C = Coupling Device DC = Dispatcher's console FAX = Facsimile equipment LT = Line trap M = Modem
MS RTU PAX PR PC
= Master station = Remote terminal unit = Private automatic exchange = Protection relay = Computer
STATION A
PLCC
WT
STATION B
CVT L A ES DC ES
CVT
LMU
PROTECTION COUPLER
LMU PLCC
PROTECTION COUPLER
PLCC
EXCHANGE
EXCHANGE
PLCC
CONSISTS OF A) INDOOR EQUIPMENT PLCC TRANSRECEIVER, TELEPHONE Xge,DATA MODEM,PROT COUPLER, RTU Etc. B) OUTDOOR EQUIPMENT LINE MATCHING UNIT,CVT,WAVETRAP C) COAXIAL CABLE interconnects I/D and O/D Equipments.
OUTDOOR EQUIPMENT
WAVETRAP CAPACITOR VOLTAGE TRANSFORMER LINE MATCHING UNIT PROTECTIVE DEVICES -EARTH SWITCH - LIGHTNING ARRESTOR
CVT IS CONNECTED BETWEEN THE LMU AND THE POWER LINE. THIS IS USED TO BLOCK THE EHT LINE VOLTAGE ENTERING INTO THE LMU/PLCC AND ALSO FOR METERING / POTECTION OF THE POWER LINE . IT IS A STACK OF CAPACITORS CONNECTED IN SERIES WITH ONE END CONNECTED TO POWER LINE AND ONE END GROUNDED. THE CAPACITANCE OF CVT IS 2200 / 4400 / 8800 PF.
LMU CONSIST OF AN IMPEDANCE TRANSFORMER WHICH MATCHES THE IMPEDANCE OF LINE WITH THE COAXIAL CABLE IMPEDANCE
CC
LINE
WAVE TRAP
CONSIST OF MAIN COIL TUNING CIRCUIT LIGHTNING ARRESTOR ALLOWS ONLY 50 HZ SIGNAL AND OFFERS HIGH IMPEDANCE TO HIGH FREQUENCY SIGNAL BAND SPECIFIED BY TUNING CIRCUIT WAVE TRAP SHALL BE DESIGNED TO CARRY THE FULL LOAD CURRENT OF THE POWERLINE.