USE THIS PART FOR DEFINING ALARM TEXT IN THE BSC, RUN ONLY ONCE PER BSC.

IF THERE WILL BE NEW ALARM TEXT, JUST PASTE IT IN COLUMN "B", AND DRAG COLUMN "D" AND "E" TO UPDATE FORMULA. Opto 1 Opto 2 Opto 3 Opto 4 Opto 5 Opto 6 Opto 7 Opto 8 Opto 9 Opto 10 Opto 11 Opto 13 Opto 14 Opto 16 ALARM TEXT INTRUDER SMOKE HIGH TEMPERATURE RECTIFIER MODULE FAIL MOVEMENT RECTIFIER SYSTEM FAILED AC MAINS FAILED BATTERY LOW AIRCON 1 FAILED EQUIPMENT OVER VOLTAGE AIRCRAFT LIGHT FAILED AC PHASE FAILED ESKOM MAINS FAILED AIRCON 2 FAILED SEV CRITICAL MAJOR MAJOR MINOR MINOR CRITICAL MAJOR CRITICAL MINOR CRITICAL MINOR MINOR MAJOR MINOR TID 1 2 3 4 5 6 7 8 13 14 15 17 18 20

AC Mains Failure Rect System / Batt Int DC Low / Batt Low Dual Air Con Operation DC High / Rect System OverTemp / High Temp Rec Module Failure Aircon System Fault AC Phase Failure Nav Light Eskom Failure Generator Failure Fire Alarm / Smoke Intruder Entry / Movement Electrical Fence

1 2 3 4 5 6 7 8 13 14 15 16 17 18 19 20

SC, RUN ONLY ONCE PER BSC. IF THERE WILL BE NEW ALARM TEXT, DRAG COLUMN "D" AND "E" TO UPDATE FORMULA. COMMAND ZEFE:TID=1:TEXT=" INTRUDER "; ZEFE:TID=2:TEXT=" SMOKE "; ZEFE:TID=3:TEXT=" HIGH TEMPERATURE "; ZEFE:TID=4:TEXT=" RECTIFIER MODULE FAIL "; ZEFE:TID=5:TEXT=" MOVEMENT "; ZEFE:TID=6:TEXT=" RECTIFIER SYSTEM FAILED "; ZEFE:TID=7:TEXT=" AC MAINS FAILED "; ZEFE:TID=8:TEXT=" BATTERY LOW "; ZEFE:TID=13:TEXT=" AIRCON 1 FAILED "; ZEFE:TID=14:TEXT=" EQUIPMENT OVER VOLTAGE "; ZEFE:TID=15:TEXT=" AIRCRAFT LIGHT FAILED "; ZEFE:TID=17:TEXT=" AC PHASE FAILED "; ZEFE:TID=18:TEXT=" ESKOM MAINS FAILED "; ZEFE:TID=20:TEXT=" AIRCON 2 FAILED ";

INPUT BCF NUMBER 1391 1391 1391 1391 1391 1391 1391 1391 1391 1391 1391 1391 1391 1391

NOTE: INBR IS THE PORT ON THE BTS SIDE, THEREFOR EQUAL TO TID SEV AL3 AL2 AL2 AL1 AL1 AL3 AL2 AL3 AL1 AL3 AL1 AL1 AL2 AL1 POL OPEN OPEN OPEN OPEN OPEN OPEN OPEN OPEN OPEN OPEN OPEN OPEN OPEN OPEN

ZEFE:TID=1:TEXT="AC Mains Failure"; ZEFE:TID=2:TEXT="Rect System / Batt Int"; ZEFE:TID=3:TEXT="DC Low / Batt Low"; ZEFE:TID=4:TEXT="Dual Air Con Operation"; ZEFE:TID=5:TEXT="DC High / Rect System"; ZEFE:TID=6:TEXT="OverTemp / High Temp"; ZEFE:TID=7:TEXT="Rec Module Failure"; ZEFE:TID=8:TEXT="Aircon System Fault"; ZEFE:TID=13:TEXT="AC Phase Failure"; ZEFE:TID=14:TEXT="Nav Light"; ZEFE:TID=15:TEXT="Eskom Failure"; ZEFE:TID=16:TEXT="Generator Failure"; ZEFE:TID=17:TEXT="Fire Alarm / Smoke"; ZEFE:TID=18:TEXT="Intruder"; ZEFE:TID=19:TEXT="Entry / Movement"; ZEFE:TID=20:TEXT=" Electrical Fence";

