Вы находитесь на странице: 1из 9

RL/22March2009

1.1 Circuit Breaker (CB)

1.2 INTRODUCTION

Circuit Breaker is one of the most important equipment in the power system. This

is because of the function of the equipment itself which is, the ability to close a

circuit or to break the circuit during maintenance work or when there is fault in

the system without getting damaged

1.3 DEFINITION

A Device capable of making and breaking an electric circuit under normal and

abnormal condition.

The function of a circuit breaker is just like a water tap; it stops and allows a

water flow through it.

1.4 Types of Circuit Breakers

Circuit breakers may be classified into 7 types such as the following:

• Bulk Oil circuit breakers

• Minimum Oil Circuit Breakers

• Vacuum Circuit Breakers

1.1
TR-SS
RL-CB/2009
RL/22March2009

• Gas Insulated Circuit Beakers

• Air Insulated Circuit Breakers

• Miniature Circuit Breakers

• Moulded Case Circuit Breakers

1.4.1 Bulk Oil Circuit Breakers

Bulk oil circuit breakers are already obsolete as they are very bulky and

expensive to maintain. It is also a high fire hazard. It is mainly used at

distribution voltage levels as the operating speed is rather slow.

In this breaker the main contacts are immersed in oil which has the dual

function of quenching the arc of the current as well as n insulating medium.

During contact opening to interrupt the current, the arc produced causes

dissociation of the oil into hydrogen and carbon. The hydrogen helps to extinguish

the arc while the carbon causes deterioration of insulation level of the oil. As

carbon is a conductor the oil has to be replaced after several fault clearances.

1.2
TR-SS
RL-CB/2009
RL/22March2009

1.4.2 Minimum Oil Circuit Breakers

Minimum Oil circuit breakers are generally similar in construction as the bulk

oil circuit breakers except that the latter contain les oil. Minimum oil c circuit

breakers are becoming less popular due to high fire risks but still widely used in

outdoor transmission substations. Their operating time is much faster than bulk

oil circuit breakers.

1.4.3 Vacuum Circuit Breakers

Vacuum circuit breakers are more popular at distribution voltage level. They

require minimum maintenance except to replace the vacuum bottle if a leak has

occurred. These types of breakers are getting more popular in recent years and

tend to replace the oil type. The reasons being they have no fire risk and have high

reliability with long maintenance free period.

1.3
TR-SS
RL-CB/2009
RL/22March2009

For these breakers the main contacts are housed within a vacuum in an

insulating cylinder of glass or ceramic having metal end plates supporting the

contacts. The vacuum device is usually referred to as a vacuum interrupter.

At 11kV normally only one vacuum interrupter per phase is used. But at 33kV

two interrupters may be used in series per phase. The closing mechanism for

VCBs is usually of the solenoid or spring-closing type. Contact wear is very low

because the arc takes place in vacuum.

1.4.4 Gas Insulated Circuit Beakers

The most commonly used circuit breakers nowadays are the gas circuit breakers

especially at transmission level. Gas circuit breakers normally using sulphur

hexafluoride (SF6) gas as the insulating medium require little maintenance and

have very fast operating time. Well design gas circuit breakers may last more

than 25 years without much maintenance.

1.4
TR-SS
RL-CB/2009
RL/22March2009

The interrupter unit and the contacts are housed in as Sf6 filled chamber. The

interrupter serves as a nozzle for the SF6 gas to pass through it at high speed

across the arc during contact opening and thus rapidly quenches the arc. SF6 gas

has a high recovery rate and minimal residue.

The closing and tripping mechanisms are similar to those of other breakers.

Cross Section view of a Gas Circuit Breaker

1.4.5 Air Insulated Circuit Breakers

Air insulated circuit breakers (ACBs) are normally used at distribution voltage

levels of 3.3kV and below especially in power stations as they are often modular

in design and may conveniently be arranged into multi-tier switchboards. They

also pose minimum fire hazard as there are no combustible materials used.

1.5
TR-SS
RL-CB/2009
RL/22March2009

The operating principle of this breaker is that the arc of the current is directed into

a chute where the arc resistance becomes higher and the arc rapidly diminished to

zero.

The forces directing the arc into the chutes of the ACBs are the electromagnetic

and thermal forces of the arc itself. In certain cases, to assist in the quenching of

low current arcs, an air cylinder is fitted to each pole to direct a puff of air across

the contact faces as the breaker opens. This helps to reduce erosion of the contact

surfaces.

Operating mechanisms for ACBs are similar to those used in OCBs.

1.6
TR-SS
RL-CB/2009
RL/22March2009

1.4.6 Miniature Circuit Breakers

MCBs are the smaller both in physical size and particularly the ratings compared

to MCCBs. Normally it us of a single pole design. It is small, manually closed and

electrically or manually opened. The MCBs have built-in bimetal strip to trip the

MCBs when excessive currents pass through them. The operation of the bimetal

corresponds to predetermined inverse-time/current characters tics. But for current

above 6 to 8 times rated current MCBs will trip instantaneously actuated by a

magnetic overcurrent trip elemnt. Neither part of the overall operation time of the

MCBs are adjustable.

1.4.7 Moulded Case Circuit Breakers

Generally MCCBs are similar to MCBs but have the following important

differences:

a. Current ratings are generally in excess of 100A up to 2.5 kA or higher.

Voltage ratings up to 1000 V a.c and 12000 d.c.

1.7
TR-SS
RL-CB/2009
RL/22March2009

b. The breakers are larger, in line with the level of ratings. MCCBs are

available as single pole, double pole, and triple pole or four pole units.

However, for multi-pole units they are moulded in one common housing.

Further, the switch for the neutral circuit is a separate device coupled to the

multi-pole MCCB.

c. The overall operating tie may be adjustable especially the larger ones.

d. Since they are of higher ratings MCCBs are normally positioned close to the

power source than the MCBs.

1.8
TR-SS
RL-CB/2009
RL/22March2009

1.5 Types of Site Electrical Test conducted on a Circuit Breaker

1.5.1 Timing Test

To measure the speed of breaker operation. Usually for opening and

closing operation.

1.5.2 Contact Resistance Test

To measure the resistance value of the main contact( fixed contact and

moving contact)

1.5.3 Dew Point Test for SF6 Gas on GCB

To measure the moisture contents of the SF6 gas.

1.5.4 Vacuum Test for VCB

To check that there is no leak on the Vacuum Insulation

*** This is just a draft lesson note, all your feedbacks on this note is very much welcome.

Do notify me at PL_Lim78@yahoo.com

1.9
TR-SS
RL-CB/2009

Вам также может понравиться