Вы находитесь на странице: 1из 24

YAEP

HIGH AMBIENT
AIR COOLED LIQUID CHILLER

PRODUCT CATALOGUE

STYLE A
REFRIGERANT TYPE: R22, R407C
MODELS: 50 Hz
Cooling Capacities: 294 to 1566 kW
84 to 446 Tons

EMEA
YORK

CONTENTS
Available Models and Nominal Cooling Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Accessories and Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Operating Limitations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Refrigerant Flow Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
YAEP R22 Cooling Capacities - Metric Data (C kW/kW) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
YAEP R22 Cooling Capacities - Imperial Data (F Tons/kW) . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
YAEP R407C Cooling Capacities - Metric Data (C kW/kW) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
YAEP R407C Cooling Capacities - Imperial Data (F Tons/kW) . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Physical Data - R22 Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Physical Data - R407C Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Electrical Data - R22 Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Electrical Data - R407C Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Power Supply Connections (Main Panel and Auxiliary Panel) . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Control Connections (Main Panel and Auxiliary Panel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Dimensions YAEP 08L and 09L. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Dimensions YAEP 44M - 77XC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Dimensions YAEP 77XF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Dimensions YAEP 88X - 99X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Dimensions YAEP 5555S - 7777XC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Dimensions YAEP 7777XF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Dimensions YAEP 8888X - 9999X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Nomenclature

YAEP99XD9B50PA
1

BASE PRODUCT TYPE


Y

: York
A

7
: Comp. 1/3

: Air Cooled
E

COMPRESSOR SIZE

: Export Series

4, 5,

: P Series

6, 7,

Compressor

8, 9

: Comp. 2/4

COOLER
S
L, M, S, X

8
CONDENSER
C
A, B, C, D, F

9
FAN CODE

10

11

REFRIGERANT

7, 9

: R407C

: R22

12

POWER SUPPLY
50
50

13

STARTING
P

DESIGN LEVEL
A

: 380/400/415 V

: Part Wind

3 phase, 50 Hz

: Star Delta Closed

: Star Delta Open

: Engineering
Change
or PIN Level

YAEP
AIR COOLED
CHILLERS
R22 and R407C
Refrigerants
50 Hertz Power Supply
Cooling Capacities
294 to 1566 kW
84 to 446 Tons
The YAEP range of chillers are designed
for water cooling. Units are available with
one, two or four refrigerant circuits.
All units are designed to be located
outside on the roof of a building or at
ground level.
One and two refrigerant circuit units have
one or two compressors and a cooler
mounted on a single base with a single
power and control panel mounted at the
end of the unit.
Four refrigerant circuit units are
constructed and shipped in two sections,
each having two compressors with a
cooler and a power and control panel
mounted at the end of the section.
Four circuit units require the installation of
a two wire communication link between
control panels and a mixed leaving liquid
temperature sensor.

AVAILABLE MODELS & NOMINAL COOLING CAPACITIES


R22 Models - 50 Hertz
Model YAEP
Capacity (kW)
Capacity (Tons)

1 Circuit Units
08LA7C
09LC9C
298
365
85
104

Model YAEP

44MA7C
Capacity (kW)
312
Capacity (Tons)
89

55SC7C
403
115

2 Circuit Units
66SC9C
77XC9C
88XB7C
438
537
610
125
153
175

99XB7C
717
205

99XD9C
778
223

4 Circuit Units
Model YAEP 5555SC7C 6666SC9C 7777XC9C 8888XB7C 8899XB7C 9999XD9C
Capacity (kW)
805
877
1074
1221
1328
1566
Capacity (Tons)
231
251
307
349
380
446

R407C Models - 50 Hertz


Model YAEP
Capacity (kW)
Capacity (Tons)

1 Circuit Units
08LC7B
09LC9B
294
349
84
100

Model YAEP

44MC7B
Capacity (kW)
325
Capacity (Tons)
93

55SC9B
393
112

2 Circuit Units
66SC9B
77XC9B
77XF7B
430
492
532
123
141
152

88XD7B
629
180

99XD9B
733
210

4 Circuit Units
Model YAEP 5555SC9B 6666SC9B 7777XC9B 7777XF7B 8888XD7B 8899XD7B 9999XD9B
Capacity (kW)
785
859
984
1065
1258
1344
1465
Capacity (Tons)
225
246
281
305
360
385
419
Cooling capacities (kW) at 7C leaving liquid temperature and 35C ambient.
Cooling capacities (Tons) at 45F leaving liquid temperature and 95F ambient.

FEATURES

BENEFITS

Manufactured to ISO 9001/EN 29001.

High standard of quality control.

Full factory run test.

Operating quality control.

2 or 4 Refrigerant circuit models with a


single compressor per circuit.

System stand-by security.

Thermostatic Expansion Valves

Reliable operation at high ambient


temperatures without sacrificing
efficiency.

Constructed from heavy gauge painted


galvanised steel.

Long life durability and weather


protection.

Industrial type serviceable semi-hermetic


reciprocating compressor with replaceable
cylinder liners.

Long life, reliable compressor


which can be repaired on site.

Separate power and control compartments


with lockable doors.

Operator safety.

Residual current circuit breaker.

Operator safety.

SPECIFICATION
General
Units are completely assembled with all
interconnecting refrigerant piping and
internal wiring, ready for field installation.
The unit is pressure-tested, evacuated
and fully charged with refrigerant and
includes an initial oil charge. After
assembly, a full run test is performed, with
water flowing through the cooler, to verify
that each refrigeration circuit operates
correctly.

The unit base and frame is of


heavy-gauge, galvanised steel, with a
baked-on enamel coloured Desert Sand
(RAL 1019).
Compressors
The unit has accessible, semi-hermetic,
reciprocating compressors. All rotating
parts are statically and dynamically
balanced.

Motor - The compressor motors are


refrigerant gas cooled, with integral
temperature-sensing solid state overload
protection in each phase. The terminal
boxes are to IP55 weather protection.
Part Winding starting is fitted as standard.
Housing - The compressor housing is
cast iron, and contains: removable
cylinder heads with internal muffling,
discharge service valve, optional suction
service valve, crankcase sight glass and
heater, oil and suction strainers, and
internal relief valves.

Page 1
Doc. No. PCYAEP-50/03.04/GB

Crankshaft - The crankshaft is ductile


(nodular) iron, drilled for positive oil
distribution, with integral counterweights
for balancing. The main bearings are
insert type, steel-backed babbitt. The
thrust bearing is bronze.
Cylinder Assemblies - Suction and
discharge valves are high-quality,
non-flexing, stainless steel. The pistons
are aluminium alloy with two piston rings.
The connecting rods are aluminium alloy
with integral bearing surfaces on both
ends. Cylinder liners are removable.
Lubrication - The lubrication is force-fed
by a reversible oil pump to all crankshaft
and bearing surfaces and filtered through
a fine mesh stainless steel oil strainer.
Capacity Control - Capacity control is
provided by, solenoid-actuated, capacity
control valves which are controlled by the
microprocessor centre. These inject high
pressure oil to lift pins that close the
cylinder suction valves when a load
requirement exists. Gas flow is sufficient
at all times to cool the motor.
Isolation - Each compressor is mounted
on isolator pads to reduce vibration
transmission to the structure.
Cooler(s)
The single/multi-circuit cooler is the
direct- expansion type, with the
refrigerant in the tubes and chilled liquid
flowing through the baffled shell.
The design working pressure of the shell
is 10.3 bar (150 psi), and 16.2 bar (235
psi) for the tube side. The refrigerant side
is constructed and tested in accordance
with CE/PED pressure vessel code
requirements. ASME pressure vessels
are available on two and four refrigerant
circuit models.
The water baffles are constructed of
galvanised steel to resist corrosion. The
removable heads allow access to the
internally enhanced, seamless, copper
tubes. Vent and drain connections are
included. Standard cooler connections
are Victaulic nozzles.
The cooler is covered with 19 mm (3/4
inch) flexible, closed-cell, UV stable,
colour co-ordinated foam insulation. Each
circuit is protected by a relief valve.
An optional cooler heater mat, controlled
by a separate thermostat, provides freeze
protection for the cooler down to -29C
ambient.
Condenser
Coils - The condenser coils are seamless
copper tubes, arranged in staggered
rows, mechanically expanded into ripple
profile aluminium fins. Integral subcooling
is included. The design working pressure
of the coil is 31 bar (450 psi).
Fans - The condenser fans are U.V.
stable polypropylene, high efficiency,
airfoil-type fan blades directly driven by
independent motors, and positioned for
vertical air discharge.
Page 2
Doc. No. PCYAEP-50/03.04/GB

