WHAT IS A BATTERY?
BATTERY IS AN ELECTROCHEMICAL DEVICE WHICH STORES CHEMICAL ENERGY AND RELEASES THE ELECTRICAL ENERGY PARTS OF BATTERY GRIDS ELECTRICALLY CONDUCTING FRAME WORK POSITIVE PLATE LEAD PEROXIDE ACTIVE MATERIAL NEGATIVE PLATE POROUS MASS OF LEAD IN SPONGY FORM SEPERATORS NON CONDUCTING POROUS MATERIAL PLACED BETWEEN POSITIVE AND NEGATIVE PLATE TO AVOID THE TOUCHING EACH OTHER ELECTROLITE H2SO4( SULPHURIC ACID )
STATION LT SUPPLY SHOULD BE ALLWAYS AVAILABLE TO KEEP THE PROTECTION SYSTEM IN ENERGISED CONDITION BUT UNFORTUNATELY THE LT SYSTEM IS NOT RELIABLE.HENCE A BACK UP OF DG SET IS KEPT IN ALL STATION, BUT TO START THE DG SET IT REQUIRES SOME TIME, DURING THAT TIME BATTERIES PROVIDES THE LOAD TO THE PROTECTION SYSTEM .THAT IS THE REASON PROTECTION SYSTEM IS ALWAYS DESIGNED FOR DC. BATTERIES CAN PROVIDE THE SUPPLY TO THE STATION PROTECTION SYSTEM UPTO 10-15 HOURS DEPENDING ON THE LOAD.
APART FROM THE PROTECTION SYSTEM THE MONITORING AND RECORDING SYSTEM LIKE ANNUNCIATION , EVENT LOGGER , DISTURBENCE RECORDER ,GPS ,RTU, SPEECH AND PROTECTION COUPLER OF PLCC ARE ALSO CONNECTED TO THE BATTERY SYSTEM FOR RELIABILITY
THERE ARE BASICALLY TWO RANGES OF BATTERY SYSTEM AVAILABLE IN SUB-STATION 1. 220 VOLTS 2. 5O VOLTS
220V BATTERY SYSTEM IS BASICALLY THE SERIES CONNECTION OF 110 NOS OF 2.1V LEAD ACID BATTERIES EACH CAPACITY OF 400 AH IN EVERY SUB-STATION TWO SETS OF BATTERIES ARE KEPT FOR MORE RELIABILITY EACH SET IS CONNECTED WITH SEPARATE BATTERY CHARGERS THESE SETS ARE USED FOR STATION PROTECTION SYSTEM , DISTURBANCE RECORDER AND ANNUNCIATION SYSTEM
50 V BATTERIES SYSTEM
50V BATTERY SYSTEM IS BASICALLY THE SERIES CONNECTION OF 24 NOS OF 2.1V LEAD ACID BATTERIES EACH CAPACITY OF 400 AH IN EVERY SUB-STATION TWO SETS OF BATTERIES ARE KEPT FOR MORE RELIABILITY EACH SET IS CONNECTED WITH SEPARATE BATTERY CHARGERS THESE SETS ARE NORMALLY USED FOR PLCC SPEECH AND PROTECTION COUPLER AND MONITORING SYSTEM SUCH AS EVENT LOGGER AND GPS
BATTERY CHARGERS
BATTERY CHARGERS CONSISTS OF FLOAT CHARGER BOOST CHARGER STAND-BY CHARGER DCDB
FLOAT CHARGER
FLOAT CHARGER IS BASICALLY DESIGNED FOR CONSTANT VOLTAGE OPERATION . VOLTAGE CAN BE SET BETWEEN 200-250V FOR 220V CHARGER AND 45-55V FOR 50V CHARGER IT IS CONNECTED IN PARALLEL TO THE BATTERY SYSTEM AND TO THE LOAD IT KEEPS THE BATTERIES UNDER CHARGED CONDITION
BOOST CHARGER
BOOST CHARGER IS GENERALLY SAME AS THE FLOAT CHARGER EXCEPT THAT OUTPUT IS SET BETWEEN 200-300V FOR 220V AND BETWEEN 45-60V FOR 50V IT IS SWITCHED ON DURING INITIAL CHARGING , WHEN BATTERIES ARE DRAINED OUT AND DURING TOPPING UP OF BATTERIES WITH DISTILLED WATER
STAND BY CHARGER
