Service Bulletin Service Settings

UCM Clear Language Display (CLD)


ORDER No: RTAA-SVB003-E4 DATE: April 2002

Introduction
This Service Bulletin provides you the factory setting to check UCM-CLD configuration.

Access to Service Settings

Service settings, enables units Service set-up menu Machine configuration group

Note: The configuration in Service settings has already been set before the unit leaves the factory, and it is password protected in order to maintain the proper operation of the chiller.

2002 American Standard Inc. All rights reserved.

Applicable Software
This Service Bulletin applies to helical-rotary liquid chiller UCMCLD microprocessor panels with the following modules. RTA-RTW-RTU-RTR CPM (A1) MCSP (A20) EXV (A52) CLD (A53) RTX CPM (A1) MCSP (A20) EXV (A52) CLD (A53)

x x x x

13650476 13650477 13650804 13650447

x x x x

13650585 13650476 13650586 13650447

Service Settings, Enables and Units


Display "Under/over voltage protection" "Unit line voltage" "Restart inhibit time" "Balanced CPRS starts and hours" "Display units" "Language" "Programmable relay setup" Comment With the option Without the option refer to order Fixed to 120 sec SI / English 7 languages 3 auxiliary relays/ select 1 to 12 Default RTWB Other units Setting E D 120 E SI [Language]

"External circuit lockout"

Refer to Table 1 E D

Simultaneously press "Previous" and "Enter" to unlock the keypad D = Disable E = Enable

RTAA-SVB003-E4

Service Setup Menu


Password: "+ + - - + +" "Enter" Display Keypad display lock feature "ICS address" "Lvg wtr temp cutout setpoint Comment Default Fixed to 55 From -23.3 to 1.6C Default (0% glycol) "Low rfgt temp cutout From -39.4C to 1.6C setpoint" Default (0% glycol) Low WTR temp. EXV gain comp. LVG WTR >=5C LVG WTR < 5 C "Condenser limit setpoint" % HPC "Cooling condenser limit setpoint" RTXA only % HPC "Heating condenser limit setpoint" RTXA only % HPC "Phase unbalance protection" "Phase reversal protection" "Superheat setpoint" "Cooling superheat setpoint" RTXA only "Heating superheat setpoint" RTXA only "EXV control response CKT1" From 2 to 200 Increase the setting if EXV "EXV control response CKT2"
response appears sluggish

Setting D 55 1.5C -5.4C D E Refer to Table 2 Refer to Table 2 Refer to Table 2 E E 3.5C 3.5C 3.5C 20

RTWB-RTUB 218-224 RTAD 115-125 other units + other RTWB/RTUB and RTAD sizes "Fan control deadband bias CKT1" From -50 to 50 (psi) "Fan control deadband bias CKT2" - Unit R134a or RTUB - Unit R404a and R22 "Defrost delta temp. setpt" RTXA only Offset to initiate defrost cycle

"Clg. EXV control response CKT1" "Clg EXV control response CKT2" "Htg EXV control response CKT1" "Htg EXV control response CKT2" "LVG WTR temp control response setpt"

RTXA only RTXA only

20 20 100

40 0 - 40 11.9

The UCM shall impose a minimum difference of 2.8C between "LVG WTR temp. Cutout setpoint" and "Chilled WTR temp. setpoint," and also 8.3C between "Low RFGT temp.Cutout setpoint" and "Chilled WTR temp. setpoint "

RTAA-SVB003-E4

Machine Configuration
Password: "+ - + - + -" "Enter" Display "Compressor model n prefix" Comment Setting 108-109-110-213 to 217 CHHB 322-324 to 434 RTWB/RTUB, RTAD or other units sizes 107-207-209-210-211-212-220 CHHN "Oil loss differential setpoint" Only with CHHN comp. - R404a -10 - R22 and R134a -8 - RTAB HR -22 Numbers of compressors" Unit 100 1 Unit 200 and RTAD 2 Unit 300 3 Unit 400 and RTAB 220 4 "Compressor A tons" Refer to Table 3 "Compressor B tons" "Compressor C tons" "Compressor D tons" "Unit model" RTA (RTR)-RTU-RTW-RTX Refer order "Variable speed fan CKT1" All units except RTW Refer to Table 4 "Variable speed fan CKT2" "Number of fan circuit 1" All units except RTW Refer to Table 4 "Number of fan circuit 2" "Reduced inrush starting" Yes E "Started type" Wye-delta or part winding Refer order Except RTAD Star delta