The fan guards are constructed of


heavy-gauge wire hot dipped galvanized
coated steel. After construction the fan
deck and cowl are hot dipped galvanized
prior to assembly. (Colour co-ordinated
paint finish is available as an extra). All
blades are dynamically and statically
balanced for vibration-free operation.
Motors - The fan motors are Totally
Enclosed Air-Over, squirrel-cage type,
current protected. They feature ball
bearings that are double sealed and
permanently lubricated.
Refrigerant Circuits
Unit piping is ACR copper with brazed joints.
The liquid line includes: a shut off valve with
charging
port,
sightglass
with
moisture-indicator, thermal expansion valve
(direct acting, max-operating pressure),
solenoid valve, and filter drier. The entire
suction line, the liquid line between the
expansion valve and the cooler, are
insulated with flexible, UV stable colour
coordinated closed-cell, foam insulation.
Compressor low, high and oil pressure
transducers plus manual high pressure
cut-outs are located on the compressor
and system pipework with Econoseal all
weather electrical connectors.
Power And Control Panel(s)
All controls and motor starting equipment
necessary for full unit operation are
factory wired and functionally tested. One
and two refrigerant circuit units have a
sigle power and control panel and four
circuit units have a two power and control
panels (main and auxiliary).
Each panel is divided into sections; with
seperate power sections serving each
refrigerant ciruit, a conrol section and a
common input section.
Components are mounted on galvanised
steel back plates, and enclosed in the
relevant section of the galvanised steel
enclosure.
Separate doors are provided for each
section. All doors are hinged, lockable
with door stays and are designed to IP55
weather protection. Enclosure and doors
are finished in zinc phosphate pre-treated
baked enamel coloured Desert Sand.
Each
Power
Section
Contains:
Partwind compressor starting contactors,
system fuses, fan contactors, fan manual
motor starters and control interface relays
(CE Compliant).
The Common Input Section Contains:
Non-fused
disconnect
switch
for
customer single point power supply
connection. Transformer and wiring to
allow control voltage to be internally
derived (CE Compliant).
The
Control
Section
Contains:
microprocessor board, power supply
board and relay board. The relay board
contains the control circuit serving
compressor
solenoids,
crankcase
heaters and compressor and fan
contactor coils.

Controls
The microprocessor based control
system is capable of multi-circuit control
to maintain chilled liquid temperature.
Compressor
starting/stopping
and
loading/
unloading
decisions
are
performed by the microprocessor to
maintain leaving water temperature.
These decisions are a function of
temperature deviation from setpoint and
rate of change of temperature.
Control System Keypad and Display
(main power and control panel only)
The backlit 40 character display (LCD, 2
lines of 20 characters) allows the operator
to view system operating parameters as
well as access programmed information
already in memory.
The keypad is provided for programming
and accessing setpoints, pressures,
temperatures, motor current, cut-outs,
daily schedule, options and fault
information.
The standard controls shall include:
automatic pump down at shutdown and
recycling pumpdown, run signal contacts,
demand load limit from external building
automation system input, remote reset
liquid temperature reset input, unit alarm
contacts, chilled liquid pump control,
automatic or manual reset after power
failure, automatic system optimisation to
match operating conditions, software
stored in non-volatile memory (EPROM)
to eliminate chiller failure due to AC power
failure. Programmed Setpoint shall be
retained in a lithium battery backed RTC
memory for a minimum of 5 years.
For each circuit, the following items shall
be displayed in Metric (C and Bar) or
Imperial (F and psi) units :

Return and leaving chilled liquid, and


ambient temperature.

Day, date and time. Daily start/stop

times. Holiday and Manual Override


status.
Compressor operating hours and
starts. Automatic or manual lead/lag.
Lead compressor identification.
Run permissive status. No cooling load
condition. Compressor run status.
Anti-recycle timer and anti-coincident
start timer status per compressor.
System
suction
(and
suction
superheat),
discharge,
and
oil
pressures and temperatures.
Percent full load compressor motor
current. Compressor capacity control
valve input steps.
Cut-out status and set-points for:
supply fluid temperature, low suction
pressure, high discharge pressure and
temperature, high oil temperature, low
and high ambient, high and low current,
and low leaving liquid temperature.
Unloading limit setpoints for high
discharge pressure and compressor
motor current.
Liquid pull-down rate sensitivity (0.3C
to 3C/minute in 0.05C increments).

Status

of:
evaporator
heater,
condenser fans, chilled liquid pump.
Out of range message.
Up to 6 fault shut down conditions.

temperature cut-out, high motor current


unload, anti-recycle time (300 - 600
seconds), local remote control, lead lag
control, power failure reset and average
motor current cut-out.

The
following
settings
can
be
programmed by the operator: high
discharge
pressure
cut-out,
high
discharge pressure unload, suction
pressure cut-out, high ambient cut-out,
low ambient cut-out, leaving liquid

Settings for liquid temperature set-point


reset signal from YORK ISN or building
automation system.

Remote cycling, unloading and chilled


water temperature reset can be
accomplished by voltage free customer
contacts.

ACCESSORIES AND OPTIONS


Single Point Power Supply Option Per Panel
Customer single point power supply
connection to factory fitted terminal block
(in lieu of standard non fused disconnect
swicth). Internal wiring to fuses in each
power section (Not CE Compliant).
Multi Point Power Supply Terminal
Block Option - Per Circuit
Customer supply connection to terminal
block in power section. A separate control
supply is required to the control circuit
switch disconnect (Not CE Compliant).
Multi Point Power Supply Fuse Block
Option - Per Circuit
Customer supply connection to fuse block
in power section. A separate control
supply is required to the control circuit
switch disconnect (Not CE Compliant).
Cable Spreader Box
To separate cores of large multi-core
cable before connection to non-fused
disconnect switch/terminal block when
Single Point Power Supply is specified.
Multi-unit Sequence Control
A separate sequencing control centre to
manage sequencing control of up to eight
chillers in parallel based on mixed leaving
liquid temperature (mounting and
interconnection/wiring
by
others).
(Cannot be fitted when a (BAS) Interface
is
fitted).
See
separate
York
documentation.
Building Automation System (BAS) /
Energy Management System (EMS)
Interface
Provides a means to reset the leaving chilled
liquid temperature from a BAS/EMS.

Consists of a factory mounted PCB to


accept 4 to 20 mA, 0 to 10 Vdc, or dry
contact closure input from the BAS/EMS.
(Cannot be fitted when a Multi-unit
Sequence Control is fitted).
Micro Gateway
Interface to enable communication with
building control systems using BACnet or
MODBUS protocols. See separate York
documentation.
York Talk Translator
Provides central communication with third
party BMS for monitoring and control of all
chillers in the system. See separate York
documentation.

Condenser Coil Fin Protection


Gold Epoxy Coated Aluminium Fins
Offers corrosion resistance in mild coastal
locations (ASTM 287* Test, after 1500 hours
7% weight loss).
Copper Fins
Condenser coils are constructed with copper
fins (ASTM 287* Test, after 1500 hours 17%
weight loss).
* ASTM 287 tests are based on Industrial /
Coastal locations.
Wire Panel Enclosure
Consists of welded-wire-mesh guards
mounted on the exterior of the unit.
Prevents unauthorized access, yet
provides free air flow.
Fan Deck Paint Finish
Paint finish for fan cowl and fan deck in
Desert Sand (RAL1019).
Cooler
Coolers constructed in accordance with
ASME pressure code requirements are
available. This option includes a single
releif valve. Not available for single
refrigerant circuit models.
Handed Evaporator
Simplifies unit layout and water
connection enabling the chillers to be
placed in the best orientation to suite the
site compound.
Double Thickness Insulation
The cooler is covered with 38 mm (1 1/2
inch)
flexible,
UV-stable
colour
co-ordinated closed-cell, foam insulation
for added frost protection.
Cooler Flange Kit
Factory fitted flanges on cooler water
connections to I.S.O. R2084-NP10.
Available in Weld or Victaulic Adaptor.
Companion Flange Kit
Weld/Victaulic Adaptor flanges to match
cooler flange kit ISO 7005-1 PN10
supplied loose for field installation by
contractor. Includes all necessary nuts,
bolts, gaskets, etc.

Added Compressor Capacity Step


(Units with 6 and 8 cylinder compressors
only)
The compressor control system is fitted
with an additional capacity step to
improve part load performance. This
option includes compressor liquid
injection cooling.
Low Ambient Kit
This accessory is factory fitted and
includes all necessary components to
allow chiller operation down to -18C
condenser intake air.
Sun Shield Kit
Sun shield kit to provide shade / air gap
around the power and control panels to
prevent overheating due to solar gain.
Unit Aesthetic Panels
Non acoustically lined infill panels
manufactured from powder painted
galvanised steel to cover the ends of the
condenser coil on the opposite end to the
control panel.
Acoustic Enclosure
A four sided acoustically treated
enclosure fitted around the compressors
and refrigerant pipework below the
condenser coils to reduce sound
emissions.
Suction Service Valves
One ball valve per compressor in the low
pressure (suction) pipework.
Mechanical Gauge Kit
Factory fitted mechanical dial gauges for
discharge, suction and oil pressure
indication in addition to transducer
pressure display.
Anti-Vibration Mounts
Open spring isolator mounts with levelling
screws and fixing down holes, supplied
loose for field installation by contractor.
Lifting Lug Kit
One set of ISO Mk5 cam locs to enable
safe and easy unit handling.

Flow Switch
Switch with 1 inch IPS thread suitable for
10 bar (145 psi) DWP and having gold
contacts for low voltage/ current, to
protect unit from loss of water flow. A flow
switch must be furnished with each unit
for field installation by contractor.

