Вы находитесь на странице: 1из 1

Power Systems Analysis II EEPB 383 Semester 2 2013/14 Homework - Symmetrical Components

A three phase inductive load is powered by a three phase power supply as shown in Figure 1. Due to a broken conductor on the blue (B) phase of the overhead line, voltage measured at the load terminals in per unit were found to be as follows:

V R = 1.00 ; VY = 1.0 120 V B = 00 .

Figure 1 The sequence impedance of the network components on a 10 MVA base are as follows: Component Sync Generator Transformer, 1000/400 V
Overhead Line, 400V Inductive Load

Sequence Impedance 2 X1 g = X g = j 0 .1 ;

0 Xg = j 0.05

1 2 0 XT = XT = XT = j 0.08 2 0 X1 L = X L = X L = j 0.06 3 phase, 400V, 1 MVA

a) Determine using symmetrical component method the phase current I R , I Y , I B of the three phase load. b) Compare and validate your answers based on calculation using phase quantity.

Вам также может понравиться