"Current ovrld setting CPRSR A" From 0 to 31 Refer to Table 5 "Current ovrld setting CPRSR B" "Current ovrld setting CPRSR C" "Current ovrld setting CPRSR D" "Low amb. Unit, half airflow fan" All units except RTW D "Low amb. Unit, two speed motor" All units except RTW Refer to Table 4 "Night noise set-back" Refer to order, option NNSB E/D "Number of EXV valves CKT1" Units 100-200, RTAB 220 and RTAD 1 Units 300-400-RTXA 200 2 "Number of EXV valves CKT2" Units 200-300, RTAB 220 and RTAD 1 Units 400-RTXA 200 2 "Refrigerant type" R22-R134a-R404a Refer order RTAD R134a LA = low-ambient unit HE = high efficiency

RTAA-SVB003-E4

Table 1: Output Relay


conf Relay 1 (1;2) 1 Alarm MR 2 Alarm MR + AR 3 Alarm MR +AR+IFW 4 Alarm MR+IFW 5 Circuilt alarm 1 MR 6 Circuit 1 alarm MR+AR 7 Circuit 1 alarm MR+AR+IFW 8 9 10 11 12 Circuit 1 alarm MR+IFW Alarm MR Alarm MR+AR Alarm MR+AR+IFW Alarm MR+IFW Relay 2 (4;5) Unit is running Unit is running Unit is running Unit is running Circuit 2 alarm MR Circuit 2 alarm MR+AR Circuit 2 alarm MR+AR+IFW Circuit 2 alarm MR+IFW Circuit 1 running Circuit 1 running Circuit 1 running Circuit 1 running Relay 3 (6;7) Maximum capacity Maximum capacity Maximum capacity Maximum capacity Maximum capacity Maximum capacity Maximum capacity Maximum capacity Circuit 2 running Circuit 2 running Circuit 2 running Circuit 2 running

MR: Manual reset AR: Auto reset IFW: Informational warnings

Table 2: Limit HP
"HPC" R22 = 2793 kPa "HPC" R134a = 2200 kPa "HPC" R404a = 3000 kPa Standard Air Cooled Units + RTXA Cooling Mode LVG WTR TEMP -12 -7 .9 -5.9 -2.9 -0.9 to -8 to -6 to -3 to -1 to 1 R22 83 84 85 86 87 % HPC R404a 78 79 81 82 83 R134a 83 84 85 86 87

1.1 to 3 88 84 88

3.1 to 5 89 85 89

5.1 to 10 90 87 90

Note: For High Ambient unit, add 3% (digit 26=C for RTAA 300/400, RTAB or RTRA) or (digit 12=H for RTAA 200). For RTAD High Ambient (digit 17 = H or W), add 5%. Whatever is the value of digit 17 , if digit 19 = Q and : -if RTAD 85 or RTAD 115 and digit 12 = N, then set to 95%. -if RTAD 100 or RTAD 125 and digit 12 = H, set to 95%. Water Cooled Units RTWA + RTA HR R22 R404a R22 (RTXA heating) R134a Mines 85 81 90 80 TUV 80 74 80 ISPESL 80 74 88 80

% HPC

Water Cooled Units RTWB/RTUB % HPC = 90

RTAA-SVB003-E4

Table 3: Compressor Tons Except RTWB/RTUB and RTAD


107 CHHN 060 (GP 60) 50 60 108 CHHB 70 (IS 70) 60 70 109 CHHB 85 (IS 85) 70 85 UNIT 110 207 209 210 CHHB 100 CHHN 35 CHHN 40 CHHN 50 (IS100) (GP 35) (GP 40) (GP 50) 85 30 35 40 100 35 40 50 CHHN 35 CHHN 40 CHHN 40 (GP 35) (GP 40) (GP 40) 30 35 35 35 40 50 211 CHHN 50 (GP 50) 40 50 CHHN 50 (GP 50) 40 50

Compressor A Configuration A 50 Hz 60 Hz Compressor B Configuration B 50 Hz 60 Hz

Compressor A Configuration A 50 Hz 60 Hz Compressor B Configuration B 50 Hz 60 Hz

