Simplicity - Reliability - Performance

Name: Toneladas Recuperadora General Description: Calculo de carga con recuperadoras

Engineer: Jeyson Alcoser Firm/Company: Refricountry S.A. Prepared By: Jeyson Alcoser Phone Number: 3005757952

Model Number: Core Designation:

EV300 G5 = J

(Info)

Fax Number: Email Address: ingrefricountry@gmail.com

Ventilation Inputs
Fresh Air Flow Rate: 300 Fresh Air Ext. Static Pressure: 0.50 Exhaust Air Flow Rate: 300 Exhaust Air Ext. Static Pressure: 0.50 CFM in W.C. CFM in W.C. Room Exhaust Air

Winter
DB: 72.0 : 50 DB: 84.0 : 70 F % F %

Summer
DB: 72.0 RH : 50 DB: 95.0 RH : 65 F % F %

Room Exhaust Air RH Outside Air Outside Air RH

Performance Data Sensible Winter Summer


Recovery Effectiveness 70 % 70 %

Total Winter Summer


54 % 42 %

Room Exhaust Winter Summer


Dry Bulb (F) Wet Bulb (F) Relative Humidity (%) Absolute Humidity (lbH20/dryair) Enthalpy (BTU/lb) 72.0 60.1 50 0.0083 26.4 72.0 60.1 50 0.0083 26.4

Outside Air Winter Summer


84.0 76.1 70 0.0176 39.5 95.0 84.5 65 0.0233 48.5

Supply Air Winter Summer


75.6 68.2 69 0.0130 32.4 78.9 75.6 86 0.0184 39.1

Sensible Winter Summer


Original Load (BTU/h) Original Load (Tons) Load with RenewAire (BTU/h) Load with RenewAire (Tons) Savings (BTU/h) Savings (Tons) -3888 -1174 -2714 7452 0.6 2251 0.2 5201 0.4

Latent Winter Summer


-13444 -6803 -6641 21719 1.8 14573 1.2 7145 0.6

Total Winter Summer


-17332 -7977 -9355 29171 2.4 16824 1.4 12347 1.0