PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE:

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

H.H.SH. AHMED BIN SAIF AL NAHYAN

SMDB REF: SMDB - F34E

LOCATION: ELECT. ROOM


34TH FLOOR
RATING-AMPS

SR. CIRCUIT FEEDER DB


SP/ TP
No.
NO.

INCOMER

1
2
3
4
5
6
7
8

OUTGOING
BOOSTER WAT. P
DB - RE
LIFT - 1
LIFT - 1 CONTROL
SEF - 1
SPF - 1
SPF - 2
SPARE

ACB

MCCB

FAULT
DUTY
MCB
KA

SWA/PVC

CABLE SIZE
2/4 x 1C
mm2

2/3/4C
mm2

LENGTH
OF
CABLE
(mtrs)

CONNECTED LOAD-KW

KWH METER

ECC
SIZE-1C
mm2

R-PHASE
KW

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

LV/HV
CT (4)

REMARKS

TP

100
(N/A)

35

FIRE PROOF

4C 70

1C 35

24.1

23.45

23.2

70.75

TP
TP
TP
SP
TP
TP
TP
TP

20
40
160
20
20
32
20
20

35
35
35
35
35
35
35
35

XLPE /SWA/PVC

4C 4
4C 10
4C 70
2C 4
4C 4
4C 6
4C 4

1C 4
1C 10
1C 35
1C 4
1C 4
1C 6
1C 4

1.00
2.60
12.00
1.00
1.00
3.00
2.50
1.00

1.00
2.95
12.00
1.00
3.00
2.50
1.00

1.00
2.70
12.00
1.00
3.00
2.50
1.00

3.00
8.25
36.00
1.00
3.00
9.00
7.50
3.00

4P ELCB 100 mA

24.1

23.5

23.2

70.75

TOTAL

SMDB- F34E CONNECTED TO: MDB - E


DEMAND FACTOR 0.90

CONTRACTOR:

PVC/XLPE

XLPE /SWA/PVC

FIRE PROOF
FIRE PROOF
FIRE PROOF
FIRE PROOF
FIRE PROOF

TOTAL CONNECTED LOAD PER PHASE

MAX. DEMAND..
63.68 KW

TOTAL CONNECTED LOAD (3PH) 70.75 KW

TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

(1) UP TO 60A
(1 PHASE)

4P ELCB 300 mA
DP ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE:

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

H.H.SH. AHMED BIN SAIF AL NAHYAN

SMDB REF: SMDB - F20E

LOCATION: ELECT. ROOM


20TH FLOOR
RATING-AMPS

SR.
No.

1
2
3
4
5
6

FAULT
DUTY
MCB
KA

PVC/XLPE

CABLE SIZE

LENGTH
OF
CABLE
(mtrs)

ECC
SIZE-1C
mm2

CIRCUIT FEEDER DB
NO.

SP/ TP

INCOMER

TP

100
(N/A)

35

FIREPROOF

4C 35

1C 16

TP
TP
TP
TP
TP
TP

40
40
40
40
40
20

35
35
35
35
35
35

XLPE /SWA/PVC

4C 10
4C 10
4C 10
4C 10
4C 10

1C 10
1C 10
1C 10
1C 10
1C 10

OUTGOING
DB - F20E
DB - F23E
DB - F26E
DB - F29E
DB - F32E
SPARE

ACB

MCCB

SMDB- F20E CONNECTED TO: MDB - E


DEMAND FACTOR

CONTRACTOR:

0.90

SWA/PVC

2/4 x 1C
mm2

2/3/4C
mm2

XLPE /SWA/PVC
XLPE /SWA/PVC
XLPE /SWA/PVC
XLPE /SWA/PVC

MAX. DEMAND..
35.55 KW

(1) UP TO 60A
(1 PHASE)

KWH METER

R-PHASE
KW

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

2.50
2.50
2.50
2.50
2.50
1.00

2.40
2.40
2.40
2.40
2.40
1.00

2.40
2.40
2.40
2.40
2.40
1.00

7.30
7.30
7.30
7.30
7.30
3.00

13.50

13.00

13.00

39.50

TOTAL CONNECTED LOAD PER PHASE

1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

LV/HV
CT (4)

REMARKS

TOTAL

TOTAL CONNECTED LOAD (3PH) 39.50 KW

TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE:

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

H.H.SH. AHMED BIN SAIF AL NAHYAN

SMDB REF: SMDB - F1E

LOCATION: ELECT. ROOM


FIRST FLOOR
RATING-AMPS

SR.
No.

1
2
3
4
5
6

FAULT
DUTY
MCB
KA

CIRCUIT FEEDER DB
NO.

SP/
TP

INCOMER

TP

200
(N/A)

35

TP
TP
TP
TP
TP
TP

20
63
40
40
40
40

35
35
35
35
35
35

OUTGOING
SEF - 2
DB- F1E
DB - F2E
DB - F5E
DF - F10E
DF - F15E

ACB

MCCB

SMDB- F1E CONNECTED TO: MDB - E


DEMAND FACTOR

CONTRACTOR:

0.90

PVC/XLPE
SWA/PVC

CABLE SIZE
2/4 x 1C
mm2

2/3/4C
mm2

LENGTH
OF
CABLE
(mtrs)

ECC
SIZE-1C
mm2

FIREPROOF

4C 95

1C 50

FIRE PROOF

4C 4
4C 16
4C 10
4C 10
4C 10
4C 10

1C 4
1C 16
1C 10
1C 10
1C 10
1C 10

XLPE /SWA/PVC
XLPE /SWA/PVC
XLPE /SWA/PVC
XLPE /SWA/PVC
XLPE /SWA/PVC

MAX. DEMAND..
82.22 KW

(1) UP TO 60A
(1 PHASE)

