Products and Devices

4.6 Instrument Transformers


Combined Instrument Transformers for Air Insulated Substations (AIS)

Type

SVAS [kV] 72.5 800 SF6

AVG 72.5 245 SF6 Technical data

IVOKT 72.5 300 Oil

Voltage range Insulation medium Composite insulator Porcelain insulator

Voltage level Rated power frequency withstand voltage Rated lightning impulse withstand voltage Rated switching impulse withstand voltage Rated frequency Creepage distance Temperature range

[kV] [kV] [kV] [kV] [Hz] [mm/ kV] [C]

72.5 140 325

123 230 550

145 275 650

170 325 750

245 460 1,050

300 460 1,050 850

362 510 1,175 950

420 630 1,425 1,050

550 680 1,550 1,175

800 975 2,100 1,550

16 50 60 25 31 (higher upon request) 40 +40 (other values upon request) CT ratings

Rated normal current up to Output current

[A] [A]

5,000 125 63 (80 on special request) 13 160 (200 on special request) E (SF6 insulated devices) A (oil insulated devices) 0.1 0.2 0.2S 0.5 0.5S 1.0 5P 10P TPY TPX TPZ TPS PR PX VT ratings

Rated short-time thermal current [kA] Rated duration of short circuit Rated dynamic current Insulation class Metering accuracy class Protection accuracy class [s] [kA]

Output voltage Rated voltage factor Metering accuracy class Output burden Protection accuracy class Output burden Thermal limiting output

[V]

110/3 200/3 (other values upon request) 1.2 1.5 1.9 (other values upon request) 0.1 0.2 0.5 1.0 3.0 for different classes according to customer specication 3P 6P for different classes according to customer specication

[VA]

3000 (other values upon request)

Values in accordance with IEC; other values like ANSI are available

Tab 4.6-5: Technical data of Trench combined instrument transformers for air-insulated substations (AIS)