1201 1201 1201 1201 1201 1201 1201 1201 1201 1201 1201 1201 1201 1201 1201 1201

AL3 AL2 AL3 AL2 AL3 AL2 AL3 AL2 AL1 AL1 AL1 AL1 AL1 AL1 AL1 AL1

Open Open Open Open Open Open Open Open Open Open Open Open Open Open NOT NOT

OTE: INBR IS THE PORT ON THE BTS SIDE, THEREFORE INBR IS NOT ALWAYS EQUAL TO TID COMMAND ZEFX:1391:INBR=1:ROU=ACT,POL=OPEN,:SEV=AL3,TID=1; ZEFX:1391:INBR=2:ROU=ACT,POL=OPEN,:SEV=AL2,TID=2; ZEFX:1391:INBR=3:ROU=ACT,POL=OPEN,:SEV=AL2,TID=3; ZEFX:1391:INBR=4:ROU=ACT,POL=OPEN,:SEV=AL1,TID=4; ZEFX:1391:INBR=5:ROU=ACT,POL=OPEN,:SEV=AL1,TID=5; ZEFX:1391:INBR=6:ROU=ACT,POL=OPEN,:SEV=AL3,TID=6; ZEFX:1391:INBR=7:ROU=ACT,POL=OPEN,:SEV=AL2,TID=7; ZEFX:1391:INBR=8:ROU=ACT,POL=OPEN,:SEV=AL3,TID=8; ZEFX:1391:INBR=13:ROU=ACT,POL=OPEN,:SEV=AL1,TID=13; ZEFX:1391:INBR=14:ROU=ACT,POL=OPEN,:SEV=AL3,TID=14; ZEFX:1391:INBR=15:ROU=ACT,POL=OPEN,:SEV=AL1,TID=15; ZEFX:1391:INBR=17:ROU=ACT,POL=OPEN,:SEV=AL1,TID=17; ZEFX:1391:INBR=18:ROU=ACT,POL=OPEN,:SEV=AL2,TID=18; ZEFX:1391:INBR=20:ROU=ACT,POL=OPEN,:SEV=AL1,TID=20;

ZEFX:1201:INBR=1:ROU=ACT,POL=Open,:SEV=AL3,TID=1; ZEFX:1201:INBR=2:ROU=ACT,POL=Open,:SEV=AL2,TID=2; ZEFX:1201:INBR=3:ROU=ACT,POL=Open,:SEV=AL3,TID=3; ZEFX:1201:INBR=4:ROU=ACT,POL=Open,:SEV=AL2,TID=4; ZEFX:1201:INBR=5:ROU=ACT,POL=Open,:SEV=AL3,TID=5; ZEFX:1201:INBR=6:ROU=ACT,POL=Open,:SEV=AL2,TID=6; ZEFX:1201:INBR=7:ROU=ACT,POL=Open,:SEV=AL3,TID=7; ZEFX:1201:INBR=8:ROU=ACT,POL=Open,:SEV=AL2,TID=8; ZEFX:1201:INBR=13:ROU=ACT,POL=Open,:SEV=AL1,TID=13; ZEFX:1201:INBR=14:ROU=ACT,POL=Open,:SEV=AL1,TID=14; ZEFX:1201:INBR=15:ROU=ACT,POL=Open,:SEV=AL1,TID=15; ZEFX:1201:INBR=16:ROU=ACT,POL=Open,:SEV=AL1,TID=16; ZEFX:1201:INBR=17:ROU=ACT,POL=Open,:SEV=AL1,TID=17; ZEFX:1201:INBR=18:ROU=ACT,POL=Open,:SEV=AL1,TID=18; ZEFX:1201:INBR=19:ROU=ACT,POL=NOT,:SEV=AL1,TID=19; ZEFX:1201:INBR=20:ROU=ACT,POL=NOT,:SEV=AL1,TID=20;