KWH METER
1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

REMARKS

R-PHASE
KW

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

1.00
6.00
5.25
6.25
6.25
6.25

1.00
5.80
5.65
5.30
5.30
5.30

1.00
6.50
5.30
6.40
6.40
6.40

3.0
18.3
16.20
17.950
17.950
17.950

4P ELCB 100 mA

31.00

28.35

32.00

91.35

TOTAL

TOTAL CONNECTED LOAD PER PHASE

LV/HV
CT (4)

TOTAL CONNECTED LOAD (3PH) 91.35 KW

TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE:

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

H.H.SH. AHMED BIN SAIF AL NAHYAN

SMDB REF: SMDB - MDF-DU

LOCATION: MDF. ROOM

RATING-AMPS
SR.
No.

1
2
3
4
5
6
7

FAULT
DUTY
MCB
KA

PVC/XLPE

CABLE SIZE

LENGTH
OF
CABLE
(mtrs)

SP/
TP

INCOMER

TP

100
(N/A)

35

XLPE/SWA/PVC

4C 35

1C 16

TP
TP
TP
TP
TP
TP
TP

40
40
40
40
40
40
40

35
35
35
35
35
35
35

XLPE /SWA/PVC

4C 10
4C 10
4C 10
4C 10
4C 10
4C 10

1C 10
1C 10
1C 10
1C 10
1C 10
1C 10

OUTGOING
DB -UPS-1
UPS-1 BY DU
DB -UPS-2
UPS-2 BY DU
RECTIFIER BY DU
CCU
SPARE

ACB

MCCB

SMDB- RN CONNECTED TO: MDB - E


DEMAND FACTOR

CONTRACTOR:

0.90

SWA/PVC

2/4 x 1C
mm2

XLPE /SWA/PVC
XLPE /SWA/PVC
XLPE /SWA/PVC
XLPE /SWA/PVC
XLPE /SWA/PVC

2/3/4C
mm2

TOTAL CONNECTED LOAD PER PHASE

MAX. DEMAND..
33.30 KW

(1) UP TO 60A
(1 PHASE)

KWH METER

R-PHASE
KW

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

2.60
0.50
2.60
0.50
0.50
5.00
0.50

2.80
0.50
2.80
0.50
0.50
5.00
0.50

2.60
0.50
2.60
0.50
0.50
5.00
0.50

8.00
1.50
8.00
1.50
1.50
15.00
1.50

12.20

12.60

12.20

37.00

1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

REMARKS

LV/HV
CT (4)

AS PER DU REQUIREMENT
AS PER DU REQUIREMENT
AS PER DU REQUIREMENT

TOTAL

TOTAL CONNECTED LOAD (3PH) 37.00 KW

TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

ECC
SIZE-1C
mm2

CIRCUIT FEEDER DB
NO.

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE:

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

H.H.SH. AHMED BIN SAIF AL NAHYAN

SMDB REF: SMDB - B1E

LOCATION: LV. ROOM


RATING-AMPS

SR.
No.

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

FAULT
DUTY
MCB
KA

PVC/XLPE

CABLE SIZE

LENGTH
OF
CABLE
(mtrs)

SP/
TP

INCOMER

TP

400
(N/A)

35

FIRE PROOF

4C 300

1C 150

OUTGOING
SEWAGE LIFT PUMP
SUMP PUMP-1
SUMP PUMP-2
DB - B3E
WATER TRANSF. PUMP
BMAF - 1
BMAF - 2
BEF - 2
BEF - 1
DB - B1E
DB - UPS
DB - CKE
DB - CE
SMDB-MDF-DU
DUMP WAITER ELEVATOR

TP
TP
TP
TP
TP
TP
TP
TP
TP
TP
TP
TP
TP
TP
TP

20
20
20
40
100
20
20
32
32
40
63
63
40
100
32

35
35
35
35
35
35
35
35
35
35
35
35
35
35
35

XLPE /SWA/PVC

4C 4
4C 4
4C 4
4C 10
4C 35
4C 4
4C 4
4C 6
4C 6
4C 10
4C 25
4C 16
4C 10
4C 35
4C 6

1C 4
1C 4
1C 4
1C 10
1C 16
1C 4
1C 4
1C 6
1C 6
1C 10
1C 16
1C 16
1C 10
1C 16
1C 6

ACB

MCCB

SMDB- RN CONNECTED TO: MDB - E


DEMAND FACTOR
CONTRACTOR:

0.90

SWA/PVC

2/4 x 1C
mm2

XLPE /SWA/PVC
XLPE /SWA/PVC
XLPE /SWA/PVC
XLPE /SWA/PVC
FIRE PROOF
FIRE PROOF
FIRE PROOF
FIRE PROOF
XLPE /SWA/PVC
XLPE /SWA/PVC
XLPE /SWA/PVC
XLPE /SWA/PVC
XLPE /SWA/PVC
XLPE /SWA/PVC

2/3/4C
mm2

TOTAL CONNECTED LOAD PER PHASE

MAX. DEMAND..
173.39 KW

(1) UP TO 60A
(1 PHASE)

KWH METER
1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

REMARKS

R-PHASE
KW

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

1.00
0.50
0.50
4.25
10.00
1.50
1.50
3.00
3.00
4.65
10.40
7.10
4.15
12.20
1.00

1.00
0.50
0.50
4.25
10.00
1.50
1.50
3.00
3.00
5.10
9.20
7.40
3.40
12.60
1.00

1.00
0.50
0.50
3.90
10.00
1.50
1.50
3.00
3.00
3.85
10.40
6.90
4.70
12.20
1.00

3.00
1.50
1.50
12.40
30.00
4.50
4.50
9.00
9.00
13.60
30.00
21.40
12.25
37.00
3.00

4P ELCB 100 mA
ELS 100-300 mA+Shunt Trip
ELS 100-300 mA+Shunt Trip

64.75

63.95

63.95

192.65

TOTAL

LV/HV
CT (4)

ELS 100-300 mA+Shunt Trip


4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA

4P ELCB 300 mA

TOTAL CONNECTED LOAD (3PH) 192.65 KW


TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

ECC
SIZE-1C
mm2

CIRCUIT FEEDER DB NO.

