TABLE 1 REQUIRED GEOTECHNICAL SPECIAL INSPECTIONS

INSPECTION SYSTEM or MATERIAL


IBC CODE REFERENCE

CODE or STANDARD REFERENCE

FREQUENCY Continuous Periodic

REMARKS

SOILS
GEOTECHNICAL INVESTIGATIONS 1803 GEOTECHNICAL INVESTIGATION SHALL INCLUDE ITEMS OF SPECIAL INSPECTION AND TESTING AS NOTED IN TABLE 5 OF THE GUIDELINES X (a) TABLE 1704.7 GEOTECHNICAL REPORT X X BY THE GEOTECHNICAL ENGINEER

VERIFY FOOTING BEARING CAPACITY AND SUBGRADE PREPARATION FOR FILLS FILL MATERIAL VERIFICATION FILL PLACEMENT & COMPACTION VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE ADEQUATE TO ACHIEVE THE DESIGN BEARING CAPACITY VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE REACHED PROPER MATERIAL PERFORM CLASSIFICATION OF COMPACTED FILL MATERIALS VERIFY USE OF PROPER MATERIALS, DENSITIES AND LIFT THICKNESSES DURING PLACEMENT AND COMPACTION OF COMPACTED FILL PRIOR TO PLACEMENT OF COMPACTED FILL, OBSERVE SUBGRADE AND VERIFY THAT SITE HAS BEEN PREPARED PROPERLY

TABLE 1704.7 TABLE 1704.7

X (a)

BY THE GEOTECHNICAL ENGINEER

TABLE 1704.7 1803.5.1 TABLE 1704.7

BY THE GEOTECHNICAL ENGINEER

TABLE 1704.7

PILING
INSTALLATION 1704.8 GEOTECHNICAL REPORT X BY THE GEOTECHNICAL ENGINEER

VERIFY ELEMENT MATERIALS, SIZES AND LENGTHS COMPLY WITH THE REQUIREMENTS

TABLE 1704.8

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

TABLE 1 REQUIRED GEOTECHNICAL SPECIAL INSPECTIONS


INSPECTION SYSTEM or MATERIAL
DETERMINE CAPACITIES OF TEST ELEMENTS AND CONDUCT ADDITIONAL LOAD TESTS, AS REQUIRED OBSERVE DRIVING OPERATIONS AND MAINTAIN COMPLETE AND ACCURATE RECORDS FOR EACH ELEMENT VERIFY PLACEMENT LOCATIONS AND PLUMBNESS, CONFIRM TYPE AND SIZE OF HAMMER, RECORD NUMBER OF BLOWS PER FOOT OF PENETRATION, DETERMINE REQUIRED PENETRATIONS TO ACHIEVE DESIGN CAPACITY, RECORD TIP AND BUTT ELEVATIONS AND DOCUMENT AND DAMAGE TO FOUNDATION ELEMENT
IBC CODE REFERENCE

CODE or STANDARD REFERENCE

FREQUENCY Continuous Periodic

REMARKS

SOILS
TABLE 1704.8 X OBSERVATION BY GEOTECHNICAL ENGINEER

TABLE 1704.8

TABLE 1704.8

FOR STEEL ELEMENTS, PERFORM ADDITIONAL INSPECTIONS IN ACCORDANCE WITH SECTION 1704.3 FOR CONCRETE ELEMENTS AND CONCRETEFILLED ELEMENTS, PERFORM ADDITIONAL INSPECTIONS IN ACCORDANCE WITH SECTION 1704.4

TABLE 1704.8

TABLE 1704.8

FOR SPECIALTY ELEMENTS, PERFORM ADDITIONAL INSPECTIONS AS DETERMINED BY THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE

TABLE 1704.8

PIER FOUNDATIONS
DRILLING AND TESTING OBSERVE DRILLING OPERATIONS AND MAINTAIN COMPLETE AND ACCURATE RECORDS FOR EACH ELEMENT TABLE 1704.9 TABLE 1704.9 GEOTECHNICAL REPORT X BY THE GEOTECHNICAL ENGINEER

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

TABLE 1 REQUIRED GEOTECHNICAL SPECIAL INSPECTIONS


INSPECTION SYSTEM or MATERIAL
IBC CODE REFERENCE

CODE or STANDARD REFERENCE

FREQUENCY Continuous Periodic

REMARKS

SOILS
VERIFY PLACEMENT LOCATIONS AND PLUMBNESS, CONFIRM ELEMENT DIAMETERS, BELL DIAMETERS (IF APPLICABLE), LENGTHS, EMBEDMENT INTO BEDROCK (IF APPLICABLE) AND ADEQUATE END-BEARING STRATA CAPACITY. RECORD CONCRETE OR GROUT VOLUMES. FOR CONCRETE ELEMENTS, PERFORM ADDITIONAL INSPECTIONS IN ACCORDANCE WITH SECTION 1704.4

TABLE 1704.9

TABLE 1704.9

SCREW ANCHORS
GEOTECHNICAL, RESEARCH AND/OR REPORT AND ICC EVALUATION REPORTS BY THE GEOTECHNICAL ENGINEER SPECIAL INSPECTIONS APPLY TO VERIFYING MANUFACTURER'S CERTIFICATION OF INSTALLERS, HELICAL ANCHOR AND BRACKET PRODUCT NAME, TYPES, INSTALLATION EQUIPMENT USED, FINAL TORQUE, PILE DIMENSIONS, EMBEDMENT DEPTH AND TIP EVALUATION

INSTALLATION

1704.10

MECHANICALLY STABILIZED EARTH (MSE) RETAINING WALLS


BY THE GEOTECHNICAL ENGINEER SPECIAL INSPECTIONS APPLY TO MODULAR UNIT PRODUCT NAME, TYPE, AND DIMENSIONS, FOUNDATION PREPARATION, MODULAR UNIT PLACEMENT, INCLUDING ALIGNMENT AND INCLINATION, GEOSYNTHETIC REINFORCEMENT PRODUCT NAME, TYPE, AND PLACEMENT, BACKFILL PLACEMENT AND COMPACTION, AND DRAINAGE PROVISIONS

INSTALLATION

1704.15

GEOTECHNICAL RESEARCH AND/OR REPORT AND ICC EVALUATION REPORTS

TENSION ANCHORS
INSTALLATION 1704.15 STRESSING GEOTECHNICAL REPORT X BY THE GEOTECHNICAL ENGINEER SPECIAL INSPECTIONS APPLY TO TENDON TYPE AND SIZE, CORROSION PROTECTION, DEPTH OF EMBEDMENT, BONDED LENGTH, TYPE OF GROUT USED, AND RECORD OF PRESTRESS

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

TABLE 1 REQUIRED GEOTECHNICAL SPECIAL INSPECTIONS


INSPECTION SYSTEM or MATERIAL
IBC CODE REFERENCE

CODE or STANDARD REFERENCE

FREQUENCY Continuous Periodic

REMARKS

SOILS STONE COLUMNS


GEOTECHNICAL RESEARCH AND/OR REPORT AND ICC EVALUATION REPORTS BY THE GEOTECHNICAL ENGINEER SPECIAL INSPECTIONS APPLY TO HOLE SIZE AND DEPTH, VERIFICATION OF AGGREGATE MATERIAL, NUMBER AND LIFTS OF AGGREGATE, INSTALLATION RAMMER ENERGY, AND TOP OF PIER ELEVATION

INSTALLATION

1704.15

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

TABLE 2 REQUIRED STRUCTURAL SPECIAL INSPECTIONS


INSPECTION SYSTEM or MATERIAL
IBC CODE REFERENC E FREQUENCY CODE or STANDARD REFERENCE Continuous Periodic

REMARKS

FABRICATORS
SPECIAL INSPECTIONS APPLY TO VERIFICATION OF DETAILED FABRICATION AND QUALITY CONTROL PROCEDURES INCLUDING REVIEW FOR COMPLETENESS AND ADEQUACY RELATIVE TO THE CODE REQUIREMENTS

FABRICATORS

1704.2

CONCRETE
INSPECTION OF ANCHORS INSTALLED IN HARDENED CONCRETE REINFORCING STEEL AND PRESTRESSING TENDON PLACEMENT 1912.1 1704.4 1907.5 1913.4 1901.4.2 1704.3.1 1903.1 TABLE 1704.4 ACI 318: 3.8.6, 8.1.3, 21.1.8 ACI 318: 3.5 ACI 318: 7.1-7.7 X (a)

