Pressure Relief Valve Calculation Report 19-set-2013

Quote Number:
Client: Location: Project:

No

Prpd. Chk. Appr. End-User Ref. No.: Project Ref. No.:

Date

Revision

VALVE ID CALCULATION NOTES 1 11 Tag No. QuickCalc001 2 12 Valve Model No. 63BM48-5 Qty. 1 3 13 SIZING DATA 4 14 Design Code ASME Section VIII Sizing Std. API 520 15 5 Gas / Vapor 6 Fluid State at Inlet 16 CALCULATION SUMMARY 7 Required 1 kg/hr Required 0,040 mm 8 18 Flow Area Rated 1236,639 kg/hr Selected 49,677 mm 9 19 Estimated Reaction Force 8,8 kgf Estimated Noise Level (db) 128,6 at 1 m 10 20 Variable Type Variable Name Symbol Input Value Equation Value Fluid Properties Molecular Weight M 86,480 86,480 Ratio of Specific Heats k 1,180 1,180 Compressibility Z 1,000 1,000 Process Cond. Required Mass Flow Wreq 1 kg/hr 1 kg/hr Set Pressure Pset 21 kg/cm g 20,594 barg Over Pressure Pover 2,1 kg/cm g 2,059 barg Inlet Line Loss Ploss 0 kg/cm g 0 barg Back Pressure Pback 0 kg/cm g 0 barg Atmospheric Pressure Patm 1,033 kg/cm a 1,013 bara Relieving Temperature T 80 C 353,150 K Distance from Valve (noise) r 1 m 1 m Rupture Disc CCF Kc 1,0 1,0 Valve Data Discharge Coefficient (actual) Kd 0,928 0,928 Discharge Coefficient (derated) K 0,835 0,835 Orifice Area A 49,677 mm 0,497 cm Back Pressure Correction Factor Kb 1,0 1,0 Outlet Diameter Do 25,400 mm 2,540 cm Calculate Inlet Relieving Pressure, Outlet Pressure, Absolute Pressure Ratio P1 = Pset + Pover - Ploss + Patm P1 23,667 bara P2 = Pback + Patm P2 1,013 bara PR = P2 / P1 PR 0,043 Calculate Gas Constant C = 394.8 * {k * [2 / (k + 1)]^[(k + 1) / (k - 1)] }^0.5 Calculate Mass Critical Flow W = A * C * K * P1 * Kb * Kc * [M / (T * Z)]^0.5 Calculate Required Orifice Area Areq = A * Wreq / W Calculate Mass Critical Flow (for Noise Calc) W = A * C * Kd * P1 * Kb * Kc * [M / (T * Z)]^0.5 Calculate Noise Level at 100-ft (30-m) C 254,5

1236,639 kg/hr

1236,639 kg/hr

Areq

0,040 mm

0,0004 cm

1374,043 kg/hr

L100

99,0 db

L100 = [6.5 * log( 1/PR ) + 51.28] + [10 * log(1.1552 * W * k * T / M)] Printed On: 19-set-2013 Page : 1

Pressure Relief Valve Calculation Report 19-set-2013

Quote Number:
Client: Location: Project:

No

Prpd. Chk. Appr. End-User Ref. No.: Project Ref. No.: 11 12 13 14 15 16 18 19 20

Date

Revision

VALVE ID 1 Tag No. QuickCalc001 2 Valve Model No. 63BM48-5 Qty. 1 3 SIZING DATA 4 Design Code ASME Section VIII Sizing Std. API 520 5 Gas / Vapor 6 Fluid State at Inlet CALCULATION SUMMARY 7 Required 1 kg/hr 8 Flow Rated 1236,639 kg/hr 9 Estimated Reaction Force 8,8 kgf 10 Calculate Noise Level at Distance, r Lp Lp = L100 - 20 * log(r / 30) Calculate Outlet Static Pressure Po Po = [(0.003225 * A * C * Kd * P1 * Kc) / (Do^2 * (k * Z)^0.5)] - Patm

CALCULATION NOTES

Area

Required Selected Estimated Noise Level (db)

0,040 mm 49,677 mm 128,6 at 1 m 128,6 db

0,264 barg

Calculate Reaction Force for Open Discharge Fr Ao = ( * Do^2) / 4 Fr = (A * C * Kd * P1 * Kc / 27.907) * {k / [(k + 1) * Z]}^0.5 + (10* Ao * Po)

8,8 kgf

86,6 N