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE:

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

H.H.SH. AHMED BIN SAIF AL NAHYAN

SMDB REF: SMDB - RN

LOCATION: ELECT. ROOM


ROOF FLOOR
RATING-AMPS

SR.
No.

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

CIRCUIT FEEDER DB
NO.

SP/
TP

INCOMER

TP

OUTGOING
LIFT - 2
LIFT - 2 CONTROL
LIFT - 3
LIFT - 3 CONTROL
LIFT - 4
LIFT - 4 CONTROL
LIFT - 5
LIFT - 5 CONTROL
LIFT - 6
LIFT - 6 CONTROL
SERVICE LIFT - 1

TP
SP
TP
SP
TP
SP
TP
SP
TP
SP
TP
SERVICE LIFT - 1 CONTROL SP
SERVICE LIFT - 2
TP
SERVICE LIFT - 2 CONTROL SP
EXHAUST FAN-1
SP
EXHAUST FAN -2
SP
FAHU - 2
TP
FAADE LIGHT
TP

ACB

MCCB
800
(N/A)
100
20
100
20
100
20
100
20
100
20
100
20
100
20
20
20
200
63

FAULT
DUTY
MCB
KA

CONTRACTOR:

0.90

SWA/PVC

CABLE SIZE
2/4 x 1C
mm2

2/3/4C
mm2

LENGTH
OF
CABLE
(mtrs)

XLPE/SWA/PVC

2x4C.300

2x1C.150

35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35

XLPE/SWA/PVC

4C 70
2C 4
4C 70
2C 4
4C 70
2C 4
4C 70
2C 4
4C 70
2C 4
4C 35
2C 4
4C 35
2C 4
2C 4
2C 4
4C 95
-

1C 35
1C 4
1C 35
1C 4
1C 35
1C 4
1C 35
1C 4
1C 35
1C 4
1C 16
1C 4
1C 16
1C 4
1C 4
1C 4
1C 50

XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC

TOTAL CONNECTED LOAD PER PHASE

MAX. DEMAND..
305.10 KW

(1) UP TO 60A
(1 PHASE)

(2) UP TO 100A

B-PHASE
KW

TOTAL
KW

12.00
1.00
12.00
12.00
12.00
1.00
12.00
9.0
9.0
1.0
24.0
8.0

12.00
12.00
1.0
12.00
12.00
12.00
1.0
9.0
9.0
1.00
24.0
8.0

12.00
12.00
12.00
1.00
12.00
12.00
9.0
1.0
9.0
1.00
24.0
8.0

36.00
1.0
36.00
1.0
36.00
1.0
36.00
1.0
36.00
1.0
27.0
1.0
27.0
1.0
1.0
1.0
72.0
24.0

4P ELCB 300 mA
DP ELCB 100 mA
4P ELCB 300 mA
DP ELCB 100 mA
4P ELCB 300 mA
DP ELCB 100 mA
4P ELCB 300 mA
DP ELCB 100 mA
4P ELCB 300 mA
DP ELCB 100 mA
4P ELCB 300 mA
DP ELCB 100 mA
4P ELCB 300 mA
DP ELCB 100 mA
DP ELCB 100 mA
DP ELCB 100 mA
ELS 100-1000 mA+Shunt Trip

113.00

113.00

113.00

339.00

TOTAL

(3 PHASE)

(4) LV CT

1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

REMARKS

Y-PHASE
KW

TEL No. 04 885 1700


(3) 125-160A

KWH METER

R-PHASE
KW

TOTAL CONNECTED LOAD (3PH) 339.00 KW

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

ECC
SIZE-1C
mm2

35

SMDB- RN CONNECTED TO: BUSBAR # 4


DEMAND FACTOR

PVC/XLPE

LV/HV
CT (4)

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE:

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

H.H.SH. AHMED BIN SAIF AL NAHYAN

SMDB REF: SMDB - PBK

LOCATION: MECHANICAL ROOM


35TH FLOOR
RATING-AMPS

SR.
No.

1
2
3
4
5
6

FAULT
DUTY
MCB
KA

PVC/XLPE

CABLE SIZE

LENGTH
OF
CABLE
(mtrs)

ECC
SIZE-1C
mm2

CIRCUIT FEEDER DB
NO.