212 CHHN 60 (GP 60) 50 60 CHHN 60 (GP 60) 50 60

213 CHHB 70 (IS 70) 60 70 CHHB 70 (IS 70) 60 70

UNIT 214 CHHB 85 (IS 85) 70 85 CHHB 70 (IS 70) 60 70

215 CHHB 85 (IS 85) 70 85 CHHB 85 (IS 85) 70 85

216 CHHB 100 (IS 100) 85 100 CHHB 85 IS 85) 70 85

217 CHHB 100 (IS 100) 85 100 CHHB 100 (IS 100) 85 100

Compressor A Configuration A 50 Hz 60 Hz Compressor B Configuration B 50 Hz 60 Hz Compressor C Configuration C 50 Hz 60 Hz Compressor D Configuration D 50 Hz 60 Hz

322 CHHB 70 (IS 70) 60 70 CHHB 70 (IS 70) 60 70 CHHB 85 (IS 85) 70 85 -

324 CHHB 85 (IS 85) 70 85 CHHB 85 (IS 85) 70 85 CHHB 100 (IS 100) 85 100 -

328 CHHB 100 (IS 100) 85 100 CHHB 100 (IS100) 85 100 CHHB 100 (IS 100) 85 100 -

UNIT 220 CHHN 60 (GP 60) 50 60 CHHN 60 (GP 60) 50 60 CHHN 60 (GP 60) 50 60 CHHN 60 (GP 60) 50 60

430 CHHB 85 (IS 85) 70 85 CHHB 85 (IS 85) 70 85 CHHB 85 (IS 85) 70 85 CHHB 85 (IS 85) 70 85

432 CHHB 100 (IS 100) 85 100 CHHB 100 (IS 100) 85 100 CHHB 85 (IS 85) 70 85 CHHB 85 (IS 85) 70 85

434 CHHB 100 (IS 100) 85 100 CHHB 100 (IS 100) 85 100 CHHB 100 (IS 100) 85 100 CHHB 100 (IS 100) 85 100

RTAA-SVB003-E4

Table 3: Compressor Tons for RTWB/RTUB Only


Unit Compressor 1 Configuration circuit 1 (50 Hz) Compressor 2 Configuration circuit 2 (50 Hz) Compressor 1 Configuration circuit A (50 Hz) Compressor 2 Configuration circuit B (50 Hz) 207 K1 30 K1 30 216 M2 70 M1 60 208 K2 35 K2 35 217 M2 70 M2 70 210 L1 40 L1 40 218 N1 85 M2 70 211 L2 50 L1 40 220 N1 85 N1 85 212 L2 50 L2 50 222 N2 100 N1 85 214 M1 60 M1 60 224 N2 100 N2 100

Table 3 : RTAD
85 L1 40 L1 40 Unit 100 L2 50 L2 50 115 M1 60 M1 60 125 M2 70 M2 70

Compressor A Configuration circuit 1 (50 Hz) Compressor B Configuration circuit 2 (50 Hz)

RTAA-SVB003-E4

Table 4: Fan Configuration


0 to 40C
Number of Fans Number of Fans

-18 to 40C HA Option


Number of Fans

0 to 40C
Number of Fans

0 to 46C

RTAB

2-speed Motor NNSB d d d d d d d d d d d d e d e d d d e d e d d d d e e d e d d d e d e X X X X X X X X X A X A X A X A X A X A X A/X A/X A A X X A X A/X A/X A X A X

2-speed Motor NNSB e e e e e e e e e d d d d d d d d d d d d d d d d d d d d d d d d A/X A/X A/X A/X A/X A/X A/X A/X A/X A X A X A X A X A X A X A/X A/X A A X X A X A/X A/X A/X A/X

2-speed Motor NNSB d d d d d d d d d d e e d e e d d e e X X X X X X X X X X X X X X X X X X X

2-speed Motor NNSB

108 R134a R22/R404A Standard R22/R404A oversize 109 R134a R22/R404A standard R22/R404A oversize 110 R134a R22/R404A standard R22/R404A oversize 207 R134a R22/R404A standard R22/R404A oversize 209 R134a R22/R404A standard R22/R404A oversize 210 134a R22/R404A standard

