Вы находитесь на странице: 1из 1

B F P PERMISSIVES

(1) (2) (3) (4) (5) (6) (7) CIRCUIT BREAKER IN SERVICE POSITION NO TRIP CONDITION PERSIST BOOSTER PUMP SUCTION PRESSURE ADEQUATE SUCTION VALVE OPEN R.C. VALVE OPEN DEARATOR LEVEL ADEQUATE 2085 mm EITHER DISCHARGE VALVE CLOSED OR DISCHARGE HEADER PRESSURE ADEQUATE (8) LUBRACATING OIL PRESSURE ADEQUATE MORE THAN 2.0 KG/CM2

TRIPPINGS
(1) DEARATOR LEVEL VERY LOW SENSED BY ANY TWO OUT OF THREE SWITCHES IS LESS THAN 1785 mm ** ALL RUNNING BFP s TRIP ON DEARATOR LEVEL VERY LOW TRIP (2) WORKING OIL TEMPERATURE VERY HIGH : 130 * C (3) MOTOR WINDING TEMPERATURE VERY HIGH : 120 * C (4) MOTOR BEARING TEMPERATURE VERY HIGH : 75 * C (5) PUMP BEARING TEMPERATURE VERY HIGH : 95 * C (6) BFP SUCTION FLOW VERY HIGH : 480 TPH for 30 sec (7) LUBRICATING OIL PRESSURE VERY LOW (8) BOOSTER PUMP DISCHARGE PRESSURE LOW (9) FEED WATER DT( Diff Temp) VERY HIGH : 0.5 KG/CM2 : 9 KG/CM2 : 15 *C

**This Tripping Comes In Service After 30 SECONDS OF BFP Starting (10) DISCHARGE TEMPERATURE HIGH : 180 * C

NOTE

: Aux RELAY 74 WILL OPERATE ON 6.6 KV BFP PANEL FOR ABOVE TRIPPING

DRUM LEVEL
(1) NORMAL LEVEL : (+) 50 TO (-) 50 mm (2) DRUM LEVEL HIGH : (+) 100 ALARM ; (+) 225 TRIP UNIT TRIP (3) DRUM LEVEL LOW : (-) 100 ALARM ; (-) 225 TRIP UNIT TRIP