SP/
TP

INCOMER

TP

160
(N/A)

35

XLPE/SWA/PVC

4C 70

1C 35

TP
TP
TP
TP
TP
TP

40
32
32
32
63
63

35
35
35
35
35
35

XLPE/SWA/PVC

4C 10
4C 6
4C 6
4C 6
4C 16
4C 16

1C 10
1C 6
1C 6
1C 6
1C 16
1C 16

OUTGOING
HOTPLATE OVEN -11
SALAMANDER -10
FRY TOP -9
FRYER -8
AHU-K6
DB - PBK

ACB

MCCB

SMDB- PBK CONNECTED TO: SMDB -35N


DEMAND FACTOR

CONTRACTOR:

0.90

SWA/PVC

XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC

2/4 x 1C
mm2

2/3/4C
mm2

MAX. DEMAND..
62.01 KW

(1) UP TO 60A
(1 PHASE)

KWH METER
1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

REMARKS

R-PHASE
KW

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

4.00
2.00
2.00
2.00
5.00
7.50

4.00
2.00
2.00
2.00
5.00
8.40

4.00
2.00
2.00
2.00
5.00
8.00

12.00
6.00
6.00
6.00
15.00
23.90

4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA

22.50

23.40

23.00

68.90

TOTAL

TOTAL CONNECTED LOAD PER PHASE

LV/HV
CT (4)

TOTAL CONNECTED LOAD (3PH) 68.90 KW

TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE:

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

H.H.SH. AHMED BIN SAIF AL NAHYAN

SMDB REF: SMDB - F35N

LOCATION: MECHANICAL ROOM


35TH FLOOR
RATING-AMPS

SR.
No.

1
2
3
4
5
6
7

FAULT
DUTY
MCB
KA

PVC/XLPE

CABLE SIZE

LENGTH
OF
CABLE
(mtrs)

ECC
SIZE-1C
mm2

CIRCUIT FEEDER DB
NO.

SP/
TP

INCOMER

TP

250
(N/A)

35

XLPE/SWA/PVC

4C 150

1C 70

TP
TP
TP
TP
TP
TP
TP

63
20
32
20
20
32
160

35
35
35
35
35
35
35

XLPE/SWA/PVC

4C 16
4C 4
4C 6
4C 4
4C 4
4C 6
4C 70

1C 16
1C 4
1C 6
1C 4
1C 4
1C 6
1C 35

OUTGOING
DB - RN
HOTWATER - RE
FILTERED WATER
COLD WATER
BOILER RE.
SOFT WATER
SMDB - PBK

ACB

MCCB

SMDB- F35N CONNECTED TO: BUSBAR # 4


DEMAND FACTOR

CONTRACTOR:

0.90

SWA/PVC

XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC

2/4 x 1C
mm2

2/3/4C
mm2

MAX. DEMAND..
109.13 KW

(1) UP TO 60A
(1 PHASE)

KWH METER
1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

REMARKS

R-PHASE
KW

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

7.15
1.50
3.00
2.00
0.50
3.00
22.50

7.05
1.50
3.00
2.00
0.50
3.00
23.40

8.15
1.50
3.00
2.00
0.50
3.00
23.00

22.35
4.50
9.00
6.00
1.50
9.00
68.90

4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA

39.65

40.45

41.15

121.25

TOTAL

TOTAL CONNECTED LOAD PER PHASE

LV/HV
CT (4)

TOTAL CONNECTED LOAD (3PH)121.25 KW

TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE: MAY 2010

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

H.H.SH. AHMED BIN SAIF AL NAHYAN

SMDB REF: SMDB - F34N

LOCATION: ELECT. ROOM


34TH FLOOR
RATING-AMPS

SR.
No.

1
2
3
4
5
6
7
8
9

FAULT
DUTY
MCB
KA

PVC/XLPE

CABLE SIZE

LENGTH
OF
CABLE
(mtrs)

ECC
SIZE-1C
mm2

CIRCUIT FEEDER DB
NO.

SP/
TP

INCOMER

TP

300
(N/A)

35

XLPE/SWA/PVC

4C 185

1C 95

OUTGOING
DB - F34N1
DB - F34N2
SWIMMING POOL
SAUNA (F)
STEAM (F)
STEAM (M)
SAUNA (M)
SPARE
SPARE

TP
TP
TP
TP
TP
TP
TP
TP
TP

63
40
250
40
40
40
40
20
20

35
35
35
35
35
35
35
35
35

XLPE/SWA/PVC

4C 16
4C 10
4C 150
4C 10
4C 10
4C 10
4C 10

1C 16
1C 10
1C 70
1C 10
1C 10
1C 10
1C 10

ACB

MCCB

SMDB- F34N CONNECTED TO: BUSBAR # 4


DEMAND FACTOR

CONTRACTOR:

0.90

SWA/PVC

XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC

2/4 x 1C
mm2

2/3/4C
mm2

MAX. DEMAND..
149.18 KW

(1) UP TO 60A
(1 PHASE)

B-PHASE
KW

TOTAL
KW

12.00
4.25
23.00
3.00
3.00
3.00
3.00
2.00
2.00

12.30
3.25
23.00
3.00
3.00
3.00
3.00
2.00
2.00

13.00
3.95
23.00
3.00
3.00
3.00
3.00
2.00
2.00

37.30
11.45
69.00
9.00
9.00
9.00
9.00
6.00
6.00

4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA

55.25

54.55

55.95

165.75

TOTAL

TEL No. 04 885 1700


(3) 125-160A
(3 PHASE)

(4) LV CT

1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

REMARKS

Y-PHASE
KW

TOTAL CONNECTED LOAD (3PH)165.75 KW

(2) UP TO 100A

KWH METER

R-PHASE
KW

TOTAL CONNECTED LOAD PER PHASE

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

LV/HV
CT (4)

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE:

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

H.H.SH. AHMED BIN SAIF AL NAHYAN

SMDB REF: SMDB - T2

LOCATION: ELECT. ROOM


31ST - 33RD FLOORS
RATING-AMPS

SR.
No.

1
2
3
4

FAULT
DUTY
MCB
KA

PVC/XLPE

CIRCUIT FEEDER DB
NO.

