Heating System Detail

Project #:1600 SF Shop May 1, 2011

Project Information
Project #: Name: Location: 1600 SF Shop 40 x 40 Shop Notes: Sample Layout for 40x40 shop with a heat loss density of 30 BTUH maximum.

Design Conditions and Summary


Load Calculation Method: Floorplans / Levels: Ground Floor Total Area: User Entered (Manual) 1,626 ft 1,626 ft Total Tubing Lengths: 1/2" RadiantPEX+ Barrier Total RH Circuits: Total Manifolds: Total Zones: Fluid Type: Total Tubing Volume: Glycol Volume (40%): Building Heat Loss: 2,567 ft 9 1 1 40% Glycol 24.64 USG 9.86 USG Radiant Heating: Radiant Back Losses: Baseboard: Forced Air: Other: Total Heating Load: 47,166 9,433 0 0 0 56,600 Btu/hr Btu/hr Btu/hr Btu/hr Btu/hr Btu/hr 47,166 Btu/hr

Zone Heating Summary


Zone # 101 Total Area 1,626 1,626 Heating Types RH (M) RH (M) RH Circuits 9 9 Flowrate 8.26 8.26 Head Loss 14.2 14.2 Rooms Room 1

Length = ft Area = ft RH = Radiant Floor Heating

Temperature = F BB = Baseboard

Heat Loss = Btu/hr FA = Forced Air

Unit Heat Loss = Btu/hrft Rv = hrftF/btu O = Other Heating SM = Snowmelt N = Not Heated

Created using LoopCAD 2011 Watts Radiant(US) Version:2.4.0297

See end of report for important Notes and Disclaimers.

Page 1 of 3

Name:40 x 40 Shop Project #:1600 SF Shop

Heating System Detail


May 1, 2011

Room Heating Summary


Ground Floor Room 1
Total Area: Heated by: Room Temperature: 1,626 ft RH (M) 68 F Radiant Heating: Heated Area: Tubing in Floor: Circuits in Room: Tube Spacing: Required Surface Temp: Required Water Temp: Est. Peak Output: 1,572 2,567 9 6/8 84 123 47,589 ft ft Load/Loss Summary: Room Design Load: Radiant Load: Baseboard Load: Forced Air Load Other Load: Radiant Back Loss: Recovered Back Loss: Total Heat Loss: 47,166 Btu/hr 56,600 0 0 0 Btu/hr Btu/hr Btu/hr Btu/hr

F F Btu/hr

9,433 Btu/hr 0 Btu/hr 56,600 Btu/hr

Radiant Heating Details


Manifold Summary
Manifold Name Manifold 1 Total # Zones 1 1 # Circuits 9 9 Flowrate 8.26 8.26 Head Loss 14.2 14.2 Required Temp. 123 123 Supplied Temp. 123 Max Temp. Drop 15 Manifold Type 1" Stainless Steel Manifold Control Type Manifold # Actuators 0 0

Length = ft Area = ft RH = Radiant Floor Heating

Temperature = F BB = Baseboard

Heat Loss = Btu/hr FA = Forced Air

Unit Heat Loss = Btu/hrft Rv = hrftF/btu O = Other Heating SM = Snowmelt N = Not Heated

Created using LoopCAD 2011 Watts Radiant(US) Version:2.4.0297

See end of report for important Notes and Disclaimers.

Page 2 of 3

Name:40 x 40 Shop Project #:1600 SF Shop

Heating System Detail


May 1, 2011

Tubing Circuit Details


Manifold 1
Circuit A-1 A-2 A-3 A-4 A-5 A-6 A-7 A-8 A-9 Total Rooms Served Room 1 Room 1 Room 1 Room 1 Room 1 Room 1 Room 1 Room 1 Room 1 Total Length 301 290 276 286 297 269 273 270 306 2,567 Tube Spacing 8/8 8/8 8/8 8/8 8/8 8/8 8/8 8/7 8/7 Area Covered 185 182 170 179 189 171 176 151 169 1,572 Tubing 1/2" RadiantPEX+ Barrier 1/2" RadiantPEX+ Barrier 1/2" RadiantPEX+ Barrier 1/2" RadiantPEX+ Barrier 1/2" RadiantPEX+ Barrier 1/2" RadiantPEX+ Barrier 1/2" RadiantPEX+ Barrier 1/2" RadiantPEX+ Barrier 1/2" RadiantPEX+ Barrier Flowrate 0.97 0.95 0.89 0.94 0.99 0.89 0.92 0.81 0.91 8.26 Head Loss 13.0 12.1 10.3 11.6 13.2 10.0 10.7 8.4 11.8 13.2 Temp Drop 15 15 15 15 15 15 15 15 15 15 Peak Radiant Output* 5,588 5,467 5,125 5,389 5,674 5,143 5,294 4,658 5,252 47,589 Actuator No No No No No No No No No 0

* Radiant Output does not include downward or back losses.

Disclaimers
The calculated values shown in this report are based on the data input by the user of the software. Inaccurate or erroneous data input will result in inaccurate or erroneous results. You are strongly advised to review all input data carefully, and to have the calculated results reviewed by an experienced heating professional to ensure reasonableness and suitability for your application.
IN NO EVENT WILL AVENIR SOFTWARE INC. (AVENIR) OR ITS AFFILIATES BE LIABLE UNDER ANY CONTRACT, NEGLIGENCE, STRICT LIABILITY OR OTHER LEGAL OR EQUITABLE THEORY FOR ANY CONSEQUENTIAL, INCIDENTAL, INDIRECT OR SPECIAL OR PUNITIVE DAMAGES WHATSOEVER (INCLUDING, BUT NOT LIMITED TO, DAMAGES FOR LOSS OF BUSINESS PROFITS, BUSINESS INTERRUPTION, LOSS OF BUSINESS INFORMATION OR DATA AND THE LIKE), EVEN IF SUCH PARTY HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. AVENIRS CUMULATIVE LIABILITY FROM ANY CAUSE RELATED TO OR ARISING FROM THE USE THIS REPORT, AND REGARDLESS OF THE FORM OF THE ACTION, SHALL BE LIMITED TO NO GREATER THAN THE AMOUNT OF FEES PAID TO AVENIR UNDER THE SOFTWARE LICENSE AGREEMENT.

Length = ft Area = ft RH = Radiant Floor Heating

Temperature = F BB = Baseboard

Heat Loss = Btu/hr FA = Forced Air

Unit Heat Loss = Btu/hrft Rv = hrftF/btu O = Other Heating SM = Snowmelt N = Not Heated

Created using LoopCAD 2011 Watts Radiant(US) Version:2.4.0297

See end of report for important Notes and Disclaimers.

Page 3 of 3