IT IS ALSO SAME AS FLOAT CHARGER EXCEPT THE FOLLOWING CHANGES IF THE MAIN FLOATS ARE ON THE STAND-BY CANNOT BE SWITCHED ON WHEN ANY ONE FLOAT CHARGER FAILS / TAKEN OUT FOR MAINTENANCE STAND-BY CAN BE TAKEN INTO SERVICE
DC DISTRIBUTION BOARD
IT IS A DISTRIBUTION BOARD FROM WHERE LOADS ARE CONNECTED SEPARATE DCDB IS AVAILABLE FOR EACH SET OF BATTERIES. COUPLING FACILITIES IS AVAILABLE
DAILY MONITORING OF SPECIFIC GRAVITY , TEMPERATURE AND VOLTAGE OF CELLS LIMITS FOR SPECIFIC GRAVITY -1.2100.005 VOLTAGES-2.17V TEMPERATURE-27C
MONTHLY MAINTENANCE
CHECKING OF ELECTROLYTE LEVEL AND TOPPING UP WITH DISTELLED WATER IF REQUITED CHECKING OF EMERGENCY DC LIGHTING IN CONTROL ROOM NOTE THE TOTAL BATTERY VOLTAGE ( SWITCH OFF THE CHARGER) MEASURE THE CELL VOLTAGE AND SPECIFIC GRAVITYOF ALL CELLS. CHECK THE ANY EARTH FAULT IN DC SYSTEM
DISCHARGE CAN BE STOPPED WHEN THE VOLTAGE ACROSS THE BATTERY BANK FALLS TO 1.85 X NUMBER OF CELLS OR VOLTAGE ACROSS ANY ONE CELL FALLS TO 1.70 V NOTE DOWN THE STIP TIME (Ts) DISCHARGE TIME (Td) = (Ts)-(Tb) FORMULA OF % CAPACITY OF BATTERY BANK =(Id) X (Td) ------------ X 100 AH
RECHARGING
RECONNECT THE BATTERY TO CHARGER RECHARGE THE BATTERY BANK AT CONSTANT NORMAL RE-CHARGE CURRENT OF 10% OF CAPACITY RECORD THE INDIVIDUAL CELL VOLTAGE, BATTERY TERMINAL VOLTAGE AND SPECIFIC GRAVITY OF CELL IN ONE INTERVALS CONTINUE CHARGING TILL THE VOLTAGE OF EACH CELL REACHES 2.55 V TO 2.65 V AND SPECIFIC GRAVITY REACHES TO 1.2100.005. STOP THE RECHARGING OPERATION
GENERATOR IS A MACHINE WHICH CONVERT THE MECHANICAL ENERGY IN TO ELECTRICAL ENERGY GENERATOR IS BASED ON PRINCIPAL THAT WHENEVER FLUX CUT BY CONDUCTOR , AN EMF IS INDUCED WHICH WILL CAUSE A CURRENT TO FLOW IF THE CONDUCTOR CIRCUIT IS CLOSED.
WHEN THE LT SUPPLY IS NOT AVAILABLE D.G SET WILL BE TAKEN IN TO SERVICE TO FEED THE A.C SUPPLY TO THE SYSTEM. IF LT SUPPLY FAILED AND D.G SET FAILED TO START, SUPPLY WILL NOT BE AVAILABLE FOR BREAKER COMPRESSORS TO BUILD UP THE REQUIRED AIR PRESSURE FOR CIRCUIT BREAKERS, A.C PLANT TO KEEP THE PROTECTION RELAYS, PLCC PROTECTION SYSTEM UNDER DESIRED TEMPARATURE F/F SYSTEM TO PUMP THE WATER AT PRESSURE WHEN IS FIRE IS TAKEN PLACE BATTERY CHARGERS WILL NOT FEED THE LOAD TO SYSTEM AND AS WELL AS TO BATTERIES. HENCE BATTERIES GET DISCHARGED. FAN AND PUMPS OF ICTS WILL NOT RUN HENCE THE WINDING AND OIL TEMPARATURE RAISES. TO OVER COME THE ABOVE PROBLEMS D.G SETSHOULD BE KEPT UNDER HEALTHY CONDTION.
STARTING PROCEDURE
START THE GENERATOR AT MINIMUM SPEED. WAIT FOR FEW MINUTES AND SLOWLY INCREASE THE SPEED UP TO 1500 RPM. CHECK THE VOLTAGE AND FREQUENCY AND ADJUST GOVERNER IF REQUIRED. CLOSE THE D.G. BREAKER AND CONNECT THE LOADS STEP BY STEP CHECK THE VOLTAGE, CURRENT, AND FREQUENCY. RECORD THE OIL/WATER TEMPARATURE, RUNNING HOURS,FUEL LEVEL ETC.ONCE IN EVERY TWO HOURS.
