NEUTRAL GROUNDING RESISTOR (NGR): Neutral Grounding Resistor (NGR) shall be as follows; a) Material : Stainless Steel b) Rated Current

: 10 Amps. c) Voltage Rating : 11 KV / 3 d) Value of resistor : 635.1 ohm e) Short time rating : 63.51 KW for 30 seconds f) Tolerance in resistance value: + 10 % g) Maximum temp. : 375 deg. C rise of Resistor over 45 deg. C Ambient Temperature.

Vacuum Contactor Specification: Rated Voltage (kV) 7.2 Rated Current (A) 200 Rated Turn-on Current (A) 2000 Rated Interrupted current in Max. (A) 1600 4s Rated Thermo-reliable Current (A) 2000 1min Industrial Frequency Bearing Voltage (kV) 32 Thunder Stroking Bearing Voltage (kV) 60 Semi-wave Permission Pass Current (kA) 40 Mechanical Lifetime Mechanical Keeping 30 10 Electrical Keeping 1x10 Electricity Life (time) AC-3: 25x10 AC-4:10x10
4 6 4

Operation Voltage (V) AC 220 Operation Current (A) AC6A Switch-off Coil Trip Current (A) AC2.5A Keeping Current (A) AC0.45A Origin China.