Page 3
Doc. No. PCYAEP-50/03.04/GB

OPERATING LIMITATIONS

TABLE 1

All YAEP Models


Leaving Chilled Liquid Temperature - R22 Units
Leaving Chilled Liquid Temperature - R407C Units
Chilled Liquid Temperature Difference
Air Entering
Standard Units
Condenser
Units with Low Ambient Kit
Electrical Power Supply 380/400/415 V, 3, 50 Hz

Min. C (F) Max. C (F)


4 (39)
12 (54)
6 (43)
12 (54)
3.3 (6)
8 (15)
-4 (25)
52 (125)
-18*(0)
52 (125)
342
440

Model YAEP
Minimum Cooler Flow l/s (gpm)
Maximum Cooler Flow l/s (gpm)
Minimum System Volume l (Usg)

1 Circuit Units
08L
09L
6.0 (95)
6.0 (95)
19 (300)
19 (300)
1310 (375) 1600 (455)

Model YAEP
Minimum Cooler Flow l/s (gpm)
Maximum Cooler Flow l/s (gpm)
Minimum Unit Flow l/s (gpm)
Maximum Unit Flow l/s (gpm)
Minimum System Volume l (Usg)

4 Circuit Units
5555S
6666S
7777X
8888X
9.4 (150)
9.4 (150)
15.8 (250)
15.8 (250)
40.5 (640)
40.5 (640)
50.7 (805)
50.7 (805)
18.8 (300)
18.8 (300)
31.6 (500)
31.6 (500)
81 (1280)
81 (1280) 101.4 (1610) 101.4 (1610)
3235 (920) 3735 (1065) 4335 (1235) 5140 (1465)

44M
7.5 (120)
36.5 (580)
1330 (380)

55S
9.4 (150)
40.5 (640)
1620 (460)

2 Circuit Units
66S
77X
9.4 (150)
15.8 (250)
40.5 (640)
50.7 (805)
1870 (530) 2170 (615)

8899X
15.8 (250)
50.7 (805)
31.6 (500)
101.4 (1610)
5910 (1680)

88X
15.8 (250)
50.7 (805)
2570 (730)

99X
15.8 (250)
50.7 (805)
3130 (890)

9999X
15.8 (250)
50.7 (805)
31.6 (500)
101.4 (1610)
6265 (1785)

4 circuit units are fitted with 2 coolers. The table details flow rate for each cooler and total flow rate for the unit.

FOULING FACTORS

TABLE 2

ALTITUDE FACTORS

TABLE 3

1.000

Comp.
Input
Factor
1.000

600

1970

0.987

1.010

0.998

1200

3940

0.973

1.020

0.993

1800

5905

0.958

1.029

2400

7075

0.943

1.038

Altitude

COOLER

mC/kW

ftF hr/Btu

Capacity
Factor

0.018

0.00012

1.000

Comp.
Input
Factor
1.000

0.044

0.00025

0.994

0.088

0.00050

0.981

Fouling Factor

0.176

0.00100

0.958

0.983

0.352

0.00200

0.910

0.960

Metres

Feet

Capacity
Factor

REFRIGERANT FLOW DIAGRAM


Condenser Coil
Refrigerant
Circuit No 2
Condenser Coil
Refrigerant
Circuit No 1

High Pressure
superheated vapour
Compressor

Fusible
Plug

Low pressure liquid refrigerant enters the cooler and is


evaporated and superheated by the heat energy absorbed from
the chilled water passing through the cooler shell. Low pressure
vapour enters the compressor where pressure and superheat
are increased. Heat is rejected via the air cooled condenser coil
and fans. The fully condensed and subcooled liquid refrigerant
then enters the expansion valve where pressure reduction and
further cooling takes place before returning to the cooler.

Optional
Suction
Service
Valve

High pressure
sub-cooled liquid

Low pressure superheated vapour


Sight TEV
Glass
Filter
Drier

Low pressure
sub-cooled
liquid/vapour

Cooler

Refrigerant Circuit No 2

Page 4
Doc. No. PC010HA/02.02/GB

SELECTION GUIDE

1.
2.
3.
4.

Required cooling capacity.


Required refrigerant.
Design chilled water entering and leaving temperatures.
Design water flow rate if one of the temperatures in item 3 are
unknown.
5. Design condenser entering air temperature. This will normally
be the design summer ambient air temperature unless
location or other factors have an influence.
6. Altitude above sea level.
7. Design cooler fouling factor.
Note: Items 1, 3 and 4 must be linked by the following formulae:
Cooling Capacity (kW) = Range (C) x Flow (litre/sec) x 4.18
Where Range = Entering liquid temperature - Leaving liquid
temperature.
SELECTION METHOD
1. Determine the correct size of chiller by selecting the model
which most closely matches the required capacity at the
design conditions of leaving water temperature and entering
air temperature.
2. Apply correction factors for fouling factor (Table 2) and
altitude (Table 3) to the capacity and power values from the
capacity tables. Ensure the corrected capacity is still
sufficient for requirements.
3. Using the corrected capacity of the selected chiller adjust the
design temperature range, or flow rate, to balance the
formulae shown in "Data Required".
4. Physical and electrical data can now be determined from
Tables 5 and 6.
5. Always re-check that selections fall within the design
limitations specified in Table 1.
CHILLER SAMPLE SELECTION
A 50 hertz R22 chiller is required to cool water from 12 to 7 C
(53 to 44 F) having a cooling capacity of 525 kW (149 Tons) at
a design flow rate of 25 l/s (396 gpm). Other design conditions
applying are:
Ambient air entering condenser:
Fouling Factor:
Altitude:

35C (95F)
0.044m C/kW
(0.00025 ftF hr/Btu)
Sea level

From a cursory examination of capacity Table 4, a model


YAEP77XC9C gives approximately the required capacity:
No correction factors apply therefore, after calculating the flow
rate, the conditions will be as follows:
Cooling Capacity:
Water temperature:
Water flow rate:
Compressor Power:

537 kW (153 Tons)


12 to 7C (Range = 5 C)
53 to 44 F (Range = 9 F)
25.7 l/s (410 gpm)
173 kW

All values are within the operating limits in Table 1.

From Pressure Drop Graph (Figure 2). YAEP77XC9C cooler


water pressure drop = 30.5 kPa (4.4 psi) at the calculated flow of
25.7 l/s. (410 gpm)

FIGURE 2

COOLER WATER PRESSURE DROP

140
120
100

44M

80

77X
88X
99X

60
50

Pressure Drop (kPa)

DATA REQUIRED
To select a YORK YAEP chiller the following information is
required:

40
30

20

10

55S
66S

8
6

08L
09L

5
4
5

10

20

30

40

50 60

Flow Rate (l/S)

Note: Pressure drop applies to each cooler on 4 Circuit Models


(i.e. the total unit flow should be divided by 2 to obtain the flow
rate through each cooler).
Model

Pressure Drop Calculation

08L,
09L

Pressure Drop [kPa] = 0.2133 x (Flow Rate [l/s]1.7018)

44M

Pressure Drop [kPa] = 0.2920 x (Flow Rate [l/s]1.6730)

55S,
Pressure Drop [kPa] = 0.2101 x (Flow Rate [l/s]1.6914)
66S
77X,
Pressure Drop [kPa] = 0.1103 x (Flow Rate [l/s]1.7282)
88X, 99X

Page 5
Doc. No. PCYAEP-50/03.04/GB

YAEP R22 COOLING CAPACITIES - METRIC DATA (C KW/KW)


Model

YAEP
08LA7C

YAEP
09LC9C

YAEP
44MA7C

YAEP
55SC7C

YAEP
66SC9C

YAEP
77XC9C

YAEP
88XB7C

YAEP
99XB7C

YAEP
99XD9C

YAEP
5555SC7C

YAEP
6666SC9C

YAEP
7777XC9C

YAEP
8888XB7C

YAEP
8899XB7C

YAEP
9999XD9C

Condenser Air Entering Temperature C


40
45
Cool
Power
Cool
Power
kW
kW
kW
kW
268
94
255
98
277
95
264
100
285
97
272
102
313
102
300
107
328
106
314
111
332
111
319
116
343
113
329
118
352
115
338
120
385
120
372
127
408
124
392
131

Leaving
Chilled
Liquid
C
5
6
7
10
12
5
6
7
10
12

Cool
kW
293
303
311
340
357
357
364
376
413
436

Power
kW
84
85
87
91
94
99
100
102
106
110

Cool
kW
281
289
298
327
343
345
355
365
400
422

Power
kW
89
90
92
97
100
105
107
108
113
117

5
6
7
10
12
5
6
7
10
12
5
6
7
10
12
5
6
7
10
12
5
6
7
10
12
5
6
7
10
12
5
6
7
10
12

307
316
325
353
374
390
404
417
454
483
435
445
455
497
526
533
545
558
607
640
609
624
638
697
731
698
723
748
805
851
748
776
805
876
921

92
93
95
100
103
110
112
113
119
123
123
125
127
134
139
160
162
164
173
181
176
179
182
192
200
219
223
227
240
248
200
204
208
217
225

296
304
312
339
361
373
388
403
440
468
415
427
438
478
504
499
518
537
581
617
581
596
610
666
700
675
696
717
780
826
724
751
778
847
891

97
99
101
106
110
117
119
121
127
131
130
132
134
142
147
167
170
173
182
190
185
189
192
204
212
231
235
239
253
262
213
217
221
232
239

