PRACTICAL CASE N

39

D OMESTIC

Problem: Ventilation of an individual garage in Barcelona. Details: 20 m2 x 2.6 m high, 20 m of ducting to the outside with a diameter of 150 mm already installed. Requirements: 520 m3/h. Pressure drop: 16 mm w.g. Solution: 1xTD-800/200 and 1xCT-150. External roof cowl. Observations: 10 air changes per hour calculated.