STOPPING PROCEDURE
REDUCE THE LOADS STEP BY STEP WAIT FOR FEW MINUTES AND BRING THE D.G.SET TO THE MINIMUM SPEED STOP THE D.G SET. RECORD THE FUEL LEVEL AND RUNNING HOURS.
D. G. SET
MAINTENANCE OF D.G.SETS
PREVENTIVE MAINTENANCE IS THE EASIEST AND LEAST EXPENSIVE TYPE OF MAINTENANCE.
MAINTENANCE SCHEDULE
A CHECKS B CHECK C CHECK D CHECK E CHECK
MAINTENANCE OF D.G.SETS
A CHECKS ( DAILY)
CHECK THE ENGINE OIL LEVEL DRAIN THE SEDIMENT FROM FUEL TANK CHECKTHE FUEL SUPPLY CHECK AIR CLEANER CHECK THE COOLENT LEVEL CHECK THE LEAKS CHECK STARTING BATTERIES
MAINTENANCE OF D.G.SETS
MAINTENANCE OF D.G.SETS
MAINTENANCE OF D.G.SETS
MAINTENANCE OF D.G.SETS
MAINTENANCE OF D.G.SETS
SEASONAL CHECKS
CLEAN THE COOLING SYSTEM REPLACE HOSE AS REQUIRED CLEAN ELECTRIC CONNECTIONS CHECK THERMAL CONTROL CHECK THE OVER SPEED SWITCH CLEAN THE ENGINE WATER HEATER
FIREFIGHTING SYSTEM
FOLLOWING EQUIPMENTS.
AIR COMPRESSOR JOCKY PUMP HYDRANT PUMP MAIN ELECTRIC PUMP DIESEL ENGINE H.P TANK CONTROL, RELAY AND ANNOUNCIATION PANELS
AIR COMPRESSOR
IT SUPPLIES THE AIR TO HP TANK TO MAINTAIN THE PRESSURE IN THE WATER LINE.
JOCKY PUMP
IT PUMPS THE WATER TO HP TANK TO MAINTAIN THE PRESSURE IN THE WATER LINE. IF THERE IS A MINOR WATER PRESSURE DROP IN THE SYSTEM DUE TO LEAKS IN THE GLAND PACKING OF VALUES, FLANGE JOINTS, OR DUE TO CHANGE IN THE ATMOSPHERIC TEMPARATURE THE JOCKY PUMP WILL START AND COMPENSATE THE MINOR LEAKAGES. IT SHOULD BE KEPT IN AUTO MODE. IT OPERATES ON HP TANK FLOAT SWITCH.
HYDRANT SYSTEM
WATER STORAGE
Water for the fire protection services has been made available in the fire water storage tank adjacent to the pump house. As per the TAC rules water to be stored for hydrant system should be 135 cum and 20 minutes water requirement of the largest equipment under the protection for HVWS system.
HYDRANT SYSTEM
II. The Water Supply, Pumping Capacity and other features of Hydrant System depend not only on the size of risk but also Fire growth and spread potentialities. Accordingly various categorized by TAC . DESCRIPTION Hydrant System is a wet line and the system is always kept pressurized at 8.0 Kgs/Cm. Hydrants Have been provided around the periphery of the various buildings at distance of not more than 60 mts from each other. Location of hydrants have been fixed keeping in mind to attendant the fire hazards at different sections of particular building being protected. Two Nos of Hoses ( 22 Mts/15 Mts ) Nozzles have been provided in each box.
HYDRANT SYSTEM
In the case of fire in a particular area, Hydrant located near by fire area to be opened by trained staff, manually. The Fire is fought by means of hoses and nozzles provided in the hose boxes
HYDRANT SYSTEM
SYSTEM OPERATION
When any hydrant is opened, the pressure in the line drops. When the pressure fallows below 6. 8 kgs/cm the pressure switch will send the impulse to the motor control panel. Due to this power will be supplied to the motor and hydrant pump will start automatically and continuous supply of water is made available for the hydrant outlets. After the fire has been quenched, the pump has to be stopped manually.