USE THIS PART FOR DEFINING ALARM TEXT IN THE BSC, RUN ONLY ONCE PER BSC. IF THERE WILL BE NEW ALARM TEXT, JUST PASTE IT IN COLUMN "B", AND DRAG COLUMN "D" AND "E" TO UPDATE FORMULA. Opto 1 Opto 2 Opto 3 Opto 4 Opto 5 Opto 6 Opto 7 Opto 8 Opto 9 Opto 10 Opto 11 Opto 12 Opto 13 Opto 14 Opto 15 Opto 16 ALARM TEXT SMOKE INTRUDER MOVEMENT HIGH TEMPERATURE AC MAINS FAIL RECTIFIER SYSTEM FAILURE RECTIFIER MODULE FAILURE LOW VOLTAGE PROMPT AIRCON 1 FAILURE AVIATION LIGHT FAILURE BATTERY INTEGRITY/EOV AC PHASE FAIL AIRCON 2 FAILURE ESCOM SUPPLY FAILURE AIRCON 1& 2 ACTIVE DAS/TMB/TMA Alarm INTRUDER SMOKE High Temperature Rectifier Module Fail MOVEMENT RECTIFIER SYSTEM FAILED AC MAINS FAILED BATTERY LOW Aircon 1 Failed EQUIPMENT OVER VOLTAGE Aircraft Light Failed TMA/VSWR ALARM AC Phase Failed ESKOM MAINS FAILED Aircon 2 Failed SEV Critical Major Minor Critical Major Major Major Major Major Minor Major Major Major Major Minor Critical CRITICAL MAJOR MAJOR MINOR MINOR CRITICAL MAJOR CRITICAL MINOR CRITICAL MINOR MAJOR MINOR MAJOR MINOR MINOR TID 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

SC, RUN ONLY ONCE PER BSC. IF THERE WILL BE NEW ALARM TEXT, DRAG COLUMN "D" AND "E" TO UPDATE FORMULA. COMMAND ZEFE:TID=1:TEXT="SMOKE"; ZEFE:TID=2:TEXT="INTRUDER"; ZEFE:TID=3:TEXT="MOVEMENT"; ZEFE:TID=4:TEXT="HIGH TEMPERATURE"; ZEFE:TID=5:TEXT="AC MAINS FAIL"; ZEFE:TID=6:TEXT="RECTIFIER SYSTEM FAILURE"; ZEFE:TID=7:TEXT="RECTIFIER MODULE FAILURE"; ZEFE:TID=8:TEXT="LOW VOLTAGE PROMPT"; ZEFE:TID=9:TEXT="AIRCON 1 FAILURE"; ZEFE:TID=10:TEXT="AVIATION LIGHT FAILURE"; ZEFE:TID=11:TEXT="BATTERY INTEGRITY/EOV"; ZEFE:TID=12:TEXT="AC PHASE FAIL"; ZEFE:TID=13:TEXT="AIRCON 2 FAILURE"; ZEFE:TID=14:TEXT="ESCOM SUPPLY FAILURE"; ZEFE:TID=15:TEXT="AIRCON 1& 2 ACTIVE "; ZEFE:TID=16:TEXT="DAS/TMB/TMA Alarm";

INPUT BCF NUMBER 1301 1301 1301 1301 1301 1301 1301 1301 1301 1301 1301 1301 1301 1301 1301 1301

NOTE: INBR IS THE PORT ON THE BTS SIDE, THEREFOR EQUAL TO TID SEV AL3 AL2 AL1 AL3 AL2 AL2 AL2 AL2 AL2 AL1 AL2 AL2 AL2 AL2 AL1 AL3 POL OPEN OPEN OPEN OPEN OPEN OPEN OPEN OPEN OPEN OPEN OPEN OPEN OPEN OPEN OPEN OPEN

Smoke Intruder Movement High Temperature AC Mains Fail Rectifier System Failure Rectifier Module Failure Low Voltage Prompt (Low Batt) Aircon 1 or 2 Failure Aviation Light Failure Battery Integrity / EOV AC Phase Fail Aircon 2 Failure Escom Supply Failure Aircon 1&2 Active DAS / TMB / TMA Alarm

Critical Major Minor Critical Major Major Major Major Major Minor Major Major Major Major Minor Critical

OTE: INBR IS THE PORT ON THE BTS SIDE, THEREFORE INBR IS NOT ALWAYS EQUAL TO TID COMMAND ZEFX:1301:INBR=1:ROU=ACT,POL=OPEN,:SEV=AL3,TID=1; ZEFX:1301:INBR=2:ROU=ACT,POL=OPEN,:SEV=AL2,TID=2; ZEFX:1301:INBR=3:ROU=ACT,POL=OPEN,:SEV=AL1,TID=3; ZEFX:1301:INBR=4:ROU=ACT,POL=OPEN,:SEV=AL3,TID=4; ZEFX:1301:INBR=5:ROU=ACT,POL=OPEN,:SEV=AL2,TID=5; ZEFX:1301:INBR=6:ROU=ACT,POL=OPEN,:SEV=AL2,TID=6; ZEFX:1301:INBR=7:ROU=ACT,POL=OPEN,:SEV=AL2,TID=7; ZEFX:1301:INBR=8:ROU=ACT,POL=OPEN,:SEV=AL2,TID=8; ZEFX:1301:INBR=9:ROU=ACT,POL=OPEN,:SEV=AL2,TID=9; ZEFX:1301:INBR=10:ROU=ACT,POL=OPEN,:SEV=AL1,TID=10; ZEFX:1301:INBR=11:ROU=ACT,POL=OPEN,:SEV=AL2,TID=11; ZEFX:1301:INBR=12:ROU=ACT,POL=OPEN,:SEV=AL2,TID=12; ZEFX:1301:INBR=13:ROU=ACT,POL=OPEN,:SEV=AL2,TID=13; ZEFX:1301:INBR=14:ROU=ACT,POL=OPEN,:SEV=AL2,TID=14; ZEFX:1301:INBR=15:ROU=ACT,POL=OPEN,:SEV=AL1,TID=15; ZEFX:1301:INBR=16:ROU=ACT,POL=OPEN,:SEV=AL3,TID=16;