SP/
TP

INCOMER

TP

250
(N/A)

35

XLPE/SWA/PVC

TP
TP
TP
TP

63
63
63
63

35
35
35
35

PVC / SC
PVC / SC
PVC / SC
PVC / SC

OUTGOING
DB - T2 - 1
DB - T2 - 2
DB - T2 - 3
DB - T2 - 4

ACB

MCCB

SMDB- T2 CONNECTED TO: BUSBAR # 4


DEMAND FACTOR

CONTRACTOR:

0.90

SWA/PVC

CABLE SIZE
2/4 x 1C
mm2

2/3/4C
mm2

LENGTH
OF
CABLE
(mtrs)

4C 150

4X1C 25
4X1C 25
4X1C 25
4X1C 25

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

1C 70

37.6

34

33.8

105.40

1C 16
1C 16
1C 16
1C 16

9.40
9.40
9.40
9.40

8.50
8.50
8.50
8.50

8.45
8.45
8.45
8.45

26.35
26.35
26.35
26.35

37.60

34.00

33.80

105.40

TOTAL CONNECTED LOAD PER PHASE

MAX. DEMAND..
94.86 KW

(1) UP TO 60A
(1 PHASE)

KWH METER

R-PHASE
KW

1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

LV/HV
CT (4)

REMARKS

TOTAL

TOTAL CONNECTED LOAD (3PH)105.40 KW

TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

ECC
SIZE-1C
mm2

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE:

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

H.H.SH. AHMED BIN SAIF AL NAHYAN

SMDB REF: SMDB - F21 / F22

LOCATION: ELECT. ROOM


21ST & 22ND FLOORS
RATING-AMPS

SR.
No.

1
2
3
4
5

FAULT
DUTY
MCB
KA

PVC/XLPE

CIRCUIT FEEDER DB
NO.

SP/
TP

INCOMER

TP

225
(N/A)

35

XLPE/SWA/PVC

TP
TP
TP
TP
TP

63
63
63
40
63

35
35
35
35
35

PVC / SC
PVC / SC
PVC / SC
PVC / SC
PVC / SC

OUTGOING
DB - (21 / 22) - 1
DB - (21 / 22) - 3
DB - (21 / 22) - 4
DB - (21 / 22) - 5
DB - (21 / 22) - 6

ACB

MCCB

SMDB- F1 / F22 CONNECTED TO: BUSBAR # 3


DEMAND FACTOR

CONTRACTOR:

0.90

SWA/PVC

CABLE SIZE
2/4 x 1C
mm2

2/3/4C
mm2

LENGTH
OF
CABLE
(mtrs)

4C 120

4X1C 25
4X1C 25
4X1C 25
4X1C 16
4X1C 25

ECC
SIZE-1C
mm2

R-PHASE
KW

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

8.85
8.85
8.85
4.90
8.85

8.00
8.00
8.00
5.60
8.00

7.90
7.90
7.90
4.70
7.90

24.75
24.75
24.75
15.20
24.75

40.30

37.60

36.30

114.20

1C 16
1C 16
1C 16
1C 16
1C 16

TOTAL CONNECTED LOAD PER PHASE

MAX. DEMAND..
102.78 KW

(1) UP TO 60A
(1 PHASE)

KWH METER
1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

LV/HV
CT (4)

REMARKS

1C 70

TOTAL

TOTAL CONNECTED LOAD (3PH)114.20 KW

TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE: MAY 2010

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

H.H.SH. AHMED BIN SAIF AL NAHYAN

SMDB REF: SMDB - T1

LOCATION: ELECT. ROOM


20TH, 23RD-30TH FLOORS
RATING-AMPS

SR.
No.

1
2
3
4
5
6

FAULT
DUTY
MCB
KA

PVC/XLPE

CIRCUIT FEEDER DB
NO.

SP/
TP

INCOMER

TP

300
(N/A)

35

XLPE/SWA/PVC

TP
TP
TP
TP
TP
TP

63
40
63
63
40
63

35
35
35
35
35
35

PVC / SC
PVC / SC
PVC / SC
PVC / SC
PVC / SC
PVC / SC

OUTGOING
DB - T1 -1
DB - T1 -2
DB - T1 -3
DB - T1 -4
DB - T1 -5
DB - T1 -6

ACB

MCCB

SMDB- T1 CONNECTED TO: BUSBAR # 3 / 4


DEMAND FACTOR

CONTRACTOR:

0.90

SWA/PVC

CABLE SIZE
2/4 x 1C
mm2

2/3/4C
mm2

LENGTH
OF
CABLE
(mtrs)

4C 185

4X1C 25
4X1C 16
4X1C 25
4X1C 25
4X1C 16
4X1C 25

ECC
SIZE-1C
mm2

R-PHASE
KW

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

8.85
4.90
8.85
8.85
4.90
8.85

8.00
5.60
8.00
8.00
5.60
8.00

7.90
4.70
7.90
7.90
4.70
7.90

24.75
15.20
24.75
24.75
15.20
24.75

45.20

43.20

41.00

129.40

1C 16
1C 16
1C 16
1C 16
1C 16
1C 16

TOTAL CONNECTED LOAD PER PHASE

MAX. DEMAND..
116.46 KW

(1) UP TO 60A
(1 PHASE)

KWH METER
1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

LV/HV
CT (4)

REMARKS

1C 95

TOTAL

TOTAL CONNECTED LOAD (3PH)129.40 KW

TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE:

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

H.H.SH. AHMED BIN SAIF AL NAHYAN

SMDB REF: SMDB - F20N

LOCATION: ELECT. ROOM


20TH FLOOR
RATING-AMPS

SR.
No.