TOLERANCES AND REINFORCING PLACEMENT PER ACI 7.5; SPACING LIMITS FOR REINFORCING ACI 7.6 REFER TO STEEL FOR WELDING REQUIREMENTS TABLE 1704.3, ITEM 5b

WELDING REINFORCING STEEL 1) VERIFICATION OF WELDABILITY OF REINFORCING STEEL OTHER THAN ASTM A 706

ACI 318: 3.5.2 AWS D1.4 AWS D1.4 ACI 318: SECTION 3.5.2

2) REINFORCING STEEL RESISTING FLEXURAL AND AXIAL FORCES IN INTERMEDIATE AND SPECIAL MOMENT FRAMES, AND BOUNDARY ELEMENTS OF SPECIAL STRUCTURAL WALLS OF CONCRETE AND SHEAR REINFORCEMENT

AWS D1.4 ACI 318: SECTION 3.5.2

X (b)

3) SHEAR REINFORCEMENT

AWS D1.4 ACI 318: SECTION 3.5.2 TABLE 1704.4 TABLE 1704.4 1911.5 1912.1 AWS D1.4 ACI 318: SECTION 3.5.2 ACI 318: 1.3.2.C ACI 318: 8.1.3 ACI 318: 21.1.8

4) OTHER REINFORCING STEEL. PLACEMENT OF BOLTS INSTALLED IN CONCRETE WHERE ALLOWABLE LOADS HAVE BEEN INCREASED OR WHERE STRENGTH DESIGN IS USED

ALL BOLTS VISUALLY INSPECTED

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

TABLE 2 REQUIRED STRUCTURAL SPECIAL INSPECTIONS


INSPECTION SYSTEM or MATERIAL
IBC CODE REFERENC E TABLE 1704.4 VERIFYING USE OF REQUIRED MIX DESIGN(S) 1904 1905.2-4 1913.2 1913.3 1901.4.1 TABLE 1704.4 1905.9-10 TABLE 1704.4 1913.6-8 CONCRETE PLACEMENT AT COMPOSITE SLABS TABLE 1704.4 TABLE 1704.4 CONCRETE/SHOTCRETE CURING 1905.11-13 1913.9 VERIFICATION OF IN-SITU CONCRETE STRENGTH PRIOR TO STRESSING OF TENDONS IN POST-TENSIONED CONCRETE TABLE 1704.4 1901.4.9 TABLE 1704.4 1901.4.10 INSPECTION OF PRESTRESSED CONCRETE: a. APPLICATION OF PRESTRESSING FORCES TABLE 1704.4 ACI 318: 18.20 X ACI 318: 1.3.2.F ACI 318: 18.20.1 ASCE 9, CHAPTER 3 X FREQUENCY CODE or STANDARD REFERENCE Continuous Periodic

REMARKS

FABRICATORS

ACI 318: CHAPTER 4 ACI 318: 5.2-5.4

CONCRETE PLACEMENT

ACI 318: 1.3.2.D ACI 318: 5.9 - 5.10

SHOTCRETE PLACEMENT

ACI 318: 1.3.2.D ACI 318: 5.11-5.13

X (a)

ACI 318: 18.13.4.3

X (a)

STRESSING OF TENDONS IN POSTTENSIONED CONCRETE

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

TABLE 2 REQUIRED STRUCTURAL SPECIAL INSPECTIONS


INSPECTION SYSTEM or MATERIAL
IBC CODE REFERENC E TABLE 1704.4 FREQUENCY CODE or STANDARD REFERENCE Continuous Periodic

REMARKS

FABRICATORS
b. GROUTING OF BONDED PRESTRESSING TENDONS IN THE SEISMIC-FORCERESISTING SYSTEM ACI 318: 18.18.4 X

ERECTION OF PRECAST MEMBERS

TABLE 1704.4 TABLE 1704.4 1906.2 TABLE 1704.4 1906.1

ACI 318: 1.3.2.E ACI 318: CHAPTER 16

X (a)

ALL CONNECTIONS VISUALLY INSPECTED REFER TO ANCHOR BOLT WELDING REQUIREMENTS AND STRUCTURAL INTEGRITY PROVISIONS

VERIFICATION OF IN-SITU CONCRETE PRIOR TO REMOVAL OF FORMS AND SHORES FROM ELEVATED BEAMS AND STRUCTURAL SLABS

ACI 318: 6.2

X (a)

VERIFICATION OF FORMWORK

ACI 318: 6.1.1

X (a)

SPECIAL INSPECTIONS APPLY TO SHAPE, LOCATION AND DIMENSIONS OF THE CONCRETE MEMBER BEING FORMED

MASONRY LEVEL 1
COMPLIANCE WITH REQUIRED INSPECTION PROVISIONS OF THE CONSTRUCTION DOCUMENTS AND THE APPROVED SUBMITTALS SHALL BE VERIFIED VERIFICATION OF F'm AND F'aac PRIOR TO CONSTRUCTION EXCEPT WHERE SPECIFICALLY EXEMPTED BY THIS CODE

TMS 602: 1.5

TMS 602: 1.4B

VERIFICATION OF SLUMP FLOW AND VSI AS TMS 602: 1.5B.1.b.3 X DELIVERED TO THE SITE FOR SELFCONSOLIDATING GROUT. AS MASONRY CONSTRUCTION BEGINS, THE FOLLOWING SHALL BE VERIFIED TO ENSURE COMPLIANCE: A) VERIFICATION OF SITE-PROPORTIONED MORTAR B) LOCATION OF REINFORCEMENT AND CONNECTORS AND PRESTRESSING TENDONS AND ANCHORAGE TMS 602: 2.6 A X

TMS 602 3.4, 3.6a

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

TABLE 2 REQUIRED STRUCTURAL SPECIAL INSPECTIONS


INSPECTION SYSTEM or MATERIAL
IBC CODE REFERENC E FREQUENCY CODE or STANDARD REFERENCE Continuous Periodic

REMARKS

FABRICATORS
C) CONSTRUCTION OF MORTAR JOINTS TMS 602: 3.3 B X (a)

D) VERIFICATION OF PRESTRESSING TECHNIQUE E) GRADE AND SIZE OF PRESTRESSING TENDONS AND ANCHORAGE

TMS 602: 3.6 B

TMS 602: 2.4B, 2.4H

DURING CONSTRUCTION THE INSPECTION PROGRAM SHALL VERIFY: A) SIZE AND LOCATION OF STRUCTURAL ELEMENTS B) ANCHORAGE OF MASONRY TO FRAMES, STRUCTURAL MEMBERS, AND DIAPHRAGMS TMS 602: 3.3 F TMS 402: 1.16.1 TMS 402: 1.2.2 (e) TMS 402: 2.1.4 TMS 402: 3.1.6 TMS 402: 1.15 TMS 602: 2.4 TMS 602: 3.4 TMS 402: 2.1.9.7.2 TMS 402: 3.3.3.4 (b) X

X (a)

(b)

C) SPECIFIED SIZE, GRADE AND TYPE OF REINFORCEMENT, ANCHOR BOLTS, PRESTRESSING TENDONS AND ANCHORAGES. D) WELDING REINFORCING STEEL PREPARATION, CONSTRUCTION, AND PROTECTION DURING COLD WEATHER (TEMPERATURE BELOW 40F) AND HOT WEATHER (TEMPERATURE ABOVE 90F)

ALL WELDS VISUALLY INSPECTED PER AWS D1.4 7.5

2104.3 2104.4

TMS 602: 1.8C TMS 602: 1.8D

X (a)

APPLICATION AND MEASUREMENT OF PRESTRESSING FORCES

TMS 602: 3.6B

(b)

PRIOR TO GROUTING, THE FOLLOWING SHALL BE VERIFIED TO ENSURE COMPLIANCE: VERIFYING GROUT SPACE IS CLEAN PRIOR TO GROUTING PLACEMENT OF REINFORCEMENT AND CONNECTORS AND PRESTRESSING TENDONS AND ANCHORAGES TMS 602: 3.2D X (b)

TMS 402: 1.13 TMS 602: 3.4

X (a)

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

TABLE 2 REQUIRED STRUCTURAL SPECIAL INSPECTIONS


INSPECTION SYSTEM or MATERIAL
IBC CODE REFERENC E FREQUENCY CODE or STANDARD REFERENCE Continuous Periodic

