FU-I1 Power supply for sensors


AC 24 V to DC 15 V power supply for active DC 15 V sensors suitable for use with all active sensors can be placed in duct sensor housing, wallboxes or in control panels

151

FU-I1

Technical data
Power supply (input) Output Output current Sensor signal Terminal connections Protection Protection class Ambient temperatures: Operation Storage, transport Weight Dimensions AC 24 V 15 % (SELV) DC 15 V 10 % Imax DC 20 mA unchanged Screw terminals 2.5 mm2 III (2) IP20 to IEC529 0 ... 50 C 25 ... 70 C 0.03 kg 56 x 22 x 18mm

Principle of operation
The FU-I1 power supply is only used when AC 24 V are available but the sensor requires DC 15 V : e.g. CLASSIC with the FKA-H2. Terminals 3 and 6 are permanently connected and are reserved for feeding through the sensor signal DC 0 ...10 V . In addition, a fixed connection is provided between terminals 4 and 5 for earthing, cable screening etc.

Construction
The plastic housing, which is enclosed in heatshrink sleeving, contains the printed circuit board with the electronics and the connection terminals.

Siemens Building Technologies Landis & Staefa Division

CA1N5151E / 11.1998 1/2

Mounting
The power supply can be mounted or placed wherever necessary: in the FKA-H2 or FKA-H2/T1 duct sensor housing (for room sensors) in wall boxes in the control panel on DIN rails or in cable ducts in sill cladding in ceilings voids Care should be taken that the environment is dry. Mounting on a DIN rail
40779

Mounting in a flush box


40780

FU-I1

Cable binder

Mounting in a sensor housing

40781

Dimensions
40782 NS AC24V (SGND) COM 0 LS AC24V OX 0...10V DC15V + 0...10V S

5 6 7 8

55

Terminal layout
40783

SGND

Com 0

1 2 3 4 5 6 7 8

NS AC 24 V LS DC 0 ... 10 V

Controller

DC 0 ... 10 V + DC 15 V

Sensor

1998 Siemens Building Technologies Ltd. CA1N5151E / 11.1998 2/2 Siemens Building Technologies Landis & Staefa Division

18

1 2 3 4

FU-I1