S1A1576900 (Rev01)

09/2009
Cedar Rapids, IA, USA

Instruction Bulletin

Replaces S1A1576900 08/2009

Trip Curve Values for Micrologic Trip Units


Basic, A, P and H Types
Retain for future use.

Micrologic Trip Curve Values


Table 1:

Micrologic Trip Unit Long-Time Delay Values


Long-Time Delay in Seconds

Setting

tr at 1.35 x Ir
tr at 1.5 x Ir
tr at 2 x Ir
tr at 3 x Ir
tr at 5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir

These values apply for Basic, A, P and H type Micrologic trip units, for all
protections levels (2.0, 3.0, 5.0 and 6.0).

0.5

12

16

20

24

Minimum

11.94

23.89

47.77

95.54

191.09

286.64

382.19

477.74

573.28

Maximum

19.12

38.24

76.49

152.98

305.96

458.94

611.92

764.9

917.88

Minimum

8.66

17.32

34.64

69.27

138.55

207.82

277.1

346.37

415.65

Maximum

12.51

25.03

50.05

100.11

200.22

300.32

400.43

500.54

600.65

Minimum

4.15

8.29

16.59

33.17

66.35

99.52

132.69

165.87

199.04

Maximum

5.47

10.93

21.87

43.73

87.46

131.91

174.92

218.65

262.38

Minimum

1.68

3.36

6.72

13.44

26.89

40.33

53.78

67.22

80.67

Maximum

2.14

4.27

8.54

17.08

34.17

51.25

68.34

85.42

102.51

Minimum

0.58

1.16

2.32

4.64

9.28

13.92

18.56

23.2

27.84

Maximum

0.73

1.45

2.91

5.81

11.63

17.44

23.25

29.07

34.88

Minimum

0.4

0.8

1.6

3.2

6.4

9.6

12.8

16

19.2

Maximum

0.5

12

16

20

24

Minimum

0.35

0.55

1.11

2.21

4.42

6.63

8.85

11.06

13.27

Maximum

0.5

0.69

1.38

2.76

5.52

8.28

11.04

13.8

16.56

Table 2:

Micrologic Trip Unit Short-Time Delay Values


Short-Time Delay

Setting

I2t off (Isd at 10 Ir) (seconds)

0.2

0.3

I2t on (Isd at 10 Ir) (seconds)

0.1

0.2

0.3

0.4

tsd (min. trip) (milliseconds)

20

80

140

230

350

tsd (max. trip) (milliseconds)

80

140

200

320

500

0.3

0.4

Micrologic Trip Unit Ground-Fault Delay Values

Setting
I2t

0.2

0.4

0.1

Table 3:

Schneider Electric
3700 Sixth St. SW
Cedar Rapids, IA 52404 USA
1-888-SquareD (1-888-778-2733)
www.schneider-electric.us

0.1
0

Ground-Fault Delay
0

0.1

0.2

0.3

0.4

off (at 1 In) (seconds)

0.1

0.2

0.3

0.4

I2t on (at 1 In) (seconds)

0.1

0.2

0.3

0.4

tsd (min. trip) (milliseconds)

20

80

140

230

350

tsd (max. trip) (milliseconds)

80

140

200

320

500

Electrical equipment should be installed, operated, serviced, and maintained only by


qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
2009 Schneider Electric All Rights Reserved