REMARKS

PROPORTIONS OF SITE PREPARED GROUT AND PRESTRESSING GROUT FOR BONDED TENDONS CONSTRUCTION OF MORTAR JOINTS GROUT PLACEMENT SHALL BE VERIFIED TO ENSURE COMPLIANCE GROUT PLACEMENT AT PRESTRESSING TENDONS PREPARATION OF ANY REQUIRED GROUT SPECIMENS, MORTAR SPECIMENS AND/OR PRISMS SHALL BE OBSERVED

FABRICATORS
TMS 602: 2.6B X

TMS 602: 3.3B

TMS 602: 3.5

TMS 602: 3.6C

2105.2.2 2105.3

TMS 602: 1.4

MASONRY LEVEL 2
COMPLIANCE WITH REQUIRED INSPECTION PROVISIONS OF THE CONSTRUCTION DOCUMENTS AND THE APPROVED SUBMITTALS VERIFICATION OF F'm AND F'AAC PRIOR TO CONSTRUCTION AND FOR EVERY 5,000 SQUARE FEET DURING CONSTRUCTION VERIFICATION OF PROPORTIONS OF MATERIALS IN PREMIXED OR PREBLENDED MORTAR AND GROUT AS DELIVERED TO THE SITE VERIFICATION OF SLUMP FLOW AND VSI AS DELIVERED TO THE SITE FOR SELFCONSOLIDATING GROUT VERIFICATION OF SITE-PREPARED MORTAR, GROUT AND PRESTRESSING GROUT FOR BONDED TENDONS PLACEMENT OF MASONRY UNITS AND MORTAR JOINT CONSTRUCTION TMS 602: 1.5 X

TMS 602: 1.4B

TMS 602: 1.5B

TMS 602: 1.5B.1.b.3

TMS 602: 2.6A

TMS 602: 3.3B

X (a)

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

TABLE 2 REQUIRED STRUCTURAL SPECIAL INSPECTIONS


INSPECTION SYSTEM or MATERIAL
IBC CODE REFERENC E FREQUENCY CODE or STANDARD REFERENCE Continuous Periodic

REMARKS

VERIFICATION OF SIZE AND LOCATION OF STRUCTURAL ELEMENTS TYPE, SIZE AND LOCATION OF ANCHORS, INCLUDING OTHER DETAILS OF ANCHORAGE OF MASONRY TO STRUCTURAL MEMBERS, FRAMES OR OTHER CONSTRUCTION

FABRICATORS
TMS 602: 3.3F X

TMS 402: 1.16.1 TMS 402: 1.2.2 (e)

(b)

TYPE, GRADE, AND SIZE OF REINFORCING STEEL, ANCHOR BOLTS, PRESTRESSING TENDONS AND ANCHORAGES PLACEMENT OF REINFORCEMENT, CONNECTORS, PRESTRESSING TENDON AND ANCHORAGE WELDING REINFORCING STEEL PREPARATION, CONSTRUCTION, AND PROTECTION DURING COLD WEATHER (TEMPERATURE BELOW 40F) AND HOT WEATHER (TEMPERATURE ABOVE 90F)

TMS 402: 1.15 TMS 602: 2.4 TMS 602: 3.4 TMS 402: 1.15 TMS 602: 3.4 TMS 602: 3.6A TMS 402: 2.1.9.7.2 TMS 402: 3.3.3.4 (b) X

X (a)

2104.3 2104.4

TMS 602: 1.8C TMS 602: 1.8D

X (a)

STRESSING OF PRESTRESSING TENDONS APPLICATION AND MEASUREMENT OF PRESTRESSING FORCES GROUT PLACEMENT GROUT SPACE PRIOR TO GROUTING GROUT PLACEMENT AT PRESTRESSING TENDONS PREPARATION OF ANY REQUIRED GROUT SPECIMENS, MORTAR SPECIMENS AND/OR PRISMS SHALL BE OBSERVED 2105.2.2 2105.3

TMS 602: 3.6B

TMS 602: 3.6B TMS 602: 3.5 TMS 602: 3.2D TMS 602: 3.6C

X X X X

TMS 602: 1.4

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

10

TABLE 2 REQUIRED STRUCTURAL SPECIAL INSPECTIONS


INSPECTION SYSTEM or MATERIAL
IBC CODE REFERENC E FREQUENCY CODE or STANDARD REFERENCE Continuous Periodic

REMARKS

FABRICATORS STEEL
FABRICATION OF STRUCTURAL ELEMENTS 1704.2 ASTM A6 ASTM STANDARDS SPECIFIED IN CONSTRUCTION DOCUMENTS AISC 360 A3.1 AISC 360 M5.5 ASTM STANDARDS SPECIFIED IN CONSTRUCTION DOCUMENTS RCSC 2.1 AISC 360 A3.4 ASTM STANDARDS SPECIFIED IN CONSTRUCTION DOCUMENTS AISC 360 A3.5 APPLICABLE AWS A5 DOCUMENTS X REFER TO INSPECTION OF FABRICATOR REQUIREMENTS

MATERIAL VERIFICATION OF STRUCTURAL STEEL AND COLD FORMED STEEL DECK

1704.3 2203.1

CERTIFIED MILL TEST REPORTS

MATERIAL VERIFICATION OF HIGH STRENGTH BOLTS, NUTS, AND WASHERS

1704.3.3

MANUFACTURER'S CERTIFIED TEST REPORTS

MATERIAL VERIFICATION OF ANCHOR BOLTS AND THREADED RODS

1704.3

MANUFACTURER'S CERTIFIED TEST REPORTS

MATERIAL VERIFICATION OF WELD FILLER METALS

1704.3.1

MANUFACTURER'S CERTIFIED TEST REPORTS

VERIFYING USE OF PROPER WPS'S VERIFYING WELDER QUALIFICATIONS COMPLETE AND PARTIAL JOINT PENETRATION GROOVE WELDS MULTIPASS FILLET WELDS 1704.3.1 AWS D1.1 SECTION 6 X

X X

COPY OF WELDING PROCEDURE SPECIFICATIONS COPY OF QUALIFICATION CARDS

X ALL WELDS VISUALLY INSPECTED PER AWS D1.1 6.9 1704.3.1 SINGLE PASS FILLET WELDS GREATER THAN X 5/16" AWS D1.1, SECTION 6 TABLE PLUG AND SLOT WELDS X 1704.4 SINGLE PASS FILLET WELDS LESS THAN OR X EQUAL TO 5/16" (a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

11

TABLE 2 REQUIRED STRUCTURAL SPECIAL INSPECTIONS


INSPECTION SYSTEM or MATERIAL
IBC CODE REFERENC E TABLE 1704.3 1704.15 TABLE 1704.3 1704.15 FLOOR AND ROOF DECK WELDS WELDING STUDS EXCEPT AS NOTED OTHERWISE WELDING STUDS IN STRUCTURAL DIAPHRAGMS WELDING STAIR AND RAILING SYSTEMS SNUG-TIGHT HIGH STRENGTH BOLT INSTALLATION PRETENSIONED HIGH STRENGTH BOLT INSTALLATION USING TURN-OF-THE-NUT METHOD WITH MATCH MARKING, DIRECT TENSION INDICATOR METHOD, OR TWIST-OFF TYPE TENSION CONTROL BOLT METHOD PRETENSIONED HIGH STRENGTH BOLT INSTALLATION USING TURN-OF-THE-NUT METHOD WITHOUT MATCH MARKING OR CALIBRATED WRENCH METHOD OR TENSIONING OF SLIP CRITICAL CONNECTIONS VERIFICATION OF FRAME JOINT DETAILS INCLUDING MEMBER AND COMPONENT LOCATIONS, BRACING, AND STIFFENERS PROPRIETARY MOMENT RESISTING FRAME CONNECTION SYSTEMS TABLE 1704.3 AWS D1.3 SECTION 7 X AWS D1.1 SECTION 7 X AWS D1.1 SECTION 6 X X ALL WELDS VISUALLY INSPECTED PER AWS D1.1 6.9 ALL CONNECTIONS INSPECTED AND VERIFIED SNUG ALL WELDS VISUALLY INSPECTED PER AWS D1.1 7.8.1 X FREQUENCY CODE or STANDARD REFERENCE Continuous Periodic

REMARKS

FABRICATORS
ICC EVALUATION REPORT ASCE 9 CHAPTER 3 X SPECIAL INSPECTIONS APPLY TO DECKING TYPE, DEPTH, GAGE, AND FASTENING