283
292
300
325
348
364
376
388
424
451
399
409
418
459
485
481
498
515
561
594
550
566
582
635
669
643
664
686
750
796
694
720
745
816
857

102
104
106
111
116
124
126
128
134
138
136
138
140
148
154
174
177
180
190
199
194
198
202
214
224
240
245
250
264
274
227
231
235
246
253

270
278
285
310
335
350
361
372
406
434
376
387
398
437
460
458
476
493
540
571
519
536
553
602
635
614
635
657
718
765
658
683
708
776
821

5
6
7
10
12
5
6
7
10
12
5
6
7
10
12
5
6
7
10
12
5
6
7
10
12
5
6
7
10
12

781
807
834
909
966
869
890
911
993
1051
1066
1090
1115
1214
1280
1218
1247
1276
1394
1462
1307
1346
1386
1502
1582
1495
1553
1611
1751
1842

220
223
227
238
246
247
250
254
268
277
320
324
328
346
361
352
358
364
384
400
395
402
409
432
448
400
408
416
434
450

747
776
805
881
935
830
854
877
956
1009
998
1036
1074
1162
1233
1162
1191
1221
1332
1401
1256
1292
1328
1446
1527
1447
1502
1556
1695
1783

235
238
242
254
262
260
264
268
283
294
334
340
346
364
380
370
377
384
408
424
416
424
431
457
474
426
434
442
464
478

728
752
775
847
903
798
818
837
918
971
962
997
1031
1122
1188
1101
1133
1165
1269
1337
1193
1231
1268
1384
1465
1388
1439
1491
1631
1714

248
252
256
269
276
272
276
280
296
308
348
354
360
380
398
388
396
404
428
448
434
443
452
478
498
454
462
470
492
506

700
722
744
813
869
752
774
795
873
921
916
951
986
1081
1141
1037
1072
1107
1204
1271
1133
1171
1210
1320
1401
1316
1366
1416
1552
1643

30

35

TABLE 4a

46

50

Cool
kW
252
260
269
297
311
315
325
335
368
388

Power
kW
98
100
102
108
112
117
119
121
128
132

Cool
kW
239
248
256
285
298
302
311
320
354
373

Power
kW
102
104
106
112
116
122
123
126
133
138

106
108
110
116
122
130
132
135
143
145
141
143
145
155
160
180
184
188
198
208
204
207
211
224
236
248
254
260
275
286
240
244
248
261
267

267
274
282
307
332
347
357
368
402
430
371
382
393
431
454
453
470
487
535
565
511
529
546
594
627
607
628
650
710
757
649
674
699
766
812

106
109
111
117
123
131
134
136
144
147
142
144
146
156
161
181
185
190
200
210
205
209
212
226
238
250
256
262
277
288
243
247
251
264
270

254
261
267
292
318
332
342
352
384
413
349
361
373
409
430
430
447
465
514
541
481
500
518
563
595
578
599
621
678
725
615
639
662
728
777

110
112
115
121
128
136
139
142
151
152
146
148
151
161
166
186
191
196
206
217
213
216
219
234
248
256
263
270
286
298
253
257
261
276
281

260
265
270
285
290
282
286
291
309
320
360
368
376
396
416
407
414
421
448
472
452
461
471
499
522
480
488
496
522
534

693
714
736
804
860
741
763
785
862
909
905
940
974
1070
1129
1022
1057
1093
1188
1255
1118
1157
1196
1304
1385
1299
1348
1398
1533
1625

262
267
272
288
293
284
288
293
312
322
362
371
379
399
420
411
418
424
452
477
455
465
474
503
527
485
493
501
528
540

665
684
704
769
825
697
721
745
819
860
860
895
930
1027
1082
962
999
1036
1125
1190
1059
1099
1139
1240
1321
1229
1277
1325
1455
1553

272
278
283
302
305
292
297
302
322
332
372
382
392
412
434
426
432
438
468
496
469
479
489
520
546
506
514
522
552
562

Power (kW) is for compressors only, Power consumption of all fans running: 08L, 44M, 55S = 8.8 kW; 09L, 66S, 77X = 15.2 kW;
88X, 99XB, 5555S = 17.6 kW; 99XD, 6666S, 7777X =30.4 kW; 8888X, 9999XB = 35.2 kW; 9999XD = 60.8 kW.

Page 6
Doc. No. PCYAEP-50/03.04/GB

TABLE 4b YAEP R22 COOLING CAPACITIES - IMPERIAL DATA (F TONS/KW)

Model

YAEP
08LA7C

YAEP
09LC9C

YAEP
44MA7C

YAEP
55SC7C

YAEP
66SC9C

YAEP
77XC9C

YAEP
88XB7C

YAEP
99XB7C

YAEP
99XD9C

YAEP
5555SC7C

YAEP
6666SC9C

YAEP
7777XC9C

YAEP
8888XB7C

YAEP
8899XB7C

YAEP
9999XD9C

Condenser Air Entering Temperature F


105
113
Cool
Power
Cool
Power
Tons
kW
Tons
kW
76
94
72
97
79
95
75
99
82
98
78
102
89
103
85
107
90
104
87
108
94
111
91
116
97
113
93
117
101
115
97
120
110
121
106
126
111
122
107
128

Leaving
Chilled
Liquid
F
41
43
45
50
53
41
43
45
50
53

Cool
Tons
84
86
89
97
99
102
104
108
118
120

Power
kW
83
84
86
91
91
98
99
101
105
106

Cool
Tons
80
82
85
93
94
98
101
104
114
115

Power
kW
89
90
92
97
98
105
107
108
113
114

41
43
45
50
53
41
43
45
50
53
41
43
45
50
53
41
43
45
50
53
41
43
45
50
53
41
43
45
50
53
41
43
45
50
53

88
90
94
101
103
112
115
120
130
132
124
127
131
142
144
152
156
160
174
176
174
178
184
199
202
199
206
215
230
234
214
222
232
250
254

91
93
95
99
100
109
111
113
118
119
123
124
127
133
135
159
161
164
172
174
175
178
182
191
193
218
222
227
239
241
199
203
207
216
218

84
86
89
96
98
106
110
115
125
128
118
121
125
136
138
142
147
153
165
168
165
169
175
189
192
192
198
205
222
226
206
213
223
241
245

97
99
101
106
107
117
119
122
127
128
130
132
134
142
143
167
170
174
182
184
185
189
193
204
206
231
235
240
253
256
213
217
222
232
234

81
83
86
92
94
104
107
111
120
123
114
116
120
130
133
137
142
147
160
162
157
161
167
180
183
183
189
196
213
217
197
205
213
232
235

102
104
106
112
113
125
127
129
135
136
137
139
141
149
150
175
178
181
191
194
195
199
204
215
218
241
246
252
265
268
228
232
237
248
250

77
79
81
88
90
99
103
107
115
118
107
110
114
124
126
130
135
141
153
156
147
152
158
171
174
174
181
188
204
208
187
194
203
221
224

41
43
45
50
53
41
43
45
50
53
41
43
45
50
53
41
43
45
50
53
41
43
45
50
53
41
43
45
50
53

223
231
240
260
265
248
254
262
284
289
305
312
321
347
353
348
357
367
399
404
374
385
399
429
436
427
444
463
500
508

218
222
226
236
238
245
249
254
266
269
318
322
328
344
349
350
356
363
382
386
392
400
408
429
434
398
406
415
431
436

212
221
231
250
255
236
243
251
272
276
284
295
307
330
336
330
339
349
379
385
357
367
380
411
418
411
427
446
482
489

235
238
243
254
256
260
264
269
283
286
334
340
347
364
369
370
377
386
408
413
416
424
433
457
462
426
434
444
464
468

207
214
222
241
246
227
232
240
261
265
274
283
295
319
325
313
322
333
361
367
339
350
363
394
400
395
409
427
464
471

249
253
258
270
273
273
277
282
297
301
349
355
363
382
387
390
398
407
430
436
436
445
456
480
486
457
465
475
495
499

199
205
213
231
236
214
220
228
248
252
260
270
282
307
312
295
305
316
342
348
322
333
346
375
382
374
388
405
441
449

85

95

115

125

Cool
Tons
72
74
77
84
86
90
92
96
105
106

Power
kW
98
100
103
108
109
117
119
122
128
129

Cool
Tons
66
69
72
79
80
84
87
90
99
100

Power
kW
103
105
108
114
115
123
124
128
135
136

106
108
111
116
118
130
132
135
142
143
141
143
146
154
156
180
184
188
198
201
203
207
211
224
227
248
254
261
275
278
240
244
249
261
263

76
78
80
87
89
98
101
105
114
117
105
108
112
122
124
129
133
140
152
155
145
150
156
169
172
172
178
186
202
206
184
191
200
218
222

106
109
112
117
119
131
134
137
144
145
142
144
147
156
157
181
185
190
200
203
205
209
213
226
230
250
256
263
277
281
243
247
252
264
266

71
72
74
81
84
93
95
99
107
110
96
100
104
114
115
120
124
131
143
146
133
138
145
156
159
161
167
174
189
193
171
177
185
202
206

111
114
117
122
124
138
141
144
153
154
148
150
154
163
164
188
193
199
209
212
216
219
223
237
242
259
266
275
290
293
257
261
267
281
282

260
265
270
285
286
282
286
292
309
312
360
368
376
396
402
407
414
422
448
455
451
461
472
499
505
479
487
498
521
525

197
203
211
228
233
211
217
225
245
249
257
267
279
304
309
290
300
312
338
343
318
329
342
370
377
369
383
400
435
443

262
267
273
288
290
284
288
295
312
315
362
371
380
399
405
411
418
426
452
459
455
465
477
503
510
485
493
504
528
531

185
191
198
214
219
193
200
208
227
231
239
249
262
287
291
266
277
290
312
318
294
305
319
345
352
341
354
370
404
413

276
282
289
307
308
295
300
307
326
329
376
386
397
417
424
432
438
446
474
483
475
485
498
527
535
514
522
533
562
564

Power (kW) is for compressors only, Power consumption of all fans running: 08L, 44M, 55S = 8.8 kW; 09L, 66S, 77X = 15.2 kW;
88X, 99XB, 5555S = 17.6 kW; 99XD, 6666S, 7777X =30.4 kW; 8888X, 9999XB = 35.2 kW; 9999XD = 60.8 kW.