SMOKE INTRUDER MOVEMENT High Temperature AC MAINS FAIL RECTIFIER SYSTEM FAIL Rectifier Module Fail BATTERY LOW Aircon 1 or 2 Failure NAVIGATION LIGHTS BATTERY INTEGRITY PHASE FAIL Aircon 2 Fail ESKOM FAIL Both Aircons Running TMA Fail

USE THIS PART FOR DEFINING ALARM TEXT IN THE BSC, RUN ONLY ONCE PER BSC. IF THERE WILL BE NEW ALARM TEXT, COLUMN "B", AND DRAG COLUMN "D" AND "E" TO UPDATE FORMULA. SMOKE INTRUDER MOVEMENT HIGH TEMPERATURE AC MAINS FAIL RECTIFIER SYSTEM FAILURE RECTIFIER MODULE FAILURE LOW VOLTAGE PROMPT AIRCON 1 OR 2 FAILURE AVIATION LIGHT FAILURE BATTERY INTEGRITY/EOV AC PHASE FAIL AIRCON 2 FAILURE ESCOM SUPPLY FAILURE AIRCON 1& 2 ACTIVE DAS/TMB/TMA Alarm ALARM TEXT SMOKE INTRUDER MOVEMENT HIGH TEMPERATURE AC MAINS FAIL RECTIFIER SYSTEM FAILURE RECTIFIER MODULE FAILURE LOW VOLTAGE PROMPT Aircon 1 or 2 Failure Aviation Light Failure EQUIPMENT OVER VOLTAGE AC PHASE FAIL AIRCON 2 FAILURE ESCOM SUPPLY FAILURE AIRCON 1& 2 ACTIVE INVERTER FAIL SEV
Critical Major Minor Critical Major Major Major Major Major Minor Major Major Major Major Minor Major

TID 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

SMOKE INTRUDER MOVEMENT HIGH TEMPERATURE AC MAINS FAIL RECTIFIER SYSTEM FAILURE RECTIFIER MODULE FAILURE LOW VOLTAGE PROMPT AIRCON 1 FAILURE AVIATION LIGHT FAILURE BATTERY INTEGRITY/EOV AC PHASE FAIL AIRCON 2 FAILURE ESCOM SUPPLY FAILURE AIRCON 1& 2 ACTIVE DAS/TMB/TMA Alarm

E PER BSC. IF THERE WILL BE NEW ALARM TEXT, JUST PASTE IT IN AND "E" TO UPDATE FORMULA. COMMAND ZEFE:TID=1:TEXT="SMOKE"; ZEFE:TID=2:TEXT="INTRUDER"; ZEFE:TID=3:TEXT="MOVEMENT"; ZEFE:TID=4:TEXT="HIGH TEMPERATURE"; ZEFE:TID=5:TEXT="AC MAINS FAIL"; ZEFE:TID=6:TEXT="RECTIFIER SYSTEM FAILURE"; ZEFE:TID=7:TEXT="RECTIFIER MODULE FAILURE"; ZEFE:TID=8:TEXT="LOW VOLTAGE PROMPT"; ZEFE:TID=9:TEXT="Aircon 1 or 2 Failure"; ZEFE:TID=10:TEXT="Aviation Light Failure"; ZEFE:TID=11:TEXT="EQUIPMENT OVER VOLTAGE"; ZEFE:TID=12:TEXT="AC PHASE FAIL"; ZEFE:TID=13:TEXT="AIRCON 2 FAILURE"; ZEFE:TID=14:TEXT="ESCOM SUPPLY FAILURE"; ZEFE:TID=15:TEXT="AIRCON 1& 2 ACTIVE "; ZEFE:TID=16:TEXT="INVERTER FAIL";