INSTALLATION OF COMPOSITE SLAB DECKING

INSTALLATION OF ROOF DECKING

ICC EVALUATION REPORT

SPECIAL INSPECTIONS APPLY TO DECKING TYPE, DEPTH AND GAGE, POWER ACTUATED FASTENERS, SCREWS, PROPRIETARY SIDE SEAM ATTACHMENTS, BUTTON PUNCHES AND SHEAR CONNECTORS ALL WELDS INSPECTED PER AWS D1.3 7.1

TABLE 1704.3

RCSC SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS SECTION 9 AISC 360, SECTION M2.5 X

ALL CONNECTIONS INSPECTED. CONNECTIONS USING DIRECT TENSION INDICATORS, ALL BOLTS SHALL BE INSPECTED AFTER SNUGGING AND AFTER PRETENSIONING

ALL CONNECTIONS INSPECTED

1704.3.2

X (a)

1703.4.1 1704.15

REFER TO WELDING AND HIGH STRENGTH BOLTING REQUIREMENTS (b)

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

12

TABLE 2 REQUIRED STRUCTURAL SPECIAL INSPECTIONS


INSPECTION SYSTEM or MATERIAL
MATERIAL VERIFICATION OF REINFORCING STEEL FOR WELDING WELDING REINFORCING EXCEPT AS NOTED OTHERWISE WELDING REINFORCING STEEL IN MOMENT RESISTING FRAMES WELDING REINFORCING STEEL IN SHEAR WALL BOUNDARY ELEMENTS WELDING SHEAR REINFORCEMENT IBC CODE REFERENC E FREQUENCY CODE or STANDARD REFERENCE Continuous Periodic

REMARKS

FABRICATORS ACI 318: 3.5.2 AWS D1.4

X X

CERTIFIED MILL TEST REPORTS

TABLE 1704.3

X X X

ALL WELDS VISUALLY INSPECTED PER AWS D1.4 7.5

ALL WELDS VISUALLY INSPECTED PER AWS D1.4.7.5 ALL WELDS VISUALLY INSPECTED PER AWS D1.4.7.5

STAINLESS STEEL
FABRICATION OF STAINLESS STEEL ELEMENTS MATERIAL VERIFICATION OF STAINLESS STEEL MATERIAL VERIFICATION OF BOLTS MATERIAL VERIFICATION OF WELD FILLER METALS VERIFYING USE OF PROPER WPS'S VERIFYING WELDER QUALIFICATIONS 1704.3.1 COMPLETE AND PARTIAL JOINT PENETRATION GROOVE WELDS MULTIPASS FILLET WELDS SINGLE PASS FILLET WELDS MATERIAL VERIFICATION OF WELD FILLER METALS 1704.3.2 Exception 2 & 1704.3.1.2 AWS D1.6 SECTION 6 X X X ALL WELDS VISUALLY INSPECTED PER AWS D1.6 6.28.1 1704.2 1704.3 1704.3 X X X X X X REFER TO INSPECTION OF FABRICATOR REQUIREMENTS CERTIFIED MILL TEST REPORTS MANUFACTURER'S CERTIFIED TEST REPORTS MANUFACTURER'S CERTIFIED TEST REPORTS COPY OF WELDING PROCEDURE SPECIFICATIONS COPY OF QUALIFICATION CARDS

COLD-FORMED STEEL FRAMING


X MANUFACTURER'S CERTIFIED TEST REPORTS

AWS D1.3 SECTION 7 X COPY OF WELDING PROCEDURE SPECIFICATIONS

VERIFYING USE OF PROPER WPS'S

COLD-FORMED STEEL ROOF AND FLOOR DECKS

1704.3.1.2

AWS D1.3

WELDING INSPECTION AND INSPECTOR QUALIFICATION

1704.3 VERIFYING WELDER QUALIFICATIONS COPY OF QUALIFICATION CARDS X Exception 2 (a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

13

TABLE 2 REQUIRED STRUCTURAL SPECIAL INSPECTIONS


INSPECTION SYSTEM or MATERIAL
IBC CODE REFERENC E FREQUENCY CODE or STANDARD REFERENCE Continuous Periodic AWS D1.3 SECTION 7

REMARKS

WELDED FRAMING CONNECTIONS

FABRICATORS

ALL WELDS VISUALLY INSPECTED PER AWS D1.3 7.1 VERIFY THAT THE TEMPORARY INSTALLATION RESTRAINT/BRACES AND THE PERMANENT INDIVIDUAL TRUSS MEMBER RESTRAINT/BRACING ARE INSTALLED IN ACCORDANCE WITH THE APPROVED TRUSS SUBMITTAL PACKAGE

COLD-FORMED STEEL TRUSSES SPANNING 60 FEET OR GREATER

1704.3.4

POST INSTALLED CONCRETE ANCHORS


SPECIAL INSPECTIONS APPLY TO ANCHOR PRODUCT NAME, TYPE, AND DIMENSIONS, HOLE DIMENSIONS, COMPLIANCE WITH DRILL BIT REQUIREMENTS, CLEANLINESS OF THE HOLE AND ANCHOR, ADHESIVE EXPIRATION DATE, ANCHOR/ADHESIVE INSTALLATION, ANCHOR EMBEDMENT, AND TIGHTENING TORQUE

INSPECTION OF ANCHORS INSTALLED IN HARDENED CONCRETE

1912.1

ICC EVALUATION REPORT ACI 318: 3.8.6, 8.1.3, 21.1.8

ALUMINUM
MATERIAL VERIFICATION OF STRUCTURAL ALUMINUM MATERIAL VERIFICATION OF BOLTS MATERIAL VERIFICATION OF WELD FILLER METALS VERIFYING USE OF PROPER WPS'S VERIFYING WELDER QUALIFICATIONS COMPLETE AND PARTIAL JOINT PENETRATION GROOVE WELDS MULTIPASS FILLET WELDS SINGLE PASS FILLET WELDS AWS D1.2 SECTION 5 X X X ALL WELDS VISUALLY INSPECTED PER AWS 1.2, 5.5 1704.15 X X X X X CERTIFIED MILL TEST REPORTS MANUFACTURER'S CERTIFIED TEST REPORTS MANUFACTURER'S CERTIFIED TEST REPORTS COPY OF WELDING PROCEDURE SPECIFICATIONS COPY OF QUALIFICATION CARDS

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

14

TABLE 2 REQUIRED STRUCTURAL SPECIAL INSPECTIONS


INSPECTION SYSTEM or MATERIAL
IBC CODE REFERENC E FREQUENCY CODE or STANDARD REFERENCE Continuous Periodic

REMARKS

FABRICATORS WOOD
FABRICATION OF PREFABRICATED STRUCTURAL ELEMENTS 1704.2 X REFER TO INSPECTION OF FABRICATOR REQUIREMENTS

1. FABRICATION OF HIGH-LOAD DIAPHRAGMS: A. VERIFY STRUCTURAL PANEL GRADE AND THICKNESS


1704.1 1704.6.1 TABLE 2306.2.1 (2) 1704.6.1 TABLE 2306.2.1 (2)

B. VERIFY NOMINAL SIZE OF FRAMING MEMBERS AT ADJOINING PANEL EDGES C. VERIFY NAIL OR STAPLE DIAMETER AND LENGTH, NUMBER OF FASTENER LINES AND SPACING BETWEEN FASTENERS IN EACH LINE AND AT EDGE MARGINS PREFABRICATED WOOD SHEAR PANELS

1704.1 1704.6.1 TABLE 2306.2.1(2)

1703.4 1704.15.3

ICC EVALUATION REPORT

SPECIAL INSPECTIONS APPLY TO HOLDOWN ANCHOR SIZE AND PLACEMENT, INCLUDING EMBEDMENT LENGTH, SPACING, AND EDGE DISTANCE

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

15

TABLE 3 REQUIRED ARCHITECTURAL SPECIAL INSPECTIONS


INSPECTION SYSTEM or MATERIAL
IBC CODE REFERENCE

CODE or STANDARD REFERENCE

FREQUENCY Continuous Periodic

REMARKS

SPRAYED FIRE-RESISTANT MATERIALS


APPROVED CONSTRUCTION DOCUMENTS SPECIAL INSPECTIONS APPLY TO CLEANLINESS AND TEMPERATURE OF SUBSTRATE AND THE ACCEPTABILITY OF PRIMED, PAINTED, OR ENCAPSULATED STEEL