HYDRANT SYSTEM
IF HYDRANT PUMP FAILS TO START, THE PRESSURE IN NET WORK WILLFURTHER DROP DOWN TO 6.2 KGS/CM MAINELETRIC PUMP WILL START IF FURTHER DROPS TO 5.8 KGS/CM, DIESEL ENGINE PRESSURE SWITCH WILL ACTUATE AND DIESEL ENGINE WILL START AUTOMATICALLY AND PRESSURIZED WATER WILL BE SUPPLIED TO THE PIPE LINE. AFTER OPERATION DIESEL PUMP SHOULD BE SWITCHED OFF MANUALLY.
HYDRANT SYSTEM
ANNOUNCIATION SCHEME HYDRANT PUMP RUNNING FIRE IN THE HYDRANT SYSTEM FAILS TO START ( IF MOTOR FAILED TO START)
HYDRANT SYSTEM
WHAT IS TO BE DONE
REQUIRED NO OF HOSES AND BRANCH PIPES ARE TO BE TAKEN FROM HOSE BOXES AND BROUGHT NEAR THE HYDRANTS TO BE OPNED. BRANCH PIPES TO BE FIXED TO HOSES AND HOSES TO HYDRANTS. THE REQUIRED NO OF HYDRANTS TO BE OPENED. WATER STREAM FROM HOSES ARE TO BE DIRECTED TO ROOT FIRE BY TRAINED STAFF. NOTE: BEFORE OPERATING HYDRANT SYSTEM POWER SUPPLY TO ELETRICAL EQUIPMEN SHALL BE CUT OFF.
HYDRANT SYSTEM
QUENCHING OF FIRE
FIRE IS QUENCHEDBY OPERATING THE HYDRANTS FOR THE NECESSARY TIME THE PUMP IS STOPPED MANUALLY, AFTER ENSURING THAT FIRE HAS BEEN QUENCHED.
HYDRANT SYSTEM
HVWS SYSTEM
HVWS SYSTEM
DETECTORS
DELUGE VALVE
HVWS SYSTEM
HVWS SYSTEM
THE ELECTRIC MOTOR WATER SPARY PUMP STARTS ELECTRIC MOTOR PUMP RUNNING ANNUNCIATION RECEIVED IN THE PANEL THE HVWS SYSTEM OPERATES CONTINUOUSLY TILL THE FIRE IS PUT OFF AFTER FIRE IS QUENCHED THE PUMP TO BE STOPED MANUALLY.
HVWS SYSTEM
SYSTEM RESETTING
THE WATER SPRAY PUMP IS STOPPED MANUALLY THE SLUICE VALVE BEFORE DELUGE VALVE IS TO BE CLOSED THE DELUGE VALVE AND PROJECTOR NETWORK PIPING IS TO BE DRAINED THE BULBS WHICH HAVE BEEN DAMAGED ARE TO BE REPLACED BY SIMILAR TYPE OF DECTORS. THE DELUGE VALUE TO BE RESETT. PRESSURISE THE DECTION LINE AROUND THE EQUIPMENT PRESSURISE THE WATER HEADER CHECK THE PRESSURE GAUGE READING NEAR THE DELUGE VALVE
PREVENTIVE MAINTENANCE
MONTHLY MAINTENANCE
RUN MOTORS FOR FIVE MINUTES & CHECK FOR SMOOTH OPRATION CLEAN ALL MOTORS, PUMPS AND OTHER EQUIPMENTS IN THE PUMP HOUSE CLEAN THE FLOOR AND CEILING CHECK ALL VALVES CHECK THE OIL LEVEL IN DIESEL ENGINE
QUARTERLY MAINTENANCE
CHECK COMPRESSOR OIL & REPLACE IF NECESSARY CHECKING OF BELT TIGHTNESS CLEANING OF OIL STAINERS
YEARLY MAINTENANCE
OPERATE DELUGE SYSTEM FOR OIL FILLED EQUIPMENTS. CHECK THE FIRE HOUSE CABNETS ARE COMPLETE WITH HOSE REELS AND NOZZLES. SEAL THE CABNET WITH LEAD SEAL AFTER INSPECTION
SMOKE DETECTION SYSTEM IS PROVIDED WITH IONISATION AND PHOTOELECTRIC TYPE SMOKE DETECTORS.