Page 7
Doc. No. PCYAEP-50/03.04/GB

YAEP R407C COOLING CAPACITIES - METRIC DATA (C KW/KW)


Model

YAEP
08LC7B

YAEP
09LC9B

YAEP
44MC7B

YAEP
55SC9B

YAEP
66SC9B

YAEP
77XC9B

YAEP
77XF7B

YAEP
88XD7B

YAEP
99XD9B

YAEP
5555SC9B

YAEP
6666SC9B

YAEP
7777XC9B

YAEP
7777XF7B

YAEP
8888XD7B

YEAP
8899XD7B

YAEP
9999XD9B

Condenser Air Entering Temperature C


40
45
Cool
Power
Cool
Power
kW
kW
kW
kW
268
92
252
96
278
94
260
98
287
96
270
100
307
100
289
105
326
104
307
109
324
112
307
117
333
114
317
119
343
116
326
122
362
121
345
127
381
126
364
133

Leaving
Chilled
Liquid
C
6
7
8
10
12
6
7
8
10
12

Cool
kW
299
309
319
339
359
355
364
375
394
414

Power
kW
83
84
86
89
92
100
102
104
108
112

Cool
kW
284
294
303
323
343
340
349
360
379
398

Power
kW
87
88
90
94
98
106
108
110
115
119

6
7
8
10
12
6
7
8
10
12
6
7
8
10
12
6
7
8
10
12
6
7
8
10
12
6
7
8
10
12
6
7
8
10
12

330
341
352
374
396
398
411
424
451
478
438
453
467
497
527
500
515
531
563
595
537
556
576
614
653
638
657
677
721
762
739
762
785
830
871

88
90
92
95
98
112
115
117
122
127
125
128
131
137
143
160
164
169
177
186
152
156
159
166
173
168
171
174
180
186
205
209
213
222
230

315
325
336
357
377
380
393
405
431
457
415
430
444
472
501
476
492
508
539
570
514
532
551
588
625
608
629
649
689
731
711
733
754
798
841

94
95
97
101
105
118
121
124
129
134
131
134
137
144
150
167
172
176
186
195
159
163
167
174
182
179
182
186
192
199
217
222
226
236
245

298
308
319
339
360
362
375
388
413
439
394
407
421
448
475
451
465
483
514
382
490
507
524
559
594
579
599
617
659
701
681
703
724
767
809

98
100
102
106
110
124
127
130
136
142
137
141
144
151
158
174
179
169
177
137
166
170
174
183
191
189
193
197
204
212
230
235
239
249
258

281
291
301
321
342
344
356
368
394
419
372
385
398
424
450
321
332
343
365
376
458
476
493
527
562
549
568
588
628
668
648
670
692
735
776

6
7
8
10
12
6
7
8
10
12
6
7
8
10
12
6
7
8
10
12
6
7
8
10
12
6
7
8
10
12
6
7
8
10
12

795
822
849
902
956
876
907
935
994
1053
1000
1031
1063
1126
1189
1074
1112
1151
1228
1305
1276
1313
1355
1441
1524
1363
1402
1444
1530
1613
1479
1524
1569
1660
1743

224
229
234
244
254
250
256
262
274
286
320
329
337
355
372
304
311
318
332
346
336
342
348
360
372
378
385
393
408
422
410
418
426
443
460

759
785
811
862
914
830
859
888
945
1002
952
984
1015
1078
1141
1028
1065
1102
1176
1250
1216
1258
1298
1378
1462
1302
1344
1385
1467
1551
1422
1465
1508
1595
1682

237
242
248
258
269
262
268
275
287
300
334
343
352
371
390
318
326
333
349
364
358
364
371
384
398
401
409
417
433
449
434
443
452
471
490

724
750
775
826
877
788
815
841
896
950
903
930
965
1028
763
979
1014
1049
1119
1188
1158
1199
1235
1318
1401
1244
1285
1324
1409
1493
1363
1405
1448
1533
1618

248
254
260
272
283
274
281
288
302
316
348
358
337
355
274
332
340
348
365
382
378
386
393
408
424
423
432
441
458
476
460
469
478
497
516

687
712
736
788
839
744
769
795
847
899
642
664
686
730
752
916
951
986
1055
1124
1098
1137
1176
1256
1336
1182
1223
1262
1345
1464
1297
1340
1383
1470
1552

30

35

TABLE 4c

46

50

Cool
kW
248
256
266
285
303
303
313
322
341
360

Power
kW
97
99
101
106
110
118
120
123
128
131

Cool
kW
192
199
207
221
235
237
245
253
268
284

Power
kW
75
77
79
82
86
91
93
95
100
104

103
105
107
112
116
130
133
136
143
149
143
147
150
158
165
118
122
125
132
139
174
178
183
191
200
200
204
208
217
225
242
247
252
262
271

276
286
296
317
337
340
352
363
230
245
367
379
392
293
310
316
327
338
360
371
452
469
485
520
388
541
560
580
620
660
640
661
682
727
768

104
106
109
111
115
131
134
135
71
74
144
149
152
100
111
119
124
127
134
141
176
180
181
190
135
202
206
210
219
223
244
249
254
259
268

159
165
171
183
195
196
203
210
226
241
250
259
268
286
304
157
162
168
178
184
305
317
330
354
379
424
440
457
488
520
503
521
539
575
608

55
56
57
60
62
69
71
73
76
80
101
104
107
112
117
56
57
59
62
63
124
127
130
136
142
158
162
165
172
179
191
195
199
207
213

260
266
272
285
298
286
293
301
315
330
237
243
250
264
278
348
357
365
383
400
400
408
417
434
450
445
454
464
483
492
484
494
504
524
542

679
703
727
460
489
733
759
784
585
621
633
655
676
720
742
904
939
971
1040
776
1082
1121
1160
1240
1320
1168
1207
1246
1329
1455
1281
1322
1364
1454
1535

262
268
270
142
148
288
298
304
212
222
238
248
254
268
282
351
360
362
379
270
404
412
421
438
445
449
459
468
482
489
488
498
509
519
537

392
407
421
453
483
500
518
536
572
607
313
324
335
357
368
610
635
660
709
758
848
879
913
976
1039
917
950
981
1049
1175
1007
1043
1079
1150
1215

139
142
145
152
159
203
208
213
223
234
111
114
117
124
127
248
254
260
272
284
317
323
330
344
358
350
358
365
380
381
381
389
397
413
426

Power (kW) is for compressors only, Power consumption of all fans running: 08L, 44M = 8.8 kW; 09L, 55S, 66S, 77XC = 15.2 kW;
77XF = 13.2 kW; 88X =17.6 kW; 99XD, 5555S, 6666S, 7777XC =30.4 kW; 7777XF = 26.4 kW; 8888X, 8899X = 35.2 kW; 9999XD = 60.8 kW.
Page 8
Doc. No. PCYAEP-50/03.04/GB

TABLE 4d YAEP R407C COOLING CAPACITIES - IMPERIAL DATA (F TONS/KW)

Model

YAEP
08LC7B

YAEP
09LC9B

YAEP
44MC7B

YAEP
55SC9B

YAEP
66SC9B

YAEP
77XC9B

YAEP
77XF7B

YAEP
88XD7B

YAEP
99XD9B

YAEP
5555SC9B

YAEP
6666SC9B

YAEP
7777XC9B

YAEP
7777XF7B

YAEP
8888XD7B

YEAP
8899XD7B

YAEP
9999XD9B

Condenser Air Entering Temperature F


105
113
Cool
Power
Cool
Power
Tons
kW
Tons
kW
76
92
72
96
80
94
75
99
83
97
78
101
87
100
82
105
89
101
84
106
92
112
87
116
95
115
91
120
98
118
94
122
103
122
98
127
105
123
100
128

Leaving
Chilled
Liquid
F
43
45
47
50
53
43
45
47
50
53

Cool
Tons
86
89
92
97
99
101
105
108
113
114

Power
kW
82
84
85
88
89
99
102
104
107
109

Cool
Tons
81
84
87
92
94
97
100
103
108
109

Power
kW
87
89
91
94
95
106
109
111
115
116

43
45
47
50
53
43
45
47
50
53
43
45
47
50
53
43
45
47
50
53
43
45
47
50
53
43
45
47
50
53
43
45
47
50
53