CONDITIONS OF SUBSTRATE

1704.12
APPLICATION WRITTEN INSTRUCTION OF APPROVED MANUFACTURER X

SPECIAL INSPECTIONS APPLY TO USE OF APPROVED MATERIAL VERIFICATION, MATERIAL EXPIRATION, HANDLING, STORAGE, MIXING, CONVEYANCE, METHOD OF APPLICATION, CURING, VENTILATION, THICKNESS, DENSITY, BOND STRENGTH AND CONDITION OF APPLICATION, AND PATCHING

MASTIC AND INTUMESCENT FIRE-RESISTIVE COATINGS

CONDITIONS OF SUBSTRATE

APPROVED CONSTRUCTION DOCUMENTS

SPECIAL INSPECTIONS APPLY TO CLEANLINESS AND TEMPERATURE OF SUBSTRATE AND THE ACCEPTABILITY OF PRIMED, PAINTED, OR ENCAPSULATED STEEL

1704.13 SPECIAL INSPECTIONS APPLY TO USE OF APPROVED MATERIAL VERIFICATION, MATERIAL EXPIRATION, HANDLING, STORAGE, MIXING, CONVEYANCE, METHOD OF APPLICATION, PROTECTION, CURING, VENTILATION, THICKNESS, VOIDS REPAIR, CONDITION OF APPLICATION, AND PATCHING

APPLICATION

AWCI TECHNICAL MANUAL 12-B

EXTERIOR INSULATION AND FINISH SYSTEMS


EIFS APPLICATION 1704.14 APPROVED CONSTRUCTION DOCUMENTS APPROVED CONSTRUCTION DOCUMENTS MANUFACTURERS WRITTEN INSTRUCTIONS X ALL EIFS APPLICATIONS EXCEPT FOR APPLICATIONS OVER WATER-RESISTIVE BARRIERS WITH A MEANS OF DRAINING MOISTURE TO THE EXTERIOR OR OVER MASONRY OR CONCRETE WALLS

WATER-RESISTIVE BARRIER COATING APPLICATION

1704.14.1

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

16

TABLE 3 REQUIRED ARCHITECTURAL SPECIAL INSPECTIONS


INSPECTION SYSTEM or MATERIAL
IBC CODE REFERENCE

CODE or STANDARD REFERENCE

FREQUENCY Continuous Periodic

REMARKS

SPRAYED FIRE-RESISTANT MATERIALS SMOKE CONTROL SYSTEMS


APPROVED CONSTRUCTION DOCUMENTS LEAKAGE TESTING AND DEVICE LOCATION PRIOR TO CONCEALMENT PRESSURE DIFFERENCE TESTING, FLOW MEASUREMENTS AND DETECTION AND CONTROL VERIFICATION PRIOR TO OCCUPANCY

INSTALLATION

1704.16

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

17

TABLE 4 REQUIRED INSPECTIONS for SPECIAL CASES


INSPECTION SYSTEM or MATERIAL
IBC CODE CODE or STANDARD REFERENCE REFERENCE FREQUENCY Continuous Periodic

REMARKS

PRE-ENGINEERED STRUCTURES
FABRICATION AND ERECTION 1704.15 X (b) X REFER TO TABLE 2 OF THIS PLAN FOR FABRICATOR, WELDING, AND HIGH STRENGTH BOLTING SPECIAL INSPECTION REQUIREMENTS

WELDED STEEL TANKS


AWWA/AWS D100 SECTION 11 API 650 5.3 API 620 SECTION 5

FABRICATION AND ERECTION

1704.15

ALL JOINTS VISUALLY INSPECTED

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

18

TABLE 5 REQUIRED TESTING for SPECIAL INSPECTIONS


TESTING
FREQUENCY

SYSTEM or MATERIAL

IBC CODE CODE or STANDARD REFERENCE REFERENCE

REMARKS
Continuous Periodic

GEOTECHNICAL
GEOTECHNICAL ENGINEER TO PERFORM TESTING OF COMPACTED FILL MATERIALS FILL IN-PLACE DENSITY OR PREPARED SUBGRADE DENSITY 1704.7 MATERIAL VERIFICATION 1803 VARIES; MINIMUM PER IBC APPENDIX J107.5 VARIES; CLASSIFICATION AND TESTING OF CONTROLLED FILL MATERIALS TESTING PER GEOTECHNICAL REPORT

X (a)

BY THE GEOTECHNICAL ENGINEER

X (a)

BY THE GEOTECHNICAL ENGINEER

TENSION ANCHORS

PERFORMANCE TEST FIRST (X) ANCHORS TO xxx% DL AND PROOF PER GEOTECHNICAL REPORT LOAD REMAINING ANCHORS TO xxx% DL

CONCRETE

AT THE TIME FRESH CONCRETE IS SAMPLED TO FABRICATE SPECIMENS FOR STRENGTH TESTS, PERFORM SLUMP AND AIR CONTENT TESTS, AND DETERMINE THE TEMPERATURE OF THE CONCRETE.

TABLE 1704.4

ASTM C 172 ASTM C 31 ACI 318: 5.6, 5.8

FABRICATE SPECIMENS AT TIME FRESH CONCRETE IS PLACED ONCE EACH DAY FOR A GIVEN CLASS OF CONCRETE, OR LESS THAN ONCE FOR EACH 150 YDS OF CONCRETE, OR LESS THAN ONCE FOR EACH 5,000 FT2 OF SURFACE AREA FOR SLABS/WALLS. ONCE EACH SHIFT FROM IN-PLACE WORK OR FROM TEST PANEL AND MINIMUM ONE SPECIMEN FOR EACH 50 CUBIC YARDS. "PRECONSTRUCTION TESTS AS REQUIRED PER THE BUILDING OFFICIAL."

CONCRETE STRENGTH

TABLE 1704.4 1903 1905

ASTM C39

CONCRETE SLUMP CONCRETE AIR CONTENT CONCRETE TEMPERATURE

ASTM C143 ASTM C231 ASTM C1064

X X X

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

19

TABLE 5 REQUIRED TESTING for SPECIAL INSPECTIONS


TESTING
FREQUENCY

SYSTEM or MATERIAL

IBC CODE CODE or STANDARD REFERENCE REFERENCE

REMARKS
Continuous Periodic

GEOTECHNICAL
1704.4 1913.10 IBC 1913.10.1: SPECIMENS SHALL BE TAKEN FROM THE INPLACE OR FROM TEST PANELS, AND SHALL BE TAKEN AT LEAST ONCE EACH SHIFT, BUT NOT LESS THAN ONE FOR EACH 50 CUBIC YARDS OF SHOTCRETE

SHOTCRETE STRENGTH

ASTM C39

MASONRY
ASTM C62 ASTM C216 ASTM C652 ASTM C476 ASTM C55 ASTM C90 TESTING EVERY 5,000 FT2

UNIT STRENGTH METHOD

2105.2.2.1

PRISM TEST METHOD

2105.2.2.2

ASTM C1314

COMPRESSIVE STRENGTH OF MORTAR

MIA - INSPECTOR'S HANDBOOK ASTM C780

(1) TEST PER DAY FOR 3 CONSECUTIVE WORK DAYS AT THE START OF THE JOB. ONE TEST SHALL CONSIST OF 3 SPECIMENS. AFTER THE FIRST THREE TESTS, SPECIMENS FOR CONTINUING QUALITY CONTROL SHALL BE TAKEN ONCE A WEEK, OR FOR EVERY 5,000 SQ. FT. OF WALL, WHICHEVER IS FIRST. AT THE START OF GROUTING OPERATIONS, TAKE ONE TEST PER DAY FOR THE FIRST THREE DAYS. THE TESTS SHALL CONSIST OF 3 SPECIMENS. AFTER THE FIRST 3 TESTS, SPECIMENS FOR CONTINUING QUALITY CONTROL SHALL BE TAKEN ONCE A WEEK OR FOR EVERY 30 CU. YDS. OF GROUT OR FOR EVERY 5,000 SQ. FT. OF WALL, WHICHEVER COMES FIRST.