SYSTEM OPERATION
GENERALLY FIRE BREAKS OUT MAINLY DUE TO THE SHORT CIRCUITING OF CABLE. IN WHICH CABLE INSULATION MELTS AND GIVES SMOKE INITIALLY, THE DENSITY OF THE SMOKE IS LESS THAN THE ATMOSPHRIC AIR AND HAS THE TENDENCY TO TRAVELL UP. WHEN THE SMOKE REACHES THE DETECTOR FIRE IS DETECTED AND THE ANNUNCIATION OF FIRE IN RESPECTIVE AREA IS RECEIVED IN THE FIRE ALARAM PANEL LOCATED IN THE CONTROL ROOM. THE HOOTER PROVIDED GIVES THE AUDIABLE SIGNAL. QUENCH THE FIRE BY USING FIRE EXTINGUISHERS.
YEARLY MAINTENANCE
CHECK FOR OPERATION OF FIRE ALARM SYSTEM INSTALLED AT VARIOUS LOCATIONS BY AGARBATTI, OR SOME SMOKE DEVICE CHECK FOR ALARAM IN THE CONTROL PANEL CHECK THE CONDITION OF BATTERY CHECK FOR CLEANLINESS.
A.C PLANT
A.C. PLANT
DESCRIPTION
A.C PLANT CONSISTING OF THE FOLLOWING EQUIPMENTS.
MOTORS COMPRESSORS (770) CONDENSER PUMPS AHUS CONDENSERS LT SUPPLY PANELS & CONTROL PANELS
A.C. PLANT
DESCRIPTION
WHEN COMPRESSOR STARTS, IT COMPRESS THE FREON GAS . THE COMPRESSED FREON GAS WITH RAISED TEMPARATURE IS DELIVERED TO THE CONDENSER UNIT. IN CONDENSER UNIT THE GAS IS COOLED AND PARTIALLY IT BECOMS LIQUID. THE LIQUID GAS MIXTURE ENTERS THE AHU ROOM THROUG THE PIPES AND GETS EXPANDEDIN THE AHU . THE FREON BECOMES GAS AND THER BY ABSORB THE HEAT FROM THE AIR. THE FREON IN GAS STATE COMES OUT OF THE AHU THROUGH PIPES AND IS SUCKED BY THE COMPRESSOR AND CYCLE REPEATS.
A.C PLANT
SEQUENCE OF OPERATION
CHECKS BEFORE STARTING
CHECH THE WATER LEVEL IN WATER TANK. CHECK THE OIL LEVEL IN THE COMPRESSOR CHECK THE ALL SOLENOID VALVES ARE IN OFF POSITION CHECK THE HP,LP,OIL PRESSURE GAUGES. CHECK THE REQUIRED VALVES ARE IN OPEN CONDITION CHECK THE AVAILABILITY OF A.C SUPPLY CLOSE THE DOORS AND WINDOW,S OF THE ROOMS TO BE COOLED. CHECK FOR GAS LEAKAGE
A.C PLANT
A.C PLANT
STOPPING PROCEDURE
REDUCE THE LOAD BY SWITCHING OFF USVII,USVI AND RSV WAIT FOR FEW MINUTES SWITCH OFF THE COMPRESSURE SWITCH OFF THE WATER CONDENSER PUMP. SWITCH OFF THE COTROL CIRCUIT UNIT SWITCH OFF THE AHU I & AHU II
A.C PLANT
CONTROL INTERLOCKS
CONDENSER PUMP STARTS ONLY IF AHU IS ON CONDENSER PUMP STOPS IF AHU TRIPS COMPRESSOR STOPS IF CONDENSER PUMP OR AHU TRIPS.
A.C PLANT
MAINTENANCE
MONTHLY MAINTENANCE COMPRESSORS
CHECK OIL LEVEL IN SIGHT CLASS CHECK THE ALIGHMENT, SAFETY GUARD LEAKAGE CHECKS FOR REFRIGERANTS AND OIL
CONTROL PANELS
CHECK FOR LOOSE CONTACTS OF TERMINALS CLEAN IN SIDE CONDENSER UNIT CHECKING OF WATER PRESSURE INLET/OUT LET CHECKING OF WATER LEAKS OPERATION OF INLET /OUTLET VALVE
A.C PLANT
A.C PLANT
YEARLY MAINTENANCE
CLEANING OF STRAINER CLEANING OF CONDENSING COILS CHECKING FOR RUSTING, DAMAGE OF PAINT- REPAINTING IF NECESSARY CLEAN THE AHU FILTERS CHECK THE OIL PRESSURE SWITCH,HP,LP CUT OUT SWITCHES, SOLENOID VALVESETC. CLEANING OF WATER TANK AND REGENARATION OF CHEMICALS CHECKS FOR LOOSE CONTACTS ANY IN ALL CONTROL PANELS