Вы находитесь на странице: 1из 1

PERSONAL SERVICE REPORT

Generator Radiator Water Report

Plant of. Address Attention Copy to

: M/s. Unique Power Plant Ltd.


: Meghnaghat, Narayangonj : General Manager (Technical) : General Manager (Power plant)

Date: 01/08/13(S/D-27/07/13) Plant: Generator

.
.

. .

TEST RESULT WATER SAMPLE TDS Generator-1 # LT Generator-1 # HT Generator-2 # LT Generator-2 # HT Generator-3 # LT Generator-3 # HT Generator-4 # LT Generator-4 # HT Generator-5 # LT Generator-5 # HT 3130 2860 1756 1080 1345 3490 2830 2750 2560 2610 pH 9.56 9.47 9.34 9.26 9.34 9.65 9.47 9.40 9.48 9.42 NO2 840 800 510 330 380 870 800 720 730 720 Fe Cl
-

RECOMMENDED READINGS

ppm as TS

TDS

pH

ppm as

ppm as

ppm as

RECOMMENDED DOSAGE OF COOLANT Nalco 2000

NO2

Fe

Cl

800 PPM to 1200 PPM Sample is not available for test due to drain

Less than 2.0 ppm

less than 350ppm

@ 1. 70 lt/100 lt water @ 1. 85 lt/100 lt water @ 1. 60 lt/100 lt water

Below 3500 PPM

9-11

@ 1. 15 lt/100 lt water @ 1. 10 lt/100 lt water @ 1. 15 lt/100 lt water

SUMMARY & RECOMMENDATIONS: Please dosage Nalcool 2000 as stated above.

For best results, drain and flush radiator system every twelve month or 8000 hours or as specified in your owner manual.
TDS = Total Dissolved Solids, NO2 = Nitrite.

WORLDWIDE LEADER ON-SITE EXPERT

NALCO SINGAPORE
Nasir Uddin Signature
( A DIVISION OF NALCO PACIFIC PTE LTD. ) 21, GUL LANE, JURONG TOWN, SINGAPORE 629416.