Вы находитесь на странице: 1из 38

The Overview of Siemens Protective Relay

Siemens AG 2013 I&C Sector

Understanding Basic function of Protective Relay

Siemens AG 2013 I&C Sector

Relay Functions u Monitoring


- CB, DS, ES, LOR Status / Alarms

u Metering
- V, I, P, Q, pf, Cos, Wh, etc

u Control
- Open/Close (CB, DS, ES) - Raise/Lower (TR tap, EDG V / f) - Start / Stop (EDG)

u Protection
- CT Input - PT Input

Page 3

March 2013

Siemens AG 2013 I&C Sector

Monitoring - Status, Alarm monitoring through BI (Binary Input) SWITCH


DC +

Protection Relay
ECMS HMI

Comm. Port IEC61850 CB Opened CB Closed

DC Siemens AG 2013 I&C Sector

Page 4

March 2013

Metering V, I, P, Q, pf, cos, wh, etc through CT, VT Current / Voltage Simulator

Protection Relay
ECMS HMI

Comm. Port IEC61850 CT Input

PT Input

Page 5

March 2013

Siemens AG 2013 I&C Sector

Control (with Logic) - Open, Close through BO (Binary Output)

SWITCH
ECMS HMI

DC +

Protection Relay
CB close Command IEC61850 CB open Command T.C C.C

Comm. Port

DC -

Page 6

March 2013

Siemens AG 2013 I&C Sector

Protection SWITCH
DC1 + Simulator DC2 +

Protection Relay

86 CT Input

T.C

PT Input

Comm. Port

DC2 DC1 ECMS HMI

IEC61850 Siemens AG 2013 I&C Sector

Page 7

March 2013

Overcurrent- / multifunctional relays


Multifunctional relay & all options
52

Busbar
7SJ62/64
Motor protection
Restart inhibit 66/86 I< Starting- Load jam time

Synchron25 isation
(7SJ64/623/624)

P<>, Q<>

V, f, P
cos df/dt>

37
Locked rotor

48 38

51M
Fault locator 21FL

32
f<>

55
U>

81R 27

only 7SJ62/64

Protection Features

14

Bearing temp. Motor statistic

U<

81

59

RTD-Box interface

Directional 47
Phase-sequence monitoring I>> dir. I> dir. Ip dir. IE>>dir. IE> dir. IEp dir. breakerfailure

I>> I>>>

I>, Ip

IE>> IE>>> IE>, IEp

I2>
restraint

u>

50

51

50N 51N 79

Inrush-

46
Lockout

49 50BF
51V

67

67N

IE>> IE>>>

Auto reclosing

86

Dir. sensitive earth fault detection

IE>, IEp

50N

51N

87N

High-impedance REF

67Ns

IEE>> IEE> IEEp

UE>

64

Page 8

March 2013

Siemens AG 2013 I&C Sector

The portfolio of Siemens Product

Siemens AG 2013 Energy I&C Sector

Energy Automation Broadest portfolio and strong brands


Energy data management Control center

Prophet Solution


Substation Automation Substation automation

Spectrum PowerCC Spectrum Power 3 Spectrum Power 4 Spectrum PowerTG DEMS

SICAM PAS SICAM SCC

SICAM 230 SICAM AK, TM, EMIC SICAM TOOLBOX II

Protection

AMIS Feeder Automation

Power Quality

SIPROTEC / DIGSI Reyrolle

SICAM PQS SICAM P SICAM Q80 SIMEAS R SICAM T

Page 10

March 2013

Siemens AG 2013 I&C Sector

SIPROTEC synonymous with the worlds leading protection technology

First use of electromagnetic relays

The digital age begins for relays

Siemens is honored by Frost & Sullivan for the implementation of IEC 61850

More than one million SIPROTECdevices in operation

First digital application in Wrzburg, Germany

Introduction of the SIPROTEC 4 product group

SIPROTEC Compact outstanding functionality and compact design

SIPROTEC 5 The new benchmark for protection, automation and monitoring

19 77

19 80

19 10

19 98

20 06

20 08

Page 11

March 2013

20 10 20 11
Siemens AG 2013 I&C Sector

Siemens protection portfolio

Page 12

March 2013

Siemens AG 2013 I&C Sector

SIPROTEC 4

Worlds No 1 in protection For all applications Proven, reliable, high experience in the region available > 1.000.000 relays in the field SIPROTEC 4 the experienced, reliable and future proof relay
Siemens AG 2013 I&C Sector

Page 13

March 2013

SIPROTEC 5

Based on 100 years of experience in protection technology Targeting the transmission market Trendsetting technology for the new electricity age Pilot projects already started SIPROTEC 5 the new benchmark for protection, automation, and monitoring of transmission grids
Page 14 March 2013 Siemens AG 2013 I&C Sector

Reyrolle

Simpler devices than SIPROTEC Focus on distribution and industry Strong position in UK influenced markets Same quality standards Reyrolle with-drawable solutions for distribution grids
Siemens AG 2013 I&C Sector

Page 15

March 2013

DIGSI 4 One DIGSI for All Tasks DIGSI 4 is the complete software solution Fault localization Parameterization

Analysis

Configuration Monitoring Control Operation


Page 16 March 2013 Siemens AG 2013 I&C Sector

Power quality detection

SICAM T
Digital transducer for electrical measurands

SICAM P
Power meter for monitoring electrical measurands

SICAM Q80
Power quality recorder for analysis of grid quality in accordance with EN50160

SIMEAS R

Fault recorder, power quality recorder, and phasor measurement unit (PMU) in accordance with IEEE C37.118
Siemens AG 2013 I&C Sector

