PCI 101
End Introduction
PCI 101.1
Module 1
PCI 101.1
Process measurement is the art and science of applying instruments to sense process conditions
PCI 101.1
The controller makes decisions based on process sensors and modulates control valves to reach the user defined setpoint.
Discuss control system diagrams on overhead projector.
No matter how advanced or sophisticated the control system, it is only as effective as the process measurement instruments it is connected to
PCI 101.1 6
PCI 101.1
PCI 101.1
PCI 101.1
Vendors may vary the use of a termspecmanship can be used to bewilder the uninformed instrument engineer
PCI 101.1
10
Optimization Arch
PCI 101.1
11
No measurement, however precise or repeated, can ever completely eliminate uncertainty due to dynamic conditions
PCI 101.1
12
Temperature Effects
Induced phase transitions (process changes from liquid to solid or liquid to gas) Changes in dimensions of measuring element Resistance of a circuit Change in flux density of a magnetic element
Temperature influences can exhibit some of the most severe effects on a process measurement
PCI 101.1
13
Temperature Effects
Corrections are required for static pressure, temperature, specific gravity etc.
A 10 degree F change in temperature causes a 2% change in density, which results in a 1% effect on total flow measurement
PCI 101.1 14
Pressure Effects
Pressure effects can also trigger phase transitions Pressure effects show up in dP measurements used in flow and level applications in addition to direct pressure measurements. Static pressure influences a transmitters output because of a physical distortion that occurs on the measuring element.
The goal is to minimize the total error that pressure effects can causevariations in line pressure are not accounted for during normal operations
PCI 101.1 15
Electrical Interference
Electromagnetic Interference (EMI) Radio Frequency Interference (RFI)
Common Mode
Normal Mode
Instrument vendors often list specifications that indicate how resistant the device is to electrical interference
PCI 101.1
16
PCI 101.1
17
Electromagnetic Interference
PCI 101.1
18
PCI 101.1
19
PCI 101.1
20
PCI 101.1
21
Electrical Interference
Handout Reducing Electrical Noise in Instrument Circuits
IEEE Transactions
With the trend toward more complete instrumentation in process plants using more sophisticated and more sensitive instruments than in the past, the reduction of electrical noise pickup by instrument circuits has become a real problem for the instrument engineerBruce Klipec, IEEE 1967
PCI 101.1
22
Instrumentation Response
Ramp Response Step Response
Time Constant
Settling Time Rise Time
For the output of a first-order system forced by a step or an impulse, T is the time required to complete 63.2% of the total rise or decay at any instant during the process
PCI 101.1
23
Ramp Response
PCI 101.1
24
Step Response
PCI 101.1
25
PCI 101.1
26
PCI 101.1
27
Damping Definitions
PCI 101.1
28
PCI 101.1
29
Range Examples
PCI 101.1
30
Range Definitions
PCI 101.1
31
An instrument spec may claim 0.25% accuracy or even greater under reference conditionshowever, the total error could be 2.5% once installed
PCI 101.1
32
Work through example in text of Zero Shift with Temperature (pg. 28) and Static Pressure Effects (pg. 31) using Rosemount 1151 Handout
PCI 101.1
33
PCI 101.1
34
Relationship of Limits
PCI 101.1
35
PCI 101.1
36
PCI 101.1
37
PCI 101.1
38
PCI 101.1
39
PCI 101.1
40
PCI 101.1
41
Repeatability
PCI 101.1
42
Linearity
Independent Terminal Zero
PCI 101.1
43
Independent Linearity
PCI 101.1
44
Terminal Linearity
PCI 101.1
45
Zero-Based Linearity
PCI 101.1
46
Hysteresis
PCI 101.1
47
PCI 101.1
48
Drift
Zero Drift Span Drift Partial Drift
Undesired slow change or amount of variation in the output signal over a period of time
PCI 101.1
49
Reliability
MTTF MTTR MTBF = MTTF + MTTR
Used to quantify a devices ability to perform a function without failure over a specified period of time or amount of use
PCI 101.1
50
PCI 101.1
51
TPE
F&P Handout 10E-3b
Because of the random distribution of errors, the square root of the sum of the squares of error contribution is used in practice
PCI 101.1
52
PCI 101.1
53
Exercise 2 Solution
Transmitter is performing at 120F and is measuring 112.5 H2O. Reference accuracy = + 0.2% of calibrated span = (.002)x(150) = 0.3 H2O Temperature effect = total error =(+ 0.5% URL+ 0.5% calibrated span)/100F x deltaT =(.005)(150)+(.005)(150)/100F x 50F = 0.75 H2O Static pressure = Zero + Span error Zero error = + 0.25% URL/2000 psi (does this apply?) Span error = + 0.25% Input reading/1000 psi (does this apply?)
PCI 101.1
54
Exercise 2 Solution
PCI 101.1
55
Keep the Design Simple Avoid using glass Keep electronics Cool Provide easy Serviceability Safety
Considering these issues will help ensure an installation that will not result in problems down the road.
PCI 101.1 56
PCI 101.1
57
PCI 101.1
58
Housing Example
PCI 101.1
59
Corrosion References
PCI 101.1
60
Ensure the measurement device is actually capable of performing the required measurement.
PCI 101.1 61
PCI 101.1
62
PCI 101.1
63
Gasket Considerations
PCI 101.1
64
Seal Example
PCI 101.1
65
PCI 101.1
66
Seal References
PCI 101.1
67
Mounting brackets, bolts, etc.? Piping support, grounding, etc.? Flanges? Location?
Dont forget your Maintenance buddies install the instrument where it can be easily accessed.
PCI 101.1 68
Flange Styles
PCI 101.1
69
PCI 101.1
70
Flange References
PCI 101.1
71
Manifolds (SST) Impulse Lines (1/2 SST tubing typical) Orientation critical (more in modules to come) Thermowell insertion length/vibration
Consider how the instrument will be usedthe installation should be suited to the application.
PCI 101.1
72
Data Transmission Power (Requirements and Consumption) Wiring methods Safety (protection methods in hazardous areas)
Consider all the aspects of electrical design the loop may work, but may not be safe to operate in the intended location.
PCI 101.1 73
PCI 101.1
74
PCI 101.1
75
PCI 101.1
76
PCI 101.1
77
PCI 101.1
78
PCI 101.1
79
PCI 101.1
80
Wiring References
PCI 101.1
81
Noise Considerations
PCI 101.1
82
PCI 101.1
83
PCI 101.1
84
Grounding Considerations
PCI 101.1
85
PCI 101.1
86
PCI 101.1
87
PCI 101.1
88
PCI 101.1
89
PCI 101.1
90
The key to electrical safety is to ensure that the electronic instrumentation will not become the source of an ignition source
PCI 101.1 91
The key to electrical safety is to ensure that the electronic instrumentation will not become the source of an ignition source
PCI 101.1 92
PCI 101.1
93
Calibration References
PCI 101.1
94
Traceability Pyramid
PCI 101.1
95
PCI 101.1
96
PCI 101.1
97
PCI 101.1
98
PCI 101.1
99
PCI 101.1
100
PCI 101.1
101
Hart Protocol
PCI 101.1
102
Honeywell DE Protocol
PCI 101.1
103
Fieldbus Architecture
PCI 101.1
104
PCI 101
End Module 1