R22/R404A oversize 211 R134a R22/R404A standard R22/R404A oversize

circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1/2 circuit 1/2 circuit 1/2 circuit 1/2 circuit 1/2 circuit 1/2 circuit 1/2 circuit 1/2 circuit 1/2 circuit 1/2 circuit 1/2 circuit 1/2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1/2 circuit 1/2 circuit 1 circuit 2 circuit 1/2 circuit 1/2 circuit 1/2 circuit 1/2

4 4 6 5 5 6 6 6 6 2 2 4 2 4 2 2 2 4 2 5 3 3 2 5 4 3 2 5 3 3 3 5 3 5 3

4 4 5 5 5 5 5 5 5 2 2 2 2 2 2 2 2 2 2 3 3 3 2 3 2 3 2 3 3 3 3 3 3

4 4 6 5 5 6 6 6 6 2 2 2 2 2 3 3 2 3 2

3 3

d e

X X

3 3

d e

X X

3 3 3 3

d d e e

X X X X

3 3 3 3 3

e d d e e

X X X X X 4 4 4 d d d X X X

RTAA-SVB003-E4

Table 4: Fan Configuration (continued)


0 to 40C
Number of Fans Number of Fans

-18 to 40C HA Option 2-speed Motor NNSB d d d d e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e A X A X X X


Number of Fans

0 to 40C
Number of Fans

0 to 46C

RTAB

2-speed Motor NNSB d d d e d d e e d d e e d d e e d d e e d d e e e e d d e e d d d d d d d d d d d d d d A X A X X X

2-speed Motor NNSB d e d d e e X X X X

2-speed Motor NNSB d d X X

212 R134a R22/R404A standard R22/R404A oversize 213 R134a R22/R404A Standard 214 R134a R22/R404A standard 215 R134a R22/R404A standard 216 R134a R22/R404A standard R134a oversize 217 R134a R22/R404A standard R134a oversize 220 R134a R22/R404A standard 324 R134a 328 R134a 430 R134a 432 R134a 434 R134a

circuit 1/2 circuit 1/2 circuit 1/2 circuit 1/2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2

3 3 5 3 4 4 3 3 4 4 3 3 5 4 3 3 5 5 4 3 5 4 4 4 4 4 5 5 4 4 4 4 5 5 5 3 6 3 5 5 6 5 6 6

3 3 3 3 4 4 3 3 4 4 3 3 5 4 3 3 5 5 4 3 5 4 4 4 4 4 5 5 4 4 4 4 5 5 5 3 5 3 5 5 5 5 5 5

3 3 4 4 4 4

4 4

4 4

e e

4 4

e e

5 4

d d

5 5

d d

4 4 5 5 5 3 6 3 5 5 6 5 6 6

d d d d d d d d d d d d d d

Note: NNSB: Option Day/Night: X without, A with

RTAA-SVB003-E4

Table 4: Fan Configuration (continued)


0 to 40C
Number of Fans Number of Fans

-18 to 40C
Number of Fans

0 to 46C

RTAA 213 standard oversize 214 standard oversize 215 216 217 standard standard standard oversize 322 standard oversize 324 standard oversize 328 430 standard standard oversize 432 standard oversize 434 standard circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit1 circuit 2

4 4 4 4 4 4 5 4 4 4 5 4 5 5 5 5 4 4 4 6 4 6 5 6 5 6 4 4 5 4 5 4 5 5 5 5

2-speed Motor d d d d e e d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d

NNSB

4 4 4 4 4 4 5 4 4 4 5 4 5 5 5 5 4 4 4 5 4 5 5 5 5 5 4 4 5 4 5 4 5 5 5 5

2-speed Motor e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e

NNSB

4 4 4 4 4 4 5 4 4 4 5 4 5 5 5 5 4 4 4 6 4 6 5 6 5 6 4 4 5 4 5 4 5 5 5 5

2-speed Motor NNSB d d d d e e d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d

10

RTAA-SVB003-E4

Table 4: Fan Configuration (continued)


0 to 40C R134a
Number of Fans

-18 to 40C R22 - 404a


Number of Fans

R134a
Number of Fans

R22 - 404a
Number of Fans

RTUA

RTCA 108 109 113 115 111 116 208 209 211 213 213 215 216 circuit 1 circuit 1 circuit 1 circuit 1 circuit 1 circuit 1 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2 circuit 1 circuit 2

