Filter air quality required The purity of the compressed air for instruments in the usage point must

fulfill class ISO - 8573 1:2010 [1:2:1] (particle size 1 m dew point -40C, total oil concentration <0.01 mg/m3); to 7 kg/cm (100 PSIG).

Therefore purity required is [1:2:1] Class 1 for particles

Class 2 for humidity and liquid water

Class 1 for oil content