system 6500 (W) x 9000 (D) x 5000 (H) Located beside TNB room 6000 (W) x 8500 (D) x 3000 (H) 1000 (W) x 750 (D) Located at Basement Car Park Located at every floor 6000 (W) x 5000 (D) x 4000 (H) 6000 (W) x 5000 (D) x 4000 (H) 10000 (W) x 4500 (D) x 4000 (H) 8500 (W) x 9000 (D) x 4000 (H) 2500 (W) x 1000 (D) Located beside TNB Room Located adjacent to Genset Room Located adjacent to TNB Sub Station Located at every floor

Description

Size (mm) (Minimum)

Remarks

Hose Tank

Reel/Wet

Fire Riser 6. Domestic Cold & Hot Water DCW Suction Tank DCW Transfer Pump Room DCW Roof Storage Tank Podium West Block DCW Roof Storage Tank Podium Centre Block DCW Roof Storage Tank Podium East Block

1300 (W) x 650 (D)

RC Tank : 167m2 X 3500 (H) 4000 x 4000 x 3500(H) 7000 x 6000 x 2500(H) 8000 x 6000 x 2500(H) 7000 x 6000 x 2500(H)

Rc tank located Carpark Level 1 Tank to be compartmented into 2 half. Attached to rc suction tank between the tank compartment FRP Sectional Tank located on RC Flat Roof c/w 600 high rc plinth FRP Sectional Tank located on RC Flat Roof c/w 600 high rc plinth FRP Sectional Tank located on RC Flat Roof c/w 600 high rc plinth

3877-3 MECHANICAL & ELECTRICAL SERVICES 2 _______________________________________________________________________ _ Services Description Size (mm) (Minimum) Remarks
DCW Roof Storage Tank - Tower Cold Water Riser (All Podium Block & Tower) DCW Hydro Pneumatic Pump Room (All block and Tower) 7. Sanitary Plumbing Last manhole Sanitary Plumbing Riser (All Podium Block & Tower) 8. Air Conditioning Toilet Exhaust Fan Room AHU Room (Tower) 2500 x 2500 x 3000 (H) 5000 x 6500 Located on RC Flat Roof above toilet (if enclosure is require, otherwise fan is exposed) 2 nos. per floor for on floor units around Lift core Area. Size include Fresh air Duct within(OR 2 nos.. 25m x 25m central AHU Room on Roof ) 2 nos. per floor for on floor units around Lift Core Area. Size include Fresh air Duct within (OR 2 nos. 20m x 15m central AHU Room on Roof) Located at Capark Level 2 Located within or next to toilet Located within or next to toilet Around Lift Core area Around Lift Core area Carpark Levels. Locate so that the shaft discharge to Ground floor open area and opposite side of Fresh Air Shaft for cross ventilation Carpark Levels. Locate so that the shaft discharge to Ground floor open area and opposite side of Fresh Air Shaft for cross ventilation Locate next to Exhaust Air Shaft 600 (W) x 600 (D) Located at building perimeter, actual location to be determine Located within the public toilets 14000 x 6000 x 2500(H) 600 (W) x 600 (D) 2500 x 2500 x 3000(H) FRP Sectional Tank located on RC Flat Roof c/w 600 high rc plinth Located within the public toilets Located at roof level near to DCW Tank All Blocks & Tower

AHU Room Podium Block)

(Each

5000 x 6500

Hex & Chilled Water Pump Room Toilet Exhaust Shaft (AllPodium Block) Toilet Exhaust Shaft (Tower) Smoke Spill Make Up shaft (All Podium Block & Tower) Smoke Spill Shaft (All Podium Bloc & Tower) Carpark Fresh Air Shaft

16000 x 13000 x 4000 (H) 600 (W) x 900 (D) 1200 (W) x 900 (D) 1500 (W) x 1500 (D) 1500 (W) x 1500 (D) 3 nos. 4000 (W) x 3000 (D)

Carpark Shaft

Exhaust

Air

3 nos. 4000 (W) x 3000 (D)

Carpark

Exhaust

Fan

4500 (W) x 4500 (D) x 3000 (H)

3877-3 MECHANICAL & ELECTRICAL SERVICES 3 _______________________________________________________________________ _ Services Description Size (mm) (Minimum) Remarks
Room Carpark Supply Air Fan Room Pressurization Shaft (All Podium Block & Tower) Pressurization Fan Room (All Podium Block & Tower) 9. BAS BAS Riser (All Podium Block & Tower) 10. LPG LPG Farm LPG Riser 7500 (W) x 1000 (D) x 3000 (H) 600 (W) x 600 (D) Outside Building Perimeter Well Ventilated 600 (W) x 600 (D) Around Lift Core area 4500 (W) x 4500 (D) x 3000 (H) 600 (W ) x 1500 (H) Locate next to Exhaust Air Shaft Attached to All internal Escape Staircases, perimeter Staircase without window and Bomba Lift Lobby Locate at RC Flat Room

3500 (W) x 300 (D) x 3000 (H)

Note: All dimensions are shown for room clearance only.