Page 17

March 2013

Over Current Protection Relay(50,51,50N,51,46,49,..) (Bay Incoming, Non Motor / Small Motor Feeder)
SIPROTEC3 SIPROTEC Compack SIPROTEC4

7SJ600(3CT) 7SJ6021,5(4CT) 7SJ6022,6(3CT+1VT)

7SJ80(4CT+0PT or 3PT) 3PT : 25(option) IEC61850 Available

7SJ61(4CT) 7SJ62(4CT+3PT or 4PT) 7SJ63(4CT+3PT) 7SJ64(4CT+4PT) 4PT : 25(option) IEC61850 Available Protection, Control Monitoring
Siemens AG 2013 I&C Sector

Protection

Protection, Control Monitoring

Page 18

March 2013

Generator Protection Relay / Large Motor (87M,50,51V,50N,51N,46,49,40,50BF,59,27,74TC,.)

SIPROTEC4

7UM62x 8CT(2x3CT+2CT) + 4PT IEC61850 Available

Protection, Control Monitoring


Page 19 March 2013 Siemens AG 2013 I&C Sector

TR Protection Relay (87T,REF,50,51,50N,51N,46,49,50BF,86,74TC,..)

2 Measuring

3 Measuring

5 Measuring

7UT612 (8CT, 3BI, 4BO) IEC61850 Available

7UT613 (13CT+4PT, 5BI, 8BO) 7UT633 (13CT+4PT, 21BI, 24BO) IEC61850 Available

7UT635 (17CT, 29BI, 24BO) IEC61850 Available

Protection

Protection, Control Monitoring


March 2013

Protection, Control Monitoring


Siemens AG 2013 I&C Sector

Page 20

LINE Protection Relay(21, 87L)

21

87L

87L + 21

7SA6(4CT+4PT) l Channel for protection data interface 7SA522(4CT+4PT) 2 Channels for protection data interface IEC61850 Available

7SD61(4CT+4PT, 5BI, 3BO) 1 Channel for protection data interface IEC61850 Available

7SD52/53(4CT+4PT) 2 Channels for protection data interface IEC61850 Available

Protection

Protection

Protection, Control Monitoring


Siemens AG 2013 I&C Sector

Page 21

March 2013

BUS Protection Relay(87B, 50BF)

High-Imp

Low-Imp. (Centralized)

Low-Imp. (Distributed)

7VH60(1CT Input)

7SS60 (2 Measuring Input)

7SS522 (Central Unit) 7SS523/7SS525 (Bay Unit) IEC61850 Available

Protection

Protection

Protection
Siemens AG 2013 I&C Sector

Page 22

March 2013

Various Protection Applications

Motor Protection

V, f, Protection

Breaker Management

7SK80 4CT or 4CT + 3PT or 4CT + 5RTD or 4CT + 3PT + 5RTD IEC61850 Available

7RW600 2 PT Input

7VK61 25, 79, 59, 27, 86 IEC61850 Available

Protection, Monitoring

Protection

Protection, Monitoring, Control


Siemens AG 2013 I&C Sector

Page 23

March 2013

SIPROTEC 5: Modular Hardware Design Base Module with Expansion Modules

Page 24

March 2013

Siemens AG 2013 I&C Sector

SIPROTEC 5 Surface mounted device front view

Page 25

March 2013

Siemens AG 2013 I&C Sector

Mounting of an expansion module

Page 26

March 2013

Siemens AG 2013 I&C Sector

SIPROTEC 5 Different Types of Operator Panels for Base Module Dual Color LEDs (settable to green or red)

No Display
Page 27 March 2013

Small Display

Large Display

Siemens AG 2013 I&C Sector

SIPROTEC 5 Operator Panel US english

Close / Trip Buttons not colored Red / green stickers are delivered for individual use

Page 28

March 2013

Siemens AG 2013 I&C Sector

SIPROTEC 5 Operator Panel Chinese Chinese characters replace the marked symbols and texts. Operator Panel with small display and without display also available in Chinese language.

Page 29

March 2013

Siemens AG 2013 I&C Sector

Operator Panels for expansion modules

Single Color LEDs (red)

Chinese variant available

Without LED
Page 30 March 2013

With LED

With LED and key switches


Siemens AG 2013 I&C Sector

Operating Elements of HMI


Base Module Description Field for LEDs 16 LEDs (red) 16 LEDs (green or red, selectable) Description Field for LEDs Context Sensitive Keys LED Acknowledge and Reset of latched information Numerical Keys and Function Keys USB plug-in Description Field for Function Keys Cursor Keys Expansion Module

Key Switch S5 Remote/Local Key Switch S1 Interlocking Off / Normal Control of Switching Elements
Siemens AG 2013 I&C Sector

Page 31

March 2013

Two Types of Terminals Current Transformer is inside of Current Terminal


Voltage terminal (for voltage measurement, BI, BO)

Current transformer

Current terminal
Page 32 March 2013 Siemens AG 2013 I&C Sector

Two Types of Terminals Change of Current Transformer

Page 33

March 2013

Siemens AG 2013 I&C Sector

Impressions (1) Detailed view on module connections


Robust and stable connection between parts

Page 34

March 2013

Siemens AG 2013 I&C Sector

Impressions (2) Back view


Label: Position and type of IO

Battery
Page 35 March 2013 Siemens AG 2013 I&C Sector

Impressions (3) change of modules

Page 36

March 2013

Siemens AG 2013 I&C Sector

Web site downloading for Relay Data (http://siemens.siprotec.com)

Page 37

March 2013

Siemens AG 2013 I&C Sector

Thank you for your attention

Siemens AG 2013 I&C Sector