Вы находитесь на странице: 1из 5

Version: 1.0.9.

0
Current transformer caIcuIation
Quantity:
1
9/30/2013 10:41:44 AM 1 / 5
Core
1S1 ÷ 1S2
Type: TPU53.23 400-800/1/1
Ratio
400/1 A
Class
5P20
Burden
15VA
|th
25kA / 1s
Ìdyn
65kA
f
60Hz
Project number:
Ìtem:
Curves and calculated values are only theoretical.
Magnetization curve 1S1 - 1S2
Ukp/Ual Rct Ìo/Ìal
Required values
Calculated values 294.50V 0.0220A
Kssc
0.0
Rb
-
-
K
9/30/2013 10:41:44 AM 2 / 5
Core
1S1 ÷ 1S3
Type: TPU53.23 400-800/1/1
Ratio
800/1 A
Class
5P20
Burden
30VA
|th
25kA / 1s
Ìdyn
65kA
f
60Hz
Project number:
Ìtem:
Curves and calculated values are only theoretical.
Magnetization curve 1S1 - 1S3
Ukp/Ual Rct Ìo/Ìal
Required values
Calculated values 589.00V 0.0110A
Kssc
0.0
Rb
-
-
K
9/30/2013 10:41:44 AM 3 / 5
Core
2S1 ÷ 2S2
Type: TPU53.23 400-800/1/1
Ratio
400/1 A
Class
0.2FS5
Burden
15VA
|th
25kA / 1s
Ìdyn
65kA
f
60Hz
Project number:
Ìtem:
Curves and calculated values are only theoretical.
Magnetization curve 2S1 - 2S2
Ukp/Ual Rct Ìo/Ìal
Required values
Calculated values 25.70V 0.0010A
Kssc
0.0
Rb
-
-
K
9/30/2013 10:41:44 AM 4 / 5
Core
2S1 ÷ 2S3
Type: TPU53.23 400-800/1/1
Ratio
800/1 A
Class
0.2FS5
Burden
30VA
|th
25kA / 1s
Ìdyn
65kA
f
60Hz
Project number:
Ìtem:
Curves and calculated values are only theoretical.
Magnetization curve 2S1 - 2S3
Ukp/Ual Rct Ìo/Ìal
Required values
Calculated values 51.50V 0.0010A
Kssc
0.0
Rb
-
-
K
9/30/2013 10:41:44 AM 5 / 5