COMPRESSIVE STRENGTH OF GROUT

MIA - INSPECTOR'S HANDBOOK ASTM C780

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

20

TABLE 5 REQUIRED TESTING for SPECIAL INSPECTIONS


TESTING
FREQUENCY

SYSTEM or MATERIAL

IBC CODE CODE or STANDARD REFERENCE REFERENCE

REMARKS
Continuous Periodic

GEOTECHNICAL STEEL
MAGNETIC PARTICLE (MT) AND ULTRASONIC (UT) TESTING OF WELDS PRE-CONSTRUCTION TESTING OF WELDING STUDS PRE-INSTALLATION TESTING OF WELDING STUDS WELDED THROUGH DECKING 1704.3.1.1 MT - AWS D1.1 6.14.4 UT - AWS D1.1 6.13 & 6.14.3 AWS D1.1 7.7.1 PER DRAWINGS EACH SIZE AND TYPE OF STUD EACH SHIFT EACH STUD SIZE AND DECK GAGE COMBINATION

1704.3.1

1704.3.1

AWS D1.1 7.6

PRE-INSTALLATION VERIFICATION OF PRETENSIONED HIGH STRENGTH BOLTS

1704.3.3

RCSC SPECIFICATION EACH COMBINATION OF FOR STRUCTURAL DIAMETER, LENGTH, JOINTS USING ASTM GRADE, AND LOT TO BE A325 OR A490 BOLTS USED IN THE WORK SECTION 7

STAINLESS STEEL
ULTRASONIC (UT) TESTING OF WELDS 1704.3.1 UT-AWS D1.6 6.13 PER DRAWINGS

ALUMINUM
LIQUID PENETRANT (PT) AND RADIOGRAPHIC (RT) TESTING OF WELDS PT - AWS D1.2 5.7.5 RT - AWS D1.2 5.10 & 5.15 PER DRAWINGS

WELDED STEEL TANKS


AWWA/AWS D100 11.5 & 11.6 API 650 6.1 API 620 5.15.1 AT SHELL JOINTS SPECIAL INSPECTIONS APPLY TO REVIEW OF THE NUMBER AND SPACING RADIOGRAPHS AND THE ASSOCIATED REPORT PER THE STANDARD INTERPRETING THE RADIOGRAPHS

RADIOGRAPHIC TESTING (RT) OF WELDS

INTUMESCENT FIRE-RESISTIVE COATINGS


THICKNESS 1704.13 AWCI TECHNICAL MANUAL 12-B EACH 10000 SF OF COATED AREA EACH FLOOR LEVEL

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

21

TABLE 5 REQUIRED TESTING for SPECIAL INSPECTIONS


TESTING
FREQUENCY

SYSTEM or MATERIAL

IBC CODE CODE or STANDARD REFERENCE REFERENCE

REMARKS
Continuous Periodic

GEOTECHNICAL SMOKE CONTROL SYSTEMS


LEAKAGE AND PRESSURE DIFFERENTIAL AND FLOW MEASUREMENT 1704.16 DETECTION AND CONTROL VERIFICATION DETERMINED BY JURISDICTION DETERMINED BY JURISDICTION

SPRAYED FIRE-RESISTANT MATERIALS


1704.12.4 1704.12.4.1 1704.12.4.2 NOT LESS THAN (4) MEASUREMENTS FOR EACH 1000 SF OF SPRAYED AREA EACH FLOOR LEVEL

THICKNESS @ FLOOR, ROOF, AND WALL ASSEMBLIES

THICKNESS @ STRUCTURAL MEMBERS

1704.12.4 1704.12.4.1 1704.12.4.3

THICKNESS DETERMINED FOR NOT LESS THAN 25% THE STRUCTURAL MEMBERS EACH FLOOR LEVEL

ASTM E605 DENSITY @ FLOOR, ROOF, AND WALL ASSEMBLIES 1704.12.5

DETERMINED FROM EACH FLOOR, ROOF, AND WALL ASSEMBLY AT A RATE OF NOT LESS THAN ONE SAMPLE FOR EVERY 2500 SF IN EACH STORY

DENSITY @ BEAMS, GIRDERS, TRUSSES, AND COLUMNS

1704.12.5

DETERMINED FROM EACH TYPE OF STRUCTURAL MEMBER AT A RATE OF NOT LESS THAN ONE SAMPLE FOR EVERY 2500 SF IN EACH STORY

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

22

TABLE 5 REQUIRED TESTING for SPECIAL INSPECTIONS


TESTING
FREQUENCY

SYSTEM or MATERIAL

IBC CODE CODE or STANDARD REFERENCE REFERENCE

REMARKS
Continuous Periodic

GEOTECHNICAL ONE FOR EACH FLOOR,


BOND STRENGTH @ FLOOR, ROOF, AND WALL 1704.12.6.1 ASSEMBLIES ASTM E736 ROOF, AND WALL ASSEMBLY EVERY 2500 SF OF SPRAYED AREA FOR EACH FLOOR LEVEL

SPRAYED FIRE-RESISTANT MATERIALS


EACH TYPE OF STRUCTURAL MEMBER FOR EACH 2500 SF OF FLOOR AREA FOR EACH FLOOR LEVEL

BOND STRENGTH @ STRUCTURAL MEMBERS

1704.12.6.2

ASTM E736

MASTIC AND INTUMESCENT FIRE-RESISTIVE COATINGS


ONE BAY PER FLOOR OR FOR EACH 10,000 SF OF FLOOR, WHICHEVER PROVIDES THE GREATEST NUMBER OF TESTS, TEST ONE COLUMN, ONE PRIMARY BEAM, ONE SECONDARY BEAM, AND ONE TRUSS

THICKNESS

1704.13

AWCI TECHNICAL MANUAL 12-B ASTM D1186

EXTERIOR INSULATION AND FINISH SYSTEMS, WATER-RESISTIVE BARRIER COATING


ASTM C297 ASTM D2247 ASTM D2898 ASTM E72 ASTM E96 ASTM E331 ASTM E1233 ASTM E2134 ASTM E2485 ASTM E2570

EXTERIOR INSULATION & FINISH SYSTEMS

1704.14.1

See ASTM

A WATER-RESISTIVE BARRIER COATING COMPLYING WITH ASTM E 2570 REQUIRES SPECIAL INSPECTION OF THE WATER-RESISTIVE BARRIER COATING WHEN INSTALLED OVER A SHEATHING SUBSTRATE.

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

23

TABLE 6 REQUIRED SPECIAL INSPECTIONS for SEISMIC RESISTANCE


INSPECTION SYSTEM or MATERIAL
IBC CODE CODE or STANDARD REFERENCE REFERENCE FREQUENCY Continuous Periodic

REMARKS

CONCRETE
CONCRETE SEISMIC-FORCE-RESISTING SYSTEMS (SEISMIC CATEGORIES C, D, E, F) (OCCUPANCY CATEGORIES III & IV) ACI 318 X (b)

1707.1 REINFORCING STEEL PLACEMENT IN SPECIAL MOMENT RESISTING FRAMES TABLE 1704.4 1707.1 TABLE 1704.4 ACI 318 1.3.5 X

INSPECTORS ARE TO BE QUALIFIED TO PERFORM THESE INSPECTIONS WHICH INCLUDES, BUT IS NOT LIMITED TO, THE PLACEMENT, STIRRUPS PLACEMENT, LAP LOCATION AND SPLICES, JOINT REINFORCEMENT PLACEMENT, ETC.

GROUTING OF BONDED POST TENSIONING TENDONS IN SEISMIC FORCE RESISTING SYSTEMS

ACI 318: 18.18.1 ACI 318: 18.18.2 ACI 318: 18.18.3 ACI 318: 18.18.4

MASONRY
SEISMIC-FORCE-RESISTING SYSTEMS IN STRUCTURES OF SEISMIC DESIGN CATEGORY C, D, E OR F (OCCUPANCY CATEGORIES III AND IV)* SEISMIC SYSTEMS IN STRUCTURES OF SEISMIC DESIGN CATEGORY D, E OR F (OCCUPANCY CATEGORIES III AND IV)*

1707.1 (1)

X (b)

1707.1 (2)

X (b)

STEEL
REFER TO TABLE 2 OF GUIDELINES FOR FABRICATOR AND WELDING SPECIAL INSPECTION REQUIREMENTS. ENGINEER OF RECORD TO CLEARLY INDICATE THE SCOPE OF INSPECTIONS ON DRAWINGS. IBC 1707.2 AND 1708.3 REQUIRE SPECIAL INSPECTIONS AND RELATED TESTING FOR STRUCTURAL STEEL FOR THE SEISMIC FORCE RESISTING SYSTEM TO COMPLY WITH THE QUALITY ASSURANCE PLAN REQUIREMENTS OF AISC 341. THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SPECIFIES THE QA PLAN WHICH SHOULD BE PROVIDED TO THE CONTRACTOR AS PART OF THE BID DOCUMENTS AND SHOULD BE CLEARLY IDENTIFIED AS SUCH. AISC RECOMMENDS THAT AISC 341 APPENDIX Q, QUALITY ASSURANCE PLAN, BE ADOPTED. AISC 341 INCLUDES COMMENTARY WHICH WILL BE HELPFUL TO ENGINEERS SPECIFYING PROJECT QA PLANS.

