The Tata Power Company Ltd.

Rev. No.: 00 Rev. Date: 01-01-2003

EQA Group
Doc. No: EQA-WI-52 Page No. 1 of 2

Work Instruction For VOLTAGE RATIO Test on Transformer Prepared by Engineer

1. Rev. No. 00

RECORD OF REVISIONS Date Details 01.01.03 First Time issued for QMS

Reviewed by SH

Approved by AGM

2 SCOPE) The test procedure guides the EQAEngineer in carrying out Voltage Ratio Test on Transformers. 3. Sr. No. 3.1 3.2 INPUTS Activity / Documents Supplies : 440 V, three phase 50 Hz. Instruments: .1 3 pole switch with fuse or MCCB .2 A.C. voltmeter / Multimeter: 0-600V 2 No. .3 1 Variac. 0-260V REFERENCE : Manufacturer manual Earlier Test record CIRCUIT DIAGRM - (Refer enclosed fig.A ) PREREQUISITES Activity Ensure that the transformer under test is de-energized. In the case of system transformers, ensure that the maintenance engineer has taken the necessary permits and isolated the transformer. Ensure that oil is filled in the transformer and no vacuum is applied. Ensure that no parallel circuits are connected to the transformer under test and there are no shorts on the secondary side/ primary side ACTIVITIES Activity / Documents Apply 440V, 3 phase 15 A fused supply to the transformer primary winding. Measure induced voltages on the secondary winding. Vary primary taps and repeat step 7.2 RECORDS Activity / Documents Test Format is as per EQA-FM-TR

1 No.

4. 4.1 4.2 5. 6. Sr. No. 6.1 6.2 6.3 7. Sr. No. 7.1 7.2 8 Sr. No. 8.1

The Tata Power Company Ltd.


Rev. No.: 00 Rev. Date: 01-01-2003

EQA Group
Doc. No: EQA-WI-52 Page No. 2 of 2

Work Instruction For VOLTAGE RATIO Test on Transformer

9. Sr. No. 9.1 10. 10.1 10.2 10.3 10.4

LIMITS Activity / Documents Maximum variation from marked value : 1% CORRECTIVE ACTIONS WHEN DEVIATIONS ARE BEYOND LIMITS The Engineer shall repeat the test and confirm the result with firm connections at all possible taps. The Engineer shall convey the deviations to SH/AGM/DGM With the concurrence of DGM the engineer/SH shall instruct the EMD to rectify the defect. The Engineer shall carry out the test after the defect is attended to.

Figure-A: Circuit Diagram for Transformer Voltage Ratio Test:

A V 3 Variac 3 ac supply B C N

a V b c n

Transformer