108 109 110

207 209 211 212 213 215 216 217

4 4 4 4 4 6 4 4 4 4 5 5 4 4 4 4 4 4 4 4

2-speed Motor d d e e d d d d d d d d d d d d d d d d

4 4 4 4 4 6 4 4 4 4 5 5 4 4 4 4 4 4 4 4

2-speed Motor d d e e d d d d d d d d d d d d d d d d

4 4 4 4 4 6 4 4 4 4 5 5 4 4 4 4 4 4 4 4

2-speed Motor e e e e e e d d d d d d d d e e e e e e

4 4 4 4 4 6 4 4 4 4 5 5 4 4 4 4 4 4 4 4

2-speed Motor e e e e e e d d d d d d d d e e e e e e

RTRA 6 to 40C -18 to 40C 15 to 40C circuit 1 circuit 1 circuit 1

107 Number of fans 2-speed motor 5 e 5 d 4 d

108 to 110 Number of fans 2-speed motor 4 e 4 d 4 d

RTXA
Number of Fans

209
Number of Fans

210
Number of Fans

211
Number of Fans

212

0 to 40C 0 to 46C

circuit 1 circuit 2 circuit 1 circuit 2

3 3 3 3

2-speed e e e e

3 2 3 2

2-speed e e e e

3 3 3 3

2-speed e e e e

4 4 4 4

2-speed e e e e

RTAA-SVB003-E4

11

Table 4 : RTUB
Variable speed fan circuit 1 : Disable Variable speed fan circuit 2 : Disable Number of fans circuit 1 : 4 Number of fans circuit 2 : 4 Low ambient Unit, two speed motor : Disable
Con temp range Digit 17 L -W Cond fan / motor configuration Digit 19 X-P L Q X-P L Q X-P L Q X-P L Q X-P L Q X-P L Q X-P L Q X-P L Q X-P L Q X-P L Q X-P L Q X-P L Q

RTAD Digit 5-6-7 85

Variable speed fan Cirt. 1 d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d Cirt. 2 d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d

Cond. Digit 12 N

N-H

100-115 125

L -W

N-H

85

L -W

N-H

100

L -W

N-H

115

L -W

N-H

125

L -W

N-H

Low Number of fans ambient unit 2 speed Cirt. 2 motor Cirt. 1 d 3 3 d d 2 2 e 3 3 d e 2 2 d d d 3 3 e d e d d d 3 3 e d e d 4 4 d d 3 3 d 4 4 d e 3 3 d d d 4 4 d d d d 5 5 d d 4 4 d 5 5 d d 4 4

12

RTAA-SVB003-E4

Table 5: Current Overload


REFRIGERANT R22 - R404a COMPRESSOR CHHN 50 CHHN 60 CHHB 70 81 98 123 01 01 02 10000 11101 10001 16 29 17 80 97 117 01 01 02 01111 11101 01101 15 29 13 79 97 113 01 01 02 01111 11101 01011 15 29 11 145 176 213 02 03 04 11101 10110 01101 29 22 13 100 123 148 02 02 02 00000 10001 11110 00 17 30 83 101 122 01 01 02 10010 11111 10000 18 31 16 175 212 255 03 04 04 10110 01100 11010 22 12 26

380/50/3

400/50/3

415/50/3

220/50/3

380/60/3

460/60/3

220/60/3

RLA (A) CT extension Dip switch UCM Setup RLA (A) CT extension Dip switch UCM Setup RLA (A) CT extension Dip switch UCM Setup RLA (A) CT extension Dip switch UCM Setup RLA (A) CT extension Dip switch UCM Setup RLA (A) CT extension Dip switch UCM Setup RLA (A) CT extension Dip switch UCM Setup

CHHN 35 62 10 10001 17 60 10 01111 15 58 10 01111 15 109 02 00111 07 76 01 01011 11 62 10 10001 17 129 02 10100 20

CHHN 40 69 10 11001 25 68 10 11001 25 67 10 11000 24 124 02 10010 18 86 01 10101 21 70 10 11010 26 148 02 11110 30

CHHB 85 141 02 11011 27 134 02 11000 24 129 02 10101 21 244 04 10111 23 169 03 10100 20 140 02 11011 27 292 05 01000 08

CHHB 100 165 03 10010 18 157 03 01110 14 151 03 01011 11 285 05 00110 06 198 03 11110 30 164 03 10001 17 343 05 10101 21

RTAA-SVB003-E4

13

Table 5: Current Overload (continued)