WELDING OF THE SEISMIC FORCE- RESISTING SYSTEM

1707.2

AISC 341 Q5.1 AWS D1.1 SECTION 6

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology. *State of Oregon only

24

TABLE 6 REQUIRED SPECIAL INSPECTIONS for SEISMIC RESISTANCE


INSPECTION SYSTEM or MATERIAL
IBC CODE CODE or STANDARD REFERENCE REFERENCE FREQUENCY Continuous Periodic

REMARKS

CONCRETE
AISC 341 Q5.3 RCSC SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS 1707.2 MOMENT RESISTING FRAME REDUCED BEAM SECTIONS AISC 341 Q5.4 SEISMIC FORCE-RESISTING SYSTEM PROTECTED ZONES X X SPECIAL INSPECTIONS APPLY TO CONTOUR, FINISH, AND DIMENSIONAL TOLERANCES SPECIAL INSPECTIONS APPLY TO VERIFYING THAT THERE ARE NO HOLES OR UNAPPROVED ATTACHMENTS INCLUDING UNACCEPTABLE WELDS IN PROTECTED ZONES REFER TO TABLE 2 FOR HIGH STRENGTH BOLTING SPECIAL INSPECTION REQUIREMENTS

HIGH STRENGTH BOLT INSTALLATION IN THE SEISMIC FORCE-RESISTING SYSTEM

COLD-FORMED STEEL FRAMING


WELDING OF THE SEISMIC-FORCE-RESISTING SYSTEM CONNECTIONS FOR DIAPHRAGM ATTACHMENT, DIAPHRAGM CHORDS, COLLECTORS AND BRACING, AND SHEAR WALL FASTENING, ANCHORAGE AND HOLDOWNS PERIODIC SPECIAL INSPECTION IS REQUIRED DURING WELDING OPERATIONS OF ELEMENTS OF THE SEISMIC-FORCERESISTING SYSTEM. PERIODIC SPECIAL INSPECTION IS REQUIRED FOR SCREW ATTACHMENT, BOLTING, ANCHORING AND OTHER FASTENING OF COMPONENTS WITHIN THE SEISMIC-FORCE-RESISTING SYSTEM, INCLUDING SHEAR WALLS, BRACES, DIAPHRAGMS, COLLECTORS (DRAG STRUTS) AND HOLD-DOWNS. 1707.4 X ALL CONNECTIONS VISUALLY INSPECTED AWS D1.3 SECTION 7 X ALL WELDS VISUALLY INSPECTED PER AWS D1.3 7.1

1707.4

AWS D1.3 SECTION 7

X (b)

ALL WELDS VISUALLY INSPECTED PER AWS D1.3 7.1 EXCEPTION: SPECIAL INSPECTION IS NOT REQUIRED FOR SHEAR WALLS, BRACES, DIAPHRAGMS, DRAG STRUT AND HOLDOWNS. IF SHEATHING IS GYP OR FIBERBOARD OR IF SHEATHING IS WOOD STRUCTURAL PANEL/STEEL SHEET ONE SIDE ONLY AND FASTENER SPACING IS GREATER THAN 4" ON CENTER.

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology. *State of Oregon only

25

TABLE 6 REQUIRED SPECIAL INSPECTIONS for SEISMIC RESISTANCE


INSPECTION SYSTEM or MATERIAL
IBC CODE CODE or STANDARD REFERENCE REFERENCE FREQUENCY Continuous Periodic

REMARKS

CONCRETE WOOD
FIELD GLUING OF DIAPHRAGM AND SHEAR WALL ELEMENTS FOR SEISMIC FORCERESISTING-SYSTEMS CONNECTIONS FOR DIAPHRAGM CHORDS, COLLECTORS, BRACING, AND SHEAR WALL ANCHORAGE AND HOLDOWNS X

X 1707.3

ALL CONNECTIONS VISUALLY INSPECTED SPECIAL INSPECTION IS NOT REQUIRED WHEN FASTENER SPACING IS GREATER THAN 4" ON CENTER FOR WOOD SHEAR WALLS, DIAPHRAGMS, NAILING, BUILDING AND OTHER COMPONENTS IN THE SEISMIC FORCE-RESISTING SYSTEM.

FASTENING OF DIAPHRAGM AND SHEAR WALL SHEATHING WITH EDGE NAILING < 4"

ARCHITECTURAL
INSTALLATION OF ANCHORAGE OF ACCESS FLOORS INSTALLATION OF ANCHORAGE OF CLADDING AND INTERIOR/EXTERIOR VENEER WEIGHING MORE THAN 5 PSF IN BUILDINGS MORE THAN 30 FEET IN HEIGHT ERECTION AND FASTENING OF INTERIOR NONBEARING WALLS WEIGHING MORE THAN 15 PSF IN BUILDINGS MORE THAN 30 FEET IN HEIGHT ERECTION AND FASTENING OF EXTERIOR NON-BEARING WALLS IN BUILDINGS MORE THAN 30 FEET IN HEIGHT INSTALLATION OF ANCHORAGE OF STORAGE RACKS WITH Ip = 1.5 INSTALLATION AND ANCHORAGE OF SUSPENDED CEILING SYSTEMS INSTALLATION OF OTHER SEISMIC SUPPORTS FOR DESIGNATED ARCHITECTURAL SYSTEMS AND THEIR COMPONENTS 1705.3 1707.5 1705.3 1707.6 X (a)

X (a)

1707.6

X (a)

1705.3 1707.6 1705.3 1707.5 1705.3 1705.3 1707.6 ASCE 7-05 Section 15.5.3 ASCE 7-05 Section 13.5.6

X (a)

X (a) X (a)

X (a)

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology. *State of Oregon only

26

TABLE 6 REQUIRED SPECIAL INSPECTIONS for SEISMIC RESISTANCE


INSPECTION SYSTEM or MATERIAL
IBC CODE CODE or STANDARD REFERENCE REFERENCE FREQUENCY Continuous Periodic

REMARKS

CONCRETE ELECTRICAL
INSTALLATION OF ANCHORAGE OF ELECTRICAL EQUIPMENT FOR EMERGENCY OR STANDBY POWER SYSTEMS INSTALLATION OF ANCHORAGE OF ALL ELECTRICAL EQUIPMENT IN SDC E OR F ONLY INSTALLATION OF VIBRATION ISOLATION SYSTEMS IN STRUCTURES ASSIGNED TO SDC C, D, E OR F WHERE THE CONSTRUCTION DOCUMENTS REQUIRE A NOMINAL CLEARANCE OF 0.25 INCHES OR LESS BETWEEN THE EQUIPMENT SUPPORT FRAME AND RESTRAINT INSTALLATION OF OTHER SEISMIC SUPPORTS FOR DESIGNATED ELECTRICAL SYSTEMS AND THEIR COMPONENTS INSTALLATION OF PIPING SYSTEM MEANT TO CARRY FLAMMABLE, COMBUSTIBLE OR HIGHLY TOXIC CONTENTS AND ITS ASSOCIATED MECHANICAL UNITS INSTALLATION OF OTHER SEISMIC SUPPORTS FOR DESIGNATED MECHANICAL SYSTEMS AND THEIR COMPONENTS 1705.3 1707.7 X (a)

1707.7

X (a)

1707.7 1707.9

X (a)

1707.7

X (a)

PROCESS MECHANICAL

1707.7

X (a)

1707.8

X (a)

BUILDING MECHANICAL
INSTALLATION OF HVAC DUCTWORK THAT WILL CONTAIN HAZARDOUS MATERIALS INSTALLATION OF FIRE PROTECTION SPRINKLER SYSTEM DESIGNATED SEISMIC SYSTEM VERIFICATION VERIFY LABEL, ANCHORAGE OR MOUNTING CONFORMS TO THE CERTIFICATE OF COMPLIANCE 1707.7 1707.1 X (a) INSPECTIONS AS REQUIRED BY LOCAL BUILDING OFFICIAL

DESIGNATED SEISMIC SYSTEM VERIFICATION


1707.8 X (a) REGISTERED DESIGN PROFESSIONAL SHALL IDENTIFY INSPECTION POINTS, FREQUENCY, TYPE AND EXTENT OF SPECIAL INSPECTIONS AND TESTING IN ACCORDANCE WITH 1704, 1707, AND AISC 341.