1
2
3
4
5
6
7
8
9

FAULT
DUTY
KA

PVC/XLPE

CABLE SIZE

LENGTH
OF
CABLE
(mtrs)

ECC
SIZE-1C
mm2

CIRCUIT FEEDER
DB NO.

SP/ TP

INCOMER

TP

400
(N/A)

35

XLPE/SWA/PVC

4C 300

1C 150

TP
TP
TP
TP
TP
TP
TP
TP
TP

20
125
63
63
63
63
63
20
20

35
35
35
35
35
35
35
35
35

XLPE/SWA/PVC

4C 4
4C 50
4C 16
4C 16
4C 16
4C 16
4C 16

1C 4
1C 25
1C 16
1C 16
1C 16
1C 16
1C 16

OUTGOING
GSM EQUIPMENT
FAHU - 1
DB - F20N
DB - F23N
DB - F26N
DB - F29N
DB - F32N
SPARE
SPARE

ACB

MCCB

MCB

SMDB- F20N CONNECTED TO: BUSBAR # 3


DEMAND FACTOR0.90

CONTRACTOR:

SWA/PVC

XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC

2/4 x 1C
mm2

2/3/4C
mm2

MAX. DEMAND..
157.50 KW

(1) UP TO 60A
(1 PHASE)

KWH METER

R-PHASE
KW

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

1.00
22.00
6.40
6.40
6.40
6.40
6.40
1.00
1.00

1.00
22.00
7.10
7.10
7.10
7.10
7.10
1.00
1.00

1.00
22.00
6.50
6.50
6.50
6.50
6.50
1.00
1.00

3.00
66.00
20.00
20.00
20.00
20.00
20.00
3.00
3.00

57.00

60.50

57.50

175.00

TOTAL CONNECTED LOAD PER PHASE

1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

REMARKS

LV/HV
CT (4)

4P ELCB 100 mA
ELS 100-1000 mA+Shunt Trip

TOTAL

TOTAL CONNECTED LOAD (3PH) 175.00 KW

TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE: MAY 2010

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

SMDB REF: SMDB -F5- F19

CONSULTANT:

RATING-AMPS
SR.
No.

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

FAULT
DUTY
MCB
KA

PVC/XLPE

CIRCUIT FEEDER DB
NO.

SP/
TP

INCOMER

TP

200
(N/A)

35

XLPE/SWA/PVC

SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP

40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25

PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC

OUTGOING
DB - GR1
DB - GR2
DB - GR3
DB - GR4
DB - GR5
DB - GR6
DB - GR7
DB - GR8
DB - GR9
DB - GR10
DB - GR11
DB - GR12
DB - GR13
DB - GR14
DB - GR15
DB - GR16
DB - GR17
DB - GR18

ACB

MCCB

SMDB- F5 - F19 CONNECTED TO: BUSBAR # 1 / 2


DEMAND FACTOR

CONTRACTOR:

0.90

SWA/PVC

H.H.SH. AHMED BIN SAIF AL NAHYAN


M/S. IAN BANHAN & ASSOCIATES

CABLE SIZE
2/4 x 1C
mm2

2/3/4C
mm2

LENGTH
OF
CABLE
(mtrs)

4C 95

2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16

ECC
SIZE-1C
mm2

(1) UP TO 60A
(1 PHASE)

KWH METER

R-PHASE
KW

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

4.80
4.80
4.80
4.80
4.80
4.80
-

4.80
4.80
4.80
4.80
4.80
4.80
-

4.80
4.80
4.80
4.80
4.80
4.80

4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80

28.80

28.80

28.80

86.40

1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

LV/HV
CT (4)

REMARKS

1C 50

1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16

TOTAL

TOTAL CONNECTED LOAD (3PH) 86.40 KW

TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

TOTAL CONNECTED LOAD PER PHASE

MAX. DEMAND..
77.76 KW

LOCATION: ELECT. ROOM


5TH - 19TH FLOOR

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE:

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

H.H.SH. AHMED BIN SAIF AL NAHYAN

SMDB REF: SMDB -F16

LOCATION: ELECT. ROOM


16TH FLOOR
RATING-AMPS

SR.
No.

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

FAULT
DUTY
KA

PVC/XLPE

CIRCUIT FEEDER DB
NO.

SP/ TP

INCOMER

TP

250
(N/A)

35

XLPE/SWA/PVC

SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
TP
TP
TP

40
40
40
40
40
40
40
40
40
40
40
40
40
63
40
40

25
25
25
25
25
25
25
25
25
25
25
25
25
35
35
35

PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC

OUTGOING
DB - GR1
DB - GR2
DB - GR3
DB - GR4
DB - GR5
DB - GR6
DB - GR7
DB - GR8
DB - GR9
DB - GR10
DB - GR11
DB - GR12
DB - GR13
DB - F16K
DB - F16N
AUTOMATIC COFFEE M/C -9

ACB

MCCB

MCB

SMDB- F16 - CONNECTED TO: BUSBAR # 2


DEMAND FACTOR

CONTRACTOR:

0.90

SWA/PVC

CABLE SIZE
2/4 x 1C
mm2

2/3/4C
mm2

LENGTH
OF
CABLE
(mtrs)

4C 150

1C 70

4C 16
4C 10
4C 10

1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 10
1C 10

2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16

XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC

ECC
SIZE-1C
mm2

MAX. DEMAND..
108.36 KW

(1) UP TO 60A
(1 PHASE)

KWH METER
1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

REMARKS

R-PHASE
KW

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

4.80
4.80
4.80
4.80
4.80
8.20
6.20
4.60

4.80
4.80
4.80
4.80
8.20
6.10
4.70

4.80
4.80
4.80
4.80
9.10
6.20
4.70

4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
25.50
18.50
14.00

4P ELCB 100 mA

43.00

38.20

39.20

120.40

TOTAL

TOTAL CONNECTED LOAD PER PHASE

LV/HV
CT (4)

TOTAL CONNECTED LOAD (3PH)120.40 KW

TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE:

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

H.H.SH. AHMED BIN SAIF AL NAHYAN

SMDB REF: SMDB -F4

LOCATION: ELECT. ROOM


4TH FLOOR
RATING-AMPS

SR.
No.

