F Application of Motor Place of Over Load Relay Motor Torque / Current Motor Rated Tourque (Full Load): Motor Rated Tourque (Full Load): Motor Starting Torque: Lock Rotor Current IL(Min): Lock Rotor Current IL(Max): Motor Starting Current : Motor Full Load Current (Line): Motor Full Load Current (Phase): Fuse (As per NEC 430-52) Non-Time Delay Fuse (Max) Time Delay Fuse (Max) Circuit Breaker (As per NEC 430-52) Instantaneous Trip Circuit Breaker (Max) Inverse Time Circuit Breaker (Max) Over Load Relay Setting Relay Min (70% of FLC Phase): Relay Max (120% of FLC Phase): OR Relay Setting (100% of FLC Line): Contactor Type of Contactor: Making / Breaking Capacity of Contactor: Main Contactor (100% of FLC Line):
415 Volt 3 Phase 3 Single Phase 3 HP 2.24 A 80% 750 0.8 Motor Load in Household Application In the line (Putting the overload before the motor) 21 28 85 4 13 27 4 2 12 7 lb-ft Nm Nm Amp Amp Amp Amp Amp Amp Amp (5252xHpxRPM) (9500xKw/RPM)
31 10
Amp Amp
2 3 4
AC7b 31 4
Amp Amp
Application
System Voltage Phase Type of Motor Motor Size Motor Code Motor Efficiency Motor RPM System P.F Application of Motor Place of Over Load Relay Motor Starting / Full Load Current Motor Rated Tourque (Full Load) Motor Rated Tourque Motor Starting Torque Lock Rotor Current IL(Min): Lock Rotor Current IL(Max): Motor Starting Current : Motor Full Load Current (Line): Motor Full Load Current (Phase): 3 2 Fuse (As per NEC 430-52) Non-Time Delay Fuse (Max) Time Delay Fuse (Max) Circuit Breaker (As per NEC 430-52) Instantaneous Trip Circuit Breaker (Max) Inverse Time Circuit Breaker (Max) Over Load Relay Setting Relay Min (70% of FLC Phase): Relay Max (120% of FLC Phase): OR Relay Setting (58% of FLC Line): Contactor Type of Contactor: Making / Breaking Capacity of Contactor: Main Contactor (58% of FLC Line): Delta Contactor (58% of FLC Line): Star Contactor (33% of FLC Line): Transient Time Delay Setting
415 Volt 3 Phase 3 3 Phase Induction 100 HP A 100% 500 0.75 Non-Inductive or Slightly Inductive ,Resistive Loa
In the windings (overload is placed after the Wind 1050 1425 2850 139 437 415 138 80 415 242 lb-ft Nm Nm Amp Amp Amp Amp Amp Amp Amp
8 3
1107 346
Amp Amp
56 96 80
75
100
dings (overload is placed after the Winding Split in to main and delta Contactor) (5252xHpxRPM) (9500xKw/RPM)
3 2
8 3
(1/3 Full Load Current) (1/3 Full Load Current) (1/3 Full Load Current)
AUXILIARY
14
22
14
34
NO:13-14
NC:21-22
1 NO + 1NC 1 3 5 13 21 1 3 5
2 NO + 1NC 13 21 43 31 13
2NO + 2NC 21 31
14
22
14
22 44
32
14
22 32
14
22 32 42 54
14
44
54
22 32
54
62 72
14
22 32 44
14
22 32
AUXILIARY CONTACTOR
AUXILIARY CONTECTOR
3NO + 1NC 43 21 21 1NO + 1NC 13
44
22
22
14
44
44 NO:43-44 NC:31-32
32
NO:13-14, 43-44
2NO + 2NC 53 61 71 83
84
54
62 72
84
NO:53-54. 83-84
42
NO:13-14
SUMMARY OF CONTACTOR
MAIN CONTACTOR: 1-2, 3-4, 5-6 AUXILARY CONTACTOR: (NO) : 13-14, 33-34, 43-44, 53-54, 83-84 AUXILARY CONTACTOR: (NC) : 21-22, 31-32, 41-42, 61-62, 71-72
NB: You can easily identify Whether Contactor is NO , NC from above Summary