INPUT BCF NUMBER 1201 1201 1201 1201 1201 1201 1201 1201 1201 1201 1201 1201 1201 1201 1201 1201

NOTE: INBR IS THE PORT ON THE BTS SIDE, THEREFOR EQUAL TO TID SEV AL3 AL2 AL1 AL3 AL2 AL2 AL2 AL2 AL2 AL1 AL2 AL2 AL2 AL2 AL1 AL2 POL CLOSED CLOSED CLOSED CLOSED CLOSED CLOSED CLOSED CLOSED CLOSED CLOSED CLOSED CLOSED CLOSED CLOSED CLOSED CLOSED

OTE: INBR IS THE PORT ON THE BTS SIDE, THEREFORE INBR IS NOT ALWAYS EQUAL TO TID COMMAND ZEFX:1201:INBR=1:ROU=ACT,POL=CLOSED,:SEV=AL3,TID=1; ZEFX:1201:INBR=2:ROU=ACT,POL=CLOSED,:SEV=AL2,TID=2; ZEFX:1201:INBR=3:ROU=ACT,POL=CLOSED,:SEV=AL1,TID=3; ZEFX:1201:INBR=4:ROU=ACT,POL=CLOSED,:SEV=AL3,TID=4; ZEFX:1201:INBR=5:ROU=ACT,POL=CLOSED,:SEV=AL2,TID=5; ZEFX:1201:INBR=6:ROU=ACT,POL=CLOSED,:SEV=AL2,TID=6; ZEFX:1201:INBR=7:ROU=ACT,POL=CLOSED,:SEV=AL2,TID=7; ZEFX:1201:INBR=8:ROU=ACT,POL=CLOSED,:SEV=AL2,TID=8; ZEFX:1201:INBR=9:ROU=ACT,POL=CLOSED,:SEV=AL2,TID=9; ZEFX:1201:INBR=10:ROU=ACT,POL=CLOSED,:SEV=AL1,TID=10; ZEFX:1201:INBR=11:ROU=ACT,POL=CLOSED,:SEV=AL2,TID=11; ZEFX:1201:INBR=12:ROU=ACT,POL=CLOSED,:SEV=AL2,TID=12; ZEFX:1201:INBR=13:ROU=ACT,POL=CLOSED,:SEV=AL2,TID=13; ZEFX:1201:INBR=14:ROU=ACT,POL=CLOSED,:SEV=AL2,TID=14; ZEFX:1201:INBR=15:ROU=ACT,POL=CLOSED,:SEV=AL1,TID=15; ZEFX:1201:INBR=16:ROU=ACT,POL=CLOSED,:SEV=AL2,TID=16;

ZEFX:1082:INBR=1:ROU=NOT,POL=OPEN,:SEV=AL1,TID=0; ZEFX:1082:INBR=2:ROU=NOT,POL=OPEN,:SEV=AL1,TID=0; ZEFX:1082:INBR=3:ROU=NOT,POL=OPEN,:SEV=AL1,TID=0; ZEFX:1082:INBR=4:ROU=NOT,POL=OPEN,:SEV=AL1,TID=0; ZEFX:1082:INBR=5:ROU=NOT,POL=OPEN,:SEV=AL1,TID=0; ZEFX:1082:INBR=6:ROU=NOT,POL=OPEN,:SEV=AL1,TID=0; ZEFX:1082:INBR=7:ROU=NOT,POL=OPEN,:SEV=AL1,TID=0; ZEFX:1082:INBR=8:ROU=NOT,POL=OPEN,:SEV=AL1,TID=0; ZEFX:1082:INBR=9:ROU=NOT,POL=OPEN,:SEV=AL1,TID=0; ZEFX:1082:INBR=10:ROU=NOT,POL=OPEN,:SEV=AL1,TID=0; ZEFX:1082:INBR=11:ROU=NOT,POL=OPEN,:SEV=AL1,TID=0; ZEFX:1082:INBR=12:ROU=NOT,POL=OPEN,:SEV=AL1,TID=0; ZEFX:1082:INBR=13:ROU=NOT,POL=OPEN,:SEV=AL1,TID=0; ZEFX:1082:INBR=14:ROU=NOT,POL=OPEN,:SEV=AL1,TID=0; ZEFX:1082:INBR=15:ROU=NOT,POL=OPEN,:SEV=AL1,TID=0; ZEFX:1082:INBR=16:ROU=NOT,POL=OPEN,:SEV=AL1,TID=0;