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

FAULT
DUTY
MCB
KA

PVC/XLPE

CIRCUIT FEEDER DB
NO.

SP/
TP

INCOMER

TP

225
(N/A)

35

XLPE/SWA/PVC

SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
TP
TP

40
40
40
40
40
40
40
40
40
40
40
40
40
63
40

25
25
25
25
25
25
25
25
25
25
25
25
25
35
35

PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC
PVC/ SC

OUTGOING
DB - GR1
DB - GR2
DB - GR3
DB - GR4
DB - GR5
DB - GR6
DB - GR7
DB - GR8
DB - GR9
DB - GR10
DB - GR11
DB - GR12
DB - GR13
DB - F4K
DISHWASHER -26

ACB

MCCB

SMDB- F4 - CONNECTED TO: BUSBAR # 1


DEMAND FACTOR

CONTRACTOR:

0.90

SWA/PVC

XLPE/SWA/PVC
XLPE/SWA/PVC

CABLE SIZE
2/4 x 1C
mm2

2/3/4C
mm2

LENGTH
OF
CABLE
(mtrs)

ECC
SIZE-1C
mm2

4C 120

1C 70

4C 16
4C 10

1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 16
1C 10

2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16
2X1C 16

MAX. DEMAND..
89.10 KW

(1) UP TO 60A
(1 PHASE)

KWH METER
1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

REMARKS

R-PHASE
KW

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

4.80
4.80
4.80
4.80
4.80
9.1
3.1

4.80
4.80
4.80
4.80
9.1
3.10

4.80
4.80
4.80
4.80
9.0
3.20

4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
4.80
27.2
9.4

4P ELCB 100 mA

36.20

31.40

31.40

99.00

TOTAL

TOTAL CONNECTED LOAD PER PHASE

LV/HV
CT (4)

TOTAL CONNECTED LOAD (3PH) 99.00 KW

TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE:

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

H.H.SH. AHMED BIN SAIF AL NAHYAN

SMDB REF: SMDB - F3N

LOCATION: ELECT. ROOM


3RD FLOOR
RATING-AMPS

SR.
No.

1
2
3
4
6
8
10
12
13
14
15
16
17
18
19

FAULT
DUTY
KA

PVC/XLPE

CABLE SIZE

LENGTH
OF
CABLE
(mtrs)

ECC
SIZE-1C
mm2

CIRCUIT FEEDER DB
NO.

SP/
TP

INCOMER

TP

630
(N/A)

35

XLPE/SWA/PVC

2X4C 185

2 X 1C95

TP
TP
TP
TP
TP
TP
TP
TP
TP
SP
TP
TP
TP
TP
TP

63
63
20
63
40
63
63
40
63
20
63
63
63
32
20

35
35
35
35
35
35
35
35
35
35
35
35
35
35
35

XLPE/SWA/PVC

4C 16
4C 16
4C 4
4C 16
4C 10
4C 16
4C 16
4C 10
4C 16
2C 4
4C 16
4C 16
4C 16

1C 16
1C 16
1C 4
1C 16
1C 10
1C 16
1C 16
1C 10
1C 16
1C 4
1C 16
1C 16
1C 16

OUTGOING
DB - F3N1
DB - F3N2
LAUNDRY
AHU - 5
AHU - 6
AHU - 7
AHU - 8
DB - F4N
SERVICE LIFT-3
SERVICE LIFT CONTROL-3

DB - F5N
DB - F10N
DB - F15N
SPARE
SPARE

ACB

MCCB

MCB

SMDB- F3N CONNECTED TO: MDB - 2


DEMAND FACTOR

CONTRACTOR:

0.90

SWA/PVC

2/4 x 1C
mm2

2/3/4C
mm2

XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC

MAX. DEMAND..
240.93 KW

(1) UP TO 60A
(1 PHASE)

KWH METER

R-PHASE
KW

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

7.40
9.15
1.50
10.00
5.00
10.00
9.00
4.05
5.00
0.50
7.80
7.80
7.80
3.00
1.00

7.80
10.20
1.50
10.00
5.00
10.00
9.00
4.95
5.00
7.30
7.30
7.30
3.00
1.00

7.15
9.30
1.50
10.00
5.00
10.00
9.00
4.40
5.00
8.00
8.00
8.00
3.00
1.00

22.35
28.65
4.50
30.00
15.00
30.00
27.00
13.40
15.00
0.50
23.10
23.10
23.10
9.00
3.00

89.00

89.35

89.35

267.70

TOTAL CONNECTED LOAD PER PHASE

1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

LV/HV
CT (4)

REMARKS

4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 300 mA
DP ELCB 100 mA

4P ELCB 100 mA

TOTAL

TOTAL CONNECTED LOAD (3PH)267.70 KW

TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE:

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

H.H.SH. AHMED BIN SAIF AL NAHYAN

SMDB REF: SMDB - F2N

LOCATION: ELECT. ROOM


2ND FLOOR
RATING-AMPS

SR.
No.