94
98
102
107
109
114
118
122
129
131
125
130
135
142
145
143
148
153
161
164
153
160
166
175
179
182
189
195
206
209
211
219
226
237
240

88
90
92
94
95
111
114
117
121
123
124
128
131
136
138
159
165
169
177
179
151
155
159
165
167
167
170
174
179
181
204
209
213
220
223

89
93
96
101
103
108
112
116
123
125
118
123
127
134
137
135
141
146
153
156
146
152
158
167
170
173
180
186
196
199
202
210
216
227
230

94
96
98
101
102
118
122
125
129
131
131
135
138
144
146
167
173
178
186
165
159
164
168
174
177
179
183
187
192
194
217
223
228
236
238

85
88
91
96
98
103
107
111
117
120
112
117
121
127
130
128
133
139
146
135
139
145
151
159
162
165
171
177
187
191
194
201
208
218
222

99
101
103
107
108
125
128
131
136
138
138
142
146
152
154
168
171
166
173
162
167
172
176
183
186
190
195
199
205
208
231
237
242
250
253

80
83
86
91
93
98
102
106
76
77
106
110
87
92
94
98
102
105
111
110
131
137
142
150
142
156
163
169
178
182
184
192
198
209
212

43
45
47
50
53
43
45
47
50
53
43
45
47
50
53
43
45
47
50
53
43
45
47
50
53
43
45
47
50
53
43
45
47
50
53

227
236
245
258
262
250
261
270
284
289
286
296
306
322
327
307
320
332
351
357
365
377
391
412
419
389
403
416
437
444
422
438
452
474
481

223
229
234
243
246
249
256
263
273
276
319
329
338
353
358
303
311
319
330
334
334
341
347
358
361
376
385
393
405
410
408
417
426
440
445

216
225
233
245
250
236
246
255
269
274
271
281
291
307
312
292
305
316
334
341
346
360
373
392
399
370
385
397
417
424
404
419
433
454
461

237
243
249
258
261
262
270
277
287
291
334
345
355
371
377
318
327
335
349
330
358
366
373
384
388
401
410
419
433
437
434
445
455
471
477

206
215
223
235
239
224
233
242
255
259
257
266
277
292
270
278
290
301
318
324
329
343
355
375
382
354
368
380
400
408
387
402
415
436
443

249
256
263
273
276
275
284
291
303
308
337
343
331
346
352
334
343
353
367
324
380
389
398
411
416
425
436
446
461
466
462
474
484
500
505

196
204
211
152
154
212
220
175
184
187
195
203
211
222
219
261
273
283
300
283
312
325
337
357
364
336
350
362
383
393
369
383
397
418
425

85

95

115

125

Cool
Tons
70
73
76
81
82
86
89
92
97
99

Power
kW
97
100
102
106
107
118
121
124
128
129

Cool
Tons
49
51
53
57
58
61
64
66
69
70

Power
kW
69
71
72
75
76
83
85
88
91
92

103
106
108
110
111
130
133
135
84
85
142
148
112
115
117
129
133
136
142
142
174
178
181
188
145
200
205
209
216
218
241
248
252
257
260

78
82
85
90
92
97
101
104
65
67
104
109
79
83
85
90
94
97
102
103
129
134
139
148
137
154
160
167
176
180
182
189
196
207
210

104
107
109
111
112
131
134
136
71
72
143
150
103
106
108
119
124
128
134
137
176
180
182
190
135
202
207
212
219
220
244
250
254
259
262

34
36
37
39
40
42
44
46
49
50
60
63
65
69
70
30
31
32
34
34
73
76
80
85
87
109
114
119
126
128
130
136
141
149
152

39
40
41
43
43
50
51
53
55
56
88
91
93
97
98
36
37
38
40
40
108
111
114
118
120
145
149
152
158
160
174
179
183
189
190

259
266
270
168
170
284
297
223
230
234
258
267
271
284
290
348
357
362
377
281
399
409
418
432
435
444
456
465
478
481
483
495
504
515
520

193
201
209
131
133
208
217
158
166
169
180
187
194
205
207
257
269
279
296
273
308
321
333
352
359
332
345
358
378
389
364
378
392
413
420

262
269
272
142
144
286
300
206
212
216
238
248
256
268
274
351
360
364
379
270
404
414
423
438
440
449
461
470
482
484
488
500
509
519
524

85
88
92
98
100
120
125
130
137
140
59
62
64
67
68
146
153
160
170
174
219
228
238
252
257
237
247
256
271
282
260
271
282
298
303

100
103
105
110
111
176
181
187
194
197
71
73
76
79
80
215
222
228
237
240
290
297
305
315
319
320
328
336
347
347
348
357
365
378
381

Power (kW) is for compressors only, Power consumption of all fans running: 08L, 44M = 8.8 kW; 09L, 55S, 66S, 77XC = 15.2 kW;
77XF = 13.2 kW; 88X =17.6 kW; 99XD, 5555S, 6666S, 7777XC =30.4 kW; 7777XF = 26.4 kW; 8888X, 8899X = 35.2 kW; 9999XD = 60.8 kW.
Page 9
Doc. No. PCYAEP-50/03.04/GB

PHYSICAL DATA - YAEP R22 UNITS


1 Circuit Units
YAEP
Unit

08LA7C
3

Number of Compressors

Oil Capacity per Compressor

11

11

11

11

11

11

11

11

Refrigerant Circuits per Cooler

90

90

135

150

150

205

205

205

205

m2

11.9

11.9

11.9

11.9

11.9

11.9

23.8

23.8

23.8

Power (each)

kW

2.2

3.8

2.2

2.2

3.8

3.8

2.2

2.2

3.8

Total Airflow

m3/s

30.4

34.8

30.4

30.4

34.8

34.8

60.8

60.8

69.6

Systems 1

kg

39.0

42.0

42.0

49.0

49.0

49.0

57.0

57.0

64.0

Systems 2

kg

42.0

49.0

49.0

49.0

57.0

57.0

64.0

Face Area
Quantity

Fans

8
11

Coolers per Unit


Water Capacity per Cooler

Condenser

2 Circuit Units

09LC9C 44MA7C 55SC7C 66SC9C 77XC9C 88XB7C 99XB7C 99XD9C

Number of Capacity Steps

Compressor Cylinders per Compressor

Cooler

TABLE 5a

Refrigerant Charge
Aluminium Fins

Weight
Copper Fins

Shipping

kg

3550

3665

4000

4200

4350

4495

5222

5222

5422

Operating

kg

3640

3640

4135

4350

4500

4700

5427

5427

5627

Shipping

kg

3740

3955

4190

4490

4640

4785

5797

5797

5997

Operating

kg

3830

4045

4325

4640

4790

4990

6002

6002

6202

Length

Dimensions Width
Height

mm

2969

2969

2969

2969

2969

2969

5703

5703

5703

mm
mm

2241
2466

2241
2466

2241
2466

2241
2466

2241
2466

2241
2466

2241
2466

2241
2466

2241
2466

4 Circuit Units
YAEP
Unit

5555SC7C

6666SC9C

7777XC9C

8888XB7C

8899XB7C

9999XD9C

Number of Capacity Steps

12

12

12

Number of Compressors

11

11

11

11

11

11

Compressor Cylinders per Compressor


Oil Capacity per Compressor

Cooler

Coolers per Unit

Refrigerant Circuits per Cooler

Water Capacity per Cooler

Condenser

Face Area

150

150

205

205

205

205

m2

23.8

23.8

23.8

47.6

47.6

47.6

16

16

16

kW

2.2

3.8

3.8

2.2

2.2

3.8

Quantity

Fans

Power (each)

m3/s

60.8

69.6

69.6

121.6

121.6

139.2

Systems 1/2

kg

49.0

49.0

49.0

57.0

57.0

64.0

Systems 3/4

kg

49.0

49.0

49.0

57.0

57.0

64.0

Ship (Main)

kg

4200

4350

4495

5222

5222

5422

Ship (Aux.)

kg

4200

4350

4495

5222

5222

5422

Operating

kg

8700

9000

9400

10854

10854

11254
5997

Total Airflow

Refrigerant Charge

Aluminium Fins

Weight
Copper Fins
Length

Dimensions Width
Height

Page 10
Doc. No. PCYAEP-50/03.04/GB

Ship (Main)

kg

4490

4640

4785

5797

5797

Ship (Aux.)

