SSW-06 Delta Connected ISoft-Starter = Irequired 3 ISoft-Starter= Irequired 1,5 = 58% of Irequired
(after the start)
= 67% of Irequired
(during start)
Notes g At the Starting, for the same motor power, the Inside Delta connection (6 leads) allows for a reduction of 33% of the Soft Starter current if compared to the 3 leads connection. Even when the motor is up to speed a reduction of 43% of the Soft Starter current is achieved by using 6 leads connection. Basically the Inside Delta connection option offered by the SSW-06 gives the costumer alernative ways of reducing cost and size when it comes to Soft Starter solutions. g A 6 leads motor is required when Inside Delta Connection is used.
MOTOR 220V - / 380V-Y 380V - / 660V-Y 440V - / 760V-Y 575V - 220V - / 380V- Y/ 440V - / 760V-Y
or the same motor power, the Inside Delta Connection (6 leads), a reduction of 42% of the soft- starter current compared F to the standard connection (3 leads). g The Inside Delta connection (6 leads) allows the soft-starter to start a motor 73% greater than the standard connection (3 leads). g The Inside Delta connection requires 6 leads from the soft-starter to the motor. g During the start, the motor current can be 1.5 times greater than the soft-starter one. g After the start, the motor current can be 1.73 times greater than the soft-starter.
g
Soft-Starters
21