REFRIGERANT R134a COMPRESSOR CHHN 50 CHHN 60 CHHB 70 57 71 86 10 10 01 01011 11100 10101 11 28 21 56 68 82 10 10 01 01010 11001 10100 10 25 20 55 68 80 10 10 01 01000 11000 01111 08 24 15 102 123 149 02 02 02 00010 10001 11111 02 17 31 70 86 102 10 01 02 11010 10101 00001 26 21 01 58 70 85 10 10 01 01101 11010 10101 13 26 21 122 148 177 02 02 03 10001 11110 10110 17 30 22

380/50/3

400/50/3

415/50/3

220/50/3

380/60/3

460/60/3

220/60/3

RLA (A) CT extension Dip switch UCM Setup RLA (A) CT extension Dip switch UCM Setup RLA (A) CT extension Dip switch UCM Setup RLA (A) CT extension Dip switch UCM Setup RLA (A) CT extension Dip switch UCM Setup RLA (A) CT extension Dip switch UCM Setup RLA (A) CT extension Dip switch UCM Setup

CHHN 35 43 09 10100 20 42 09 10011 19 41 09 10001 17 76 01 01011 11 52 10 00011 03 43 09 10100 20 92 01 11001 25

CHHN 40 49 09 11101 29 48 09 11100 28 47 09 11011 27 87 01 10110 22 60 10 01111 15 50 09 11111 31 104 02 00100 04

CHHB 85 CHHB 100 99 112 01 02 11100 01010 28 10 90 108 01 02 11011 01001 27 09 90 106 01 02 10110 00100 22 04 171 196 03 04 10001 00110 17 06 112 139 02 02 01001 11001 09 25 98 111 01 02 11011 01001 27 09 204 240 03 04 11110 10100 30 20

RTAD, RTWB and RTUB VOLTAGE RLA (A) CT extension Dip switch UCM Setup RLA (A) CT extension Dip switch UCM Setup RLA (A) CT extension Dip switch UCM Setup K1 57 Ti 10 01011 11 54 Ti 10 00111 07 52 Ti 10 00011 03 K2 66 Ti 10 10110 22 63 Ti 10 10011 19 61 Ti 10 10000 16

380/50/3

400/50/3

415/50/3

REFRIGERANT R134a COMPRESSOR L1 L2 M1 84 100 117 Ti 01 Ti 01 Ti 02 10011 11111 01101 19 31 13 80 95 111 Ti 01 Ti 01 Ti 02 01111 11100 01001 15 28 09 77 92 107 Ti 01 Ti 01 Ti 02 01100 11001 00110 12 25 06

M2 142 Ti 02 11100 28 135 Ti 02 11000 24 130 Ti 02 10110 22

N1 171 Ti 03 10100 20 162 Ti 03 10000 16 156 Ti 03 01101 13

N2 206 Ti 04 1001 09 196 Ti 04 00110 06 189 Ti 04 00010 02

14

RTAA-SVB003-E4

Module MCSP (all units)

EXV Module (only RTXA)

IPC Address Dip-switch Settings: Compressor A (A20-1) Compressor B (A20-2) Compressor C (A20-3) Compressor D (A20-4) EXV master (A52-1) - cooling EXV slave (A52-2) - heating

SW1-1 0 0 1 1 0 0

SW1-2 0 1 0 1 0 1

RTAA-SVB003-E4

15

Literature Order Number File Number Supersedes Stocking Location

RTAA-SVB003-E4 SV-RF-RTAA-SVB003-0402 L80 SB 050 E 1099 La Crosse

The Trane Company An American Standard Company www.trane.com For more information contact your local sales office or e-mail us at comfort@trane.com

Since The Trane Company has a policy of continuous product and product data improvement, it reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this bulletin. Socit Trane Socit Anonyme au capital de 61 005 000 Euros Sige Social: 1 rue des Amriques 88190 Golbey France Siret 306 050 188-00011 RSC Epinal B 306 050 188 Numro didentification taxe intracommunautaire: FR 83 3060501888