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology. *State of Oregon only

27

TABLE 7 REQUIRED TESTING for SEISMIC RESISTANCE SPECIAL INSPECTIONS


TESTING SYSTEM or MATERIAL
IBC CODE CODE or STANDARD REFERENCE REFERENCE FREQUENCY Continuous Periodic

REMARKS

CONCRETE REINFORCEMENT
TEST A615 REINFORCEMENT USED TO RESIST EARTHQUAKE INDUCED LOAD IN SPECIAL MOMENT FRAMES, SPECIAL STRUCTURAL WALLS, AND END COUPLING BEAMS CONNECTING STRUCTURAL WALLS IN STRUCTURE ASSIGNED TO SEISMIC DESIGN CATEGORY B, C, D, E AND F TEST A615 REINFORCEMENT FOR WELDABILITY WHEN SUCH REINFORCEMENT IS TO BE WELDED

1708.2 1708.1.1

ACI 318: 21.1.5.2

X (b)

X (a)

NOT REQUIRED WHEN CERTIFIED MILL TEST REPORTS ARE PROVIDED

1708.2 1708.1.1

ACI 318: 3.5.2

X (a)

STEEL
UT OF BASE METAL THICKER THAN 1-1/2" SUBJECT TO THROUGH-THICKNESS WELD SHRINKAGE STRAINS MT OF K-AREA OF ROLLED WIDE FLANGE COLUMN WEBS ADJACENT TO DOUBLER/CONTINUITY PLATE WELDS MAGNETIC PARTICLE (MT) AND ULTRASONIC (UT) TESTING OF COMPLETE JOINT PENETRATION GROOVE (CJP) WELDS IN MATERIALS 5/16" THICK AND GREATER MT OF THERMALLY CUT SURFACES OF BEAM COPES AND ACCESS HOLES AT WELDED SPLICES AND CONNECTIONS WHEN THE FLANGE THICKNESS EXCEEDS 1 1/2" FOR ROLLED SHAPES OR THE WEB THICKNESS EXCEEDS 1 1/2" FOR BUILT-UP SHAPES MT OF THE WELD AND ADJACENT AREA IN A REDUCED BEAM SECTION (RBS) PLASTIC HINGE REGION REPAIRED BY WELDING MT OF THE ENDS OF FLANGE WELDS FROM WHICH WELD TABS HAVE BEEN REMOVED 1708.3 AISC 341 Q5.2 AWS D1.1 6.13 & 6.14.3 AISC 341 Q5.2 AWS D1.1 6.14.4 AISC 341 Q5.2 MT - AWS D1.1 6.14.4 UT - AWS D1.1 6.13 & 6.14.3 BEHIND AND ADJACENT TO EACH WELD

1708.3

EACH PLATE LOCATION IBC 1707.2 AND 1708.3 REQUIRE SPECIAL INSPECTIONS AND RELATED TESTING FOR STRUCTURAL STEEL FOR THE SEISMIC FORCE RESISTING SYSTEM TO COMPLY WITH THE QUALITY ASSURANCE PLAN REQUIREMENTS OF AISC 341. THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SPECIFIES THE QA PLAN WHICH SHOULD BE PROVIDED TO THE CONTRACTOR AS PART OF THE BID DOCUMENTS AND SHOULD BE CLEARLY IDENTIFIED AS SUCH. AISC RECOMMENDS THAT AISC 341 APPENDIX Q, "QUALITY ASSURANCE PLAN", BE ADOPTED. AISC 341INCLUDES COMMENTARY WHICH WILL BE HELPFUL TO ENGINEERS SPECIFYING PROECT QA PLANS.

1708.3

UT 100% OF WELDS MT 25% OF WELDS REFER TO DRAWINGS FOR LOCATIONS

1708.3

AISC 341 Q5.2 AWS D1.1 6.14.4

EACH LOCATION

1708.3

AISC 341 Q5.2 AWS D1.1 6.14.4 AISC 341 Q5.2 AWS D1.1 6.14.4

EACH LOCATION

1708.3

EACH LOCATION

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

28

TABLE 7 REQUIRED TESTING for SEISMIC RESISTANCE SPECIAL INSPECTIONS


TESTING SYSTEM or MATERIAL
IBC CODE CODE or STANDARD REFERENCE REFERENCE FREQUENCY Continuous Periodic

REMARKS

CONCRETE REINFORCEMENT ARCHITECTURAL, MECHANICAL AND ELECTRICAL


COMPONENT TESTING INCLUDING MOUNTING SYSTEMS OR ANCHORAGE IF CERTIFICATES OF COMPLIANCE ARE NOT AVAILABLE 1708.4 1708.1.1 1708.1.2 ASCE 7 - SECTION 13.2.1, 13.2.2

X (a)

SEISMICALLY ISOLATED STRUCTURES


SYSTEM TESTS 1708.5 ASCE 7 - 17.8 X (a)

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

29

TABLE 8 REQUIRED SPECIAL INSPECTIONS for WIND RESISTANCE


INSPECTION SYSTEM or MATERIAL
ROOF CLADDING AND ROOF FRAMING CONNECTIONS WALL CONNECTIONS TO ROOF AND FLOOR DIAPHRAGMS AND FRAMING ROOF AND FLOOR DIAPHRAGM SYSTEMS, INCLUDING COLLECTORS, DRAG STRUTS AND BOUNDARY ELEMENTS IBC CODE CODE or STANDARD REFERENCE REFERENCE 1706.2 1706.4 1706.2 FREQUENCY Continuous Periodic X (a)

REMARKS

X (a)

1706.2

X (a)

VERTICAL WINDFORCE-RESISTING SYSTEMS, INCLUDING BRACED FRAMES, MOMENT FRAMES AND SHEAR WALLS

1705.4

X (a)

CONTINUOUS SPECIAL INSPECTION IS REQUIRED DURING FIELD GLUING OPERATIONS OF ELEMENTS OF THE MAIN WINDFORCE-RESISTING SYSTEM. PERIODIC SPECIAL INSPECTION IS REQUIRED FOR NAILING, BOLTING, ANCHORING AND OTHER FASTENING OF COMPONENTS WITHIN THE MAIN WINDFORCE-RESISTING SYSTEM, INCLUDING WOOD SHEAR WALLS, WOOD DIAPHRAGMS, DRAG STRUTS, BRACES AND HOLD-DOWNS

REFER TO TABLE 2: REQUIRED STRUCTURAL SPECIAL INSPECTIONS

1706.2

X (a)

FIELD GLUING OPERATIONS OF ELEMENTS OF THE MAIN WIND-FORCE-RESISTING SYSTEM.

1706.2

X SPECIAL INSPECTIONS ARE NOT REQUIRED FOR WOOD SHEAR WALLS AND DIAPHRAGMS WHERE THE FASTENER SPACING IS MORE THAN 4 INCHES ON CENTER OR FOR COLDFORMED CONSTRUCTION WHERE THE SHEATHING IS GYPSUM BOARD, FIBERBOARD, OR WOOD STRUCTURAL PANEL OR STEEL SHEET ON ONE SIDE ONLY.

COLD-FORMED STEEL LIGHT-FRAME CONSTRUCTION

1706.3

X (a)

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

30

TABLE 9 STRUCTURAL OBSERVATION


INSPECTION SYSTEM or MATERIAL
IBC CODE REFERENCE

CODE or STANDARD REFERENCE

FREQUENCY Continuous Periodic

REMARKS

AS REQUIRED BY THE DESIGN PROFESSIONAL SEISMIC RESISTANCE WIND REQUIREMENTS

1710.1 1710.2 1710.3 X (a) X (a) SEE COMMENTARY SEE COMMENTARY

(a) Periodic Special Inspection frequency and timing to be defined by the registered design professional. (b) Selection to be made by the registered design professional based on building category and design methodology.

31