kg

4490

4640

4785

5797

5797

5997

Operating

kg
mm
mm
mm

9280
6128
2241
2466

9580
6128
2241
2466

9980
6128
2241
2466

12004
11705
2241
2466

12004
11705
2241
2466

12404
11705
2241
2466

PHYSICAL DATA - YAEP R407C UNITS

TABLE 5b

1 Circuit Units
YAEP
Unit

08LC7B

Number of Compressors

11

11

11

11

11

11

11

11

11

Coolers per Unit

Refrigerant Circuits per Cooler

Water Capacity per Cooler

90

90

135

150

150

205

205

205

205

m2

11.9

11.9

11.9

11.9

11.9

11.9

17.8

23.8

23.8

Power (each)

kW

2.2

3.8

2.2

3.8

3.8

3.8

2.2

2.2

3.8

Total Airflow

m3/s

30.4

34.8

30.4

34.8

34.8

34.8

44.7

60.8

69.6

Systems 1

kg

39.0

42.0

42.0

49.0

49.0

49.0

53.0

57.0

64.0

Systems 2

kg

42.0

49.0

49.0

49.0

53.0

57.0

64.0

Face Area
Quantity

Fans

88XD7B 99XD9B

Oil Capacity per Compressor

Condenser

77XF7B

Number of Capacity Steps

Compressor Cylinders per Compressor

Cooler

2 Circuit Units

09LC9B 44MC7B 55SC9B 66SC9B 77XC9B

Refrigerant Charge
Aluminium Fins

Weight
Copper Fins

Shipping

kg

3550

3665

4000

4200

4350

4495

4985

5222

5422

Operating

kg

3640

3640

4135

4350

4500

4700

5190

5427

5627

Shipping

kg

3740

3955

4190

4490

4640

4785

5400

5797

5997

Operating

kg

3830

4045

4325

4640

4790

4990

5605

6002

6202

Length

Dimensions Width
Height

mm

2969

2969

2969

2969

2969

2969

4193

5703

5703

mm
mm

2241
2466

2241
2466

2241
2466

2241
2466

2241
2466

2241
2466

2241
2466

2241
2466

2241
2466

4 Circuit Units
YAEP
Unit

5555SC9B

6666SC9B

7777XC9B

7777XF7B

8888XD7B

Number of Capacity Steps

12

12

12

Number of Compressors

11

11

11

11

11

11

11

Coolers per Unit

Refrigerant Circuits per Cooler

150

150

205

205

205

205

205

m2

23.8

23.8

23.8

35.6

47.6

47.6

47.6

12

16

16

16

3.8

3.8

3.8

2.2

2.2

2.2

3.8

Compressor Cylinders per Compressor


Oil Capacity per Compressor

Cooler

Water Capacity per Cooler

Condenser

Face Area

Quantity

Fans

Power (each)

kW

Total Airflow

m3/s

69.6

69.6

69.6

89.4

121.6

121.6

139.2

Systems 1/2

kg

49.0

49.0

49.0

53.0

57.0

57.0

64

Systems 3/4

kg

49.0

49.0

49.0

53.0

57.0

57.0

64

Ship (Main)

kg

4200

4350

4495

4985

5222

5222

5422

Ship (Aux.)

kg

4200

4350

4495

4985

5222

5222

5422

Operating

kg

8700

9000

9400

10380

10854

10854

11254

Refrigerant Charge
Aluminium Fins

Weight
Copper Fins

Dimensions

8899XD7B 9999XD9B

Length
Width
Height

Ship (Main)

kg

4490

4640

4785

5400

5797

5797

5997

Ship (Aux.)

kg

4490

4640

4785

5400

5797

5797

5997

Operating

kg
mm
mm
mm

9280
6128
2241
2466

9580
6128
2241
2466

9980
6128
2241
2466

11210
8586
2241
2466

12004
11705
2241
2466

12004
11705
2241
2466

12404
11705
2241
2466

Page 11
Doc. No. PCYAEP-50/03.04/GB

ELECTRICAL DATA - YAEP R22 UNITS

TABLE 6a

Power Requirement per Panel - 1, 2 and 4 Refrigerant Circuit Units with Single Point Power Supply - Disconnect Switch (CE) or Terminal Block Option (Non CE)

(Data includes one/both compressors and associated fans)


Note: To obtain the total unit power requirements on four circuit models 5555SC7C / 6666SC9C / 7777XC9C / 8888XB7C / 9999XD9C multiply the panel values by 2.
Note: To obtain the total unit power requirements on four circuit model 8899XB7C the panel values should be added together.

YAEP Model

Circuits

08LA7C
09LC9C
44MC7C
(55)55SC7C
(66)66SC9C
(77)77XC9C
(88)88XB7C
99XB7C

1
1
2
2/4
2/4
2/4
2/4
2

8899XB7C

2+2

(99)99XD9C

2/4

35C/7C
Nom. kW
101
122
107
137
149
189
228
270
228
270
250

Max. kW
144
150
125
163
185
227
300
300
300
300
300

380 V
195
228
197
239
278
348
410
480
410
480
469

Nominal. Amps
400 V
194
226
195
237
276
344
408
470
408
470
463

415 V
193
224
193
235
274
342
406
466
406
466
461

342 V
293
293
275
315
356
422
580
580
580
580
595

Maximum. Amp
380 V
400 V
268
266
268
266
231
225
289
285
336
332
408
404
530
526
530
526
530
526
530
526
545
541

415 V
264
264
221
279
328
400
522
522
522
522
537

380 V
689
689
398
500
626
753
954
954
954
954
961

Part Wind Inrush


400 V
415 V
725
752
725
752
409
420
518
532
648
674
780
802
988
1015
988
1015
988
1015
988
1015
995
1020

Power Requirement per Refrigeration Circuit - 2 and 4 Refrigerant Circuit Units with Multi Point Power Supply Option (Non CE)

(Data includes each circuit compressor and associated fans)


YAEP Model
44MC7C
55SC7C
66SC9C
77XC9C
88XB7C
99XB7C
99XD9C
5555SC7C
6666SC9C
7777XC9C
8888XB7C
8899XB7C Main
8899XB7C Aux
9999XD9C

Circuits
2
2
2
2
2
2
2
4
4
4
4
2
2
4

35C/7C
Nom. kW
53
69
75
95
114
135
125
65
71
91
114
114
135
125

Max. kW
62
82
93
114
150
150
150
82
93
114
150
150
150
150

380 V
98
119
139
174
205
240
234
119
139
174
205
205
240
234

Nominal. Amps
400 V
97
118
138
172
204
235
231
118
138
172
204
204
235
227

415 V
96
117
137
171
203
233
230
117
137
171
203
203
233
230

342 V
137
157
178
211
290
290
297
157
178
211
290
290
290
297

Maximum. Amp
380 V
400 V
115
112
144
142
168
166
204
202
265
263
265
263
272
270
144
142
168
166
204
202
265
263
265
263
265
263
272
270

415 V
110
139
164
200
261
261
268
139
164
200
261
261
261
268

380 V
283
356
458
549
689
689
689
356
458
549
689
689
689
689

Part Wind Inrush


400 V
415 V
297
308
376
390
482
508
578
600
725
752
725
752
725
752
376
390
482
508
578
600
725
752
725
752
725
752
725
752

ELECTRICAL DATA - YAEP R407C UNITS

TABLE 6b

Power Requirement per Panel - 1, 2 and 4 Refrigerant Circuit Units with Single Point Power Supply - Disconnect Switch (CE) or Terminal Block Option (Non CE)

(Data includes one/both compressors and associated fans)


Note: To obtain the total unit power requirements on four circuit models 5555SC9B / 6666SC9B / 7777XC9B / 7777XF7B / 8888XB7B / 9999XD9B multiply the panel values by 2.
Note: To obtain the total unit power requirements on four circuit model 8899XB7B the panel values should be added together.

YAEP Model

Circuits

08LC7B
09LC9B
44MC7B
(55)55SC9B
(66)66SC9B
(77)77XC9B
(77)77XF7B
(88)88XB7B

1
1
2
2/4
2/4
2/4
2/4
2/4

(88)99XB7B

2+2

(99)99XD9B

2/4

35C/7C
Nom. kW
97
123
105
137
149
187
177
200
200
244
250

Max. kW
144
150
125
163
185
227
225
288
288
288
300

380 V
190
228
197
246
280
348
331
386
386
450
457

Nominal. Amps
400 V
189
226
195
244
278
346
329
380
380
448
455

415 V
188
224
193
242
276
342
327
374
446
446
453

342 V
293
293
275
322
356
422
427
580
580
580
595

Maximum. Amp
380 V
400 V
268
266
268
266
231
225
296
292
336
332
412
406
417
411
530
526
530
526
530
526
545
541

415 V
264
264
221
286
328
400
405
522
522
522
537

380 V
689
689
398
504
626
755
758
954
954
954
961

Part Wind Inrush


400 V
415 V
725
752
725
752
409
418
522
533
648
672
781
800
784
803
988
1013
988
1013
988
1013
995
1020

Power Requirement per Refrigeration Circuit - 2 and 4 Refrigerant Circuit Units with Multi Point Power Supply Option (Non CE)

(Data includes each circuit compressor and associated fans)


YAEP Model
44MC7B
55SC9B
66SC9B
77XC9B
77XF7B
88XB7B
99XD9B
5555SC9B
6666SC9B
7777XC9B
7777XF7B
8888XB7B
8899XB7B Main
8899XB7B Aux
9999XD9B

Circuits
2
2
2
2
2
2
2
4
4
4
4
4
2
2
4

Page 12
Doc. No. PCYAEP-50/03.04/GB

35C/7C
Nom. kW
52
69
75
94
89
100
125
65
71
90
91
100
100
122
125

Max. kW
62
82
93
114
113
144
150
82
93
114
113
144
144
144
150

380 V
98
123
140
174
166
193
228
123
140
174
166
193
193
225
228

Nominal. Amps
400 V
97
122
139
173
165
190
227
122
139
173
165
190
190
224
227

415 V
96
121
138
171
164
187
226
121
138
171
164
187
187
223
226

342 V
137
161
178
211
214
290
297
161
178
211
214
290
290
290
297

Maximum. Amp
380 V
400 V
115
112
148
146
168
166
206
203
209
206
265
263
272
270
148
146
168
166
206
203
209
206
265
263
265
263
265
263
272
270

415 V
110
143
164
200
203
261
268
143
164
200
203
261
261
261
268

380 V
283
356
458
549
549
689
689
356
458
549
549
689
689
689
689

Part Wind Inrush


400 V
415 V
297
308
376
390
482
508
578
600
578
600
725
752
725
752
376
390
482
508
578
600
578
600
725
752
725
752
725
752
725
752

POWER SUPPLY CONNECTIONS


(Main Panel and Auxiliary Panel when fitted)
Power Section

YAEP 08L-09L

Common Input
Section
Control Circuit Switch
Disconnect / Emergency
Stop Device

Control
Section
Power
Section 1
Common
Input
Section

YAEP 44M-77X & 5555S-7777X


Control
Section
Power
Section 2

Power
Section 1
Common
Input
Section

YAEP 88X-99X & 8888X-9999X

Non-Fused
Disconnect Switch
or Terminal Block

Control
Section
Power
Section 1

Protective
Earth

Power
Section 2
Common
Input
Section

System Fuses,
or Terminal Block

Standard Single Point Power Supply (CE)


One supply per panel to master non-fused disconnect switch
(XCSISD) with internal power distribution to fuses, control supply
to non-fused disconnect switch (QCSD/ESD) derived internally.
2 PS
CIS
F F F

F F F

QCSISD

DESIGNATION
AMB
APB
ARB
CS
CIS
F
PE
PS
QCSD/ESD

U V W

PE

L1 L2 L3
3

PE

QCSISD
QCSITB
QRESB

Multi Point Power Supply (Non CE) Options


One supply per refrigerant circuit to fuse/terminal block
with separate control supply to non-fused disconnect
switch (QCSD/ESD).

QRESB

50 Hz 380/400 V

Single Point Power Supply (Non CE) Option


One supply per panel to a common terminal block (QCSITB) with
internal power distribution to fuses, control supply to non-fused
disconnect switch (QCSD/ESD) derived internally.

1 PS

DESCRIPTION
MICROPROCESSOR BOARD
POWER SUPPLY BOARD
RELAY BOARD
CONTROL SECTION
COMMON INPUT SECTION
FUSE
PROTECTIVE EARTH
POWER SECTION
CONTROL CIRCUIT SWITCH DISCONNECT
/ EMERGENCY STOP DEVICE
COMMON SUPPLY INPUT SWITCH DISCONNECT
COMMON SUPPLY INPUT TERMINAL BLOCK
REMOTE EMERGENCY STOP BUTTON

2 PS

1 PS

APB

1 PS

Protective
Earth

2 PS

AMB ARB

CS

CIS

Compressor
Contactor

CIS

3
4

Compressor
Contactor

U V W

F F F

U V W

F F F

QCSITB

PE

QCSD/ESD
PE

PE

U V W

PE

QRESB
L1 L2 L3
3

PE

QRESB

50 Hz 380/400 V

PE

PE
L1 L2 L3

3
50Hz
380/400V

L1 L3

2
50Hz
380/400V

PE

L1 L2 L3

3
50Hz
380/400V

Page 13
Doc. No. PCYAEP-50/03.04/GB

CONTROL CONNECTIONS
(Main Panel and Auxiliary Panel when fitted)

YAEP 44M-77X & 5555S-7777X

YAEP 08L-09L

YAEP 88X-99X & 8888X-9999X

Control
Section

Control
Section

Control
Section

Power
Section 1

Power
Section 2

Power
Section 1

Common
Input
Section

Power
Section 1

Power
Section 2
Common
Input
Section

Common
Input
Section

Control Section
Communication Link
(4 Circuit Units Only)

34

}
}
}
}
}
}

APB
33
36
35

AMB

37

ARB

MAIN
PANEL

38
39

BLACK
WHITE

30
31
32

AUXILIARY
PANEL

Mixed Water
Temperature
(4 Circuit Units Only)

Note 1
13

Communications Link Cable


to be field run and
connected to Main Panel TB7
during installation

10

11

14

12

15

16

13

17

18

10

13

Chilled Liquid Pump Start

Unit Run Signal


Open on Alarm

Open on Alarm

System
Close on Alarm No. 2 / 4

System
Close on Alarm No. 1 / 3

DESIGNATION
AMB
APB
ARB
CS
CIS
PS

DESCRIPTION
MICROPROCESSOR BOARD
POWER SUPPLY BOARD
RELAY BOARD
CONTROL SECTION
COMMON INPUT SECTION
POWER SECTION

Remote Lead/Lag
Remote Print (Main Panel only)
Remote Setpoint Reset (Main Panel only)
Remote Unload
System No. 2 / 4 Remote Start/Stop
System No. 1 / 3 Remote Start/Stop

Chilled Liquid Flow Switch

Note 1: Fit link between terminals 14 and 15 and connect a voltage free contact to terminals 11 and 14
for combined Remote Start/Stop of systems 1 / 2 (2 circuit units) and systems 3 / 4 (4 circuit units).

Page 14
Doc. No. PCYAEP-50/03.04/GB

946

335

2466

493 AVM
500

6" (150 mm)


Inlet

2897

1778

1911 AVM C
L

6" (150 mm)


Outlet

2969

446

2241

2172 AVM POSITIONS

148

DIMENSIONS YAEP 08L & 09L

Page 15
Doc. No. PCYAEP-50/03.04/GB

520

840

1990

Page 16
Doc. No. PCYAEP-50/03.04/GB

2241

2466.4

340
(314 on 44M)

493

8" (200 mm)


(6" (150 mm) on 44M)
Inlet

2897

2108 (2160 on 44M)

1911

8" (200 mm)


(6" (150 mm) on 44M)
Outlet

2969

407
(382 on 44M and 446 on 77XC)

449

2172 AVM POSITIONS

702

DIMENSIONS YAEP 44M - 77XC

2467

312

1707 AVM POSNS.


2108

1631

8" (200 mm)


Inlet

1676 AVM POSNS.

4187

8" (200 mm)


Outlet

4250

446

493

702
2166 AVM POSNS.

2241

DIMENSIONS YAEP 77XF

Page 17
Doc. No. PCYAEP-50/03.04/GB

2166 AVM POSITIONS

2438 AVM POSITIONS

2108

8" (200 mm)


Inlet

5407

1220 AVM

124

1257 AVM

1153

292 AVM

838

40

446

1800
221

Page 18
Doc. No. PCYAEP-50/03.04/GB

2426

199 AVM

634

8" (200 mm)


Outlet

5700

COMPRESSOR
2241 SYSTEM 2
SYSTEM 1 COMPRESSOR
REMOVED FOR DRAWING CLARITY

702

DIMENSIONS YAEP 88X - 99X

2897

2108

1911 AVM POS.

8" (200 mm)


Outlet

340

493

300

340

493

8" (200 mm)


Inlet

2897

2108

1911 AVM POS.

8" (200 mm)


Outlet

2172 AVM POSITIONS

2241

1150
840

8" (200 mm)


Inlet

6232

DIMENSIONS YAEP 5555S - 7777XC

Page 19
Doc. No. PCYAEP-50/03.04/GB

406
(446 on 7777XC)

2466

Page 20
Doc. No. PCYAEP-50/03.04/GB

446

493

8" (200 mm)


Inlet

1707

2108

4187

8" (200 mm)


Outlet

1676

1631

8675

312

300

312

8812

1676

1631

4187

8" (200 mm)


Outlet

1707

2108

8" (200 mm)


Inlet

702
2172

2241

DIMENSIONS YAEP 7777XF

2467

292

292

2426

MULTI POINT
CABLE ENTRY
SYSTEM 4

40

446

1257 AVM

2664

1220 AVM

5407

8" (200 mm)


Inlet

699
1568 REF.

2438 AVM POSITIONS


2108

8" (200 mm)


Outlet

11700

300

5407

292

292

2241

COMPRESSOR
SYSTEM 2,3

SYSTEM 1 and 4 COMPRESSORS


REMOVED FOR DRAWING CLARITY

702

2166 AVM POSITIONS

MULTI POINT
CABLE ENTRY
SYSTEM 1

SINGL POINT
CABLE ENTRY
SYSTEMS 1 & 2

MULTI POINT
CABLE ENTRY
SYSTEM 2

Note: DIMENSIONS AND AVM POSITIONS


ARE IDENTICAL FOR BOTH SECTIONS
- REFER TO OTHER SECTION FOR DETAILS

1257 AVM

1800
221

SINGL POINT
CABLE ENTRY
SYSTEMS 3 & 4

1153
838

MULTI POINT
CABLE ENTRY
SYSTEM 3

DIMENSIONS YAEP 8888X - 9999X

Page 21
Doc. No. PCYAEP-50/03.04/GB

EMEA
YORK
YORK INTERNATIONAL
Gardiners Lane South, Basildon, Essex SS14 3HE, England

GB
Subject to change without notice. ALL RIGHTS RESERVED

Вам также может понравиться