1
2
3
4
5
6

FAULT
DUTY
MCB
KA

PVC/XLPE

CABLE SIZE

LENGTH
OF
CABLE
(mtrs)

ECC
SIZE-1C
mm2

CIRCUIT FEEDER DB
NO.

SP/
TP

INCOMER

TP

200
(N/A)

35

XLPE/SWA/PVC

4C 120

1C 50

TP
TP
TP
TP
TP
TP

63
40
63
32
32
32

35
35
35
35
35
35

XLPE/SWA/PVC

4C 16
4C 10
4C 16

1C 16
1C 10
1C 16

OUTGOING
DB - F2N1
DB - F2N2
DB - F2N3
SPARE
SPARE
SPARE

ACB

MCCB

SMDB- F2N CONNECTED TO: MDB - 2


DEMAND FACTOR

CONTRACTOR:

0.90

SWA/PVC

XLPE/SWA/PVC
XLPE/SWA/PVC

2/4 x 1C
mm2

2/3/4C
mm2

MAX. DEMAND..
80.37 KW

(1) UP TO 60A
(1 PHASE)

KWH METER
1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

REMARKS

R-PHASE
KW

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

9.50
4.45
7.30
2.87
3.00
3.00

8.90
4.35
7.30
2.86
3.00
3.00

8.70
3.90
8.30
2.87
3.00
3.00

27.10
12.70
22.90
8.60
9.00
9.00

4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA

30.12

29.41

29.77

89.30

TOTAL

TOTAL CONNECTED LOAD PER PHASE

LV/HV
CT (4)

TOTAL CONNECTED LOAD (3PH) 89.30 KW

TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE: MAY 2010

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

SMDB REF: SMDB - F1K

CONSULTANT:

RATING-AMPS
SR.
No.

1
2
3
4
5
6
7
8
9
10
11
12
13

FAULT
DUTY
MCB
KA

PVC/XLPE

H.H.SH. AHMED BIN SAIF AL NAHYAN


M/S. IAN BANHAN & ASSOCIATES

CABLE SIZE

LENGTH
OF
CABLE
(mtrs)

ECC
SIZE-1C
mm2

CIRCUIT FEEDER DB NO.

SP/
TP

INCOMER

TP

400
(N/A)

35

XLPE/SWA/PVC

4C 300

1C 150

TP
TP

63
63

35
35

XLPE/SWA/PVC

4C 16
4C 16

TP
TP
SPARE
TP
ELECT CONVECTION OVEN -119
TP
ELECT INDUCTION COOK TOP -122 TP
ELECT INDUCTION COOK TOP -122 TP
ELECT TOP -123
TP
FABRICATED HOTPLATE RACE
TP
COMBI - OVEN
TP
SALAMNDER
TP
BLAST CHILLER
TP

80
32
20
80
32
32
32
32
63
32
32

35
35
35
35
35
35
35
35
35
35
35

XLPE/SWA/PVC

OUTGOING
DB - F1K
DB - F1K1
CONVEYOR DISHWASHER 68

ELECT INDUCTION UNIT - 76

ACB

MCCB

SMDB- F1K CONNECTED TO: SMDB - F1N


DEMAND FACTOR

CONTRACTOR:

0.90

SWA/PVC

2/4 x 1C
mm2

XLPE/SWA/PVC

XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC

2/3/4C
mm2

(1) UP TO 60A
(1 PHASE)

KWH METER
1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

REMARKS

R-PHASE
KW

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

1C 16
1C 16

8.27
9.90

8.97
9.90

9.17
8.90

26.40
28.70

4C 25
4C 6

1C 16
1C 6

4C 25
4C 6
4C 6
4C 6
4C 6
4C 16
4C 6
4C 6

1C 16
1C 6
1C 6
1C 6
1C 6
1C 16
1C 6
1C 6

11.70
3.10
1.40
11.70
2.30
2.30
3.00
2.00
6.00
2.00
3.00

11.70
3.20
1.30
11.70
2.30
2.40
3.00
2.00
6.00
2.00
3.00

11.60
3.20
1.30
11.60
2.40
2.30
3.00
2.00
7.00
2.00
3.00

35.00
9.50
4.00
35.00
7.00
7.00
9.00
6.00
19.00
6.00
9.00

4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA

66.67

67.47

67.47

201.60

TOTAL

LV/HV
CT (4)

TOTAL CONNECTED LOAD (3PH)201.60 KW

TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

TOTAL CONNECTED LOAD PER PHASE

MAX. DEMAND..
181.44 KW

LOCATION: ELECT. CABINET


1ST FLOOR

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE:

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

H.H.SH. AHMED BIN SAIF AL NAHYAN

SMDB REF: SMDB - F1N

LOCATION: ELECT. ROOM


1ST FLOOR
RATING-AMPS

SR.
No.

1
2
3
4
8
6

FAULT
DUTY
MCB
KA

PVC/XLPE

CABLE SIZE

LENGTH
OF
CABLE
(mtrs)

ECC
SIZE-1C
mm2

CIRCUIT FEEDER DB
NO.

SP/
TP

INCOMER

TP

630
(N/A)

35

XLPE/SWA/PVC

2X 4C 185

2X 1C 95

TP
TP
TP
TP
TP
TP

63
40
400
40
20
20

35
35
35
35
35
35

XLPE/SWA/PVC

4C 16
4C 10
4C 300
4C 10
4C 4

1C 16
1C 10
1C 150
1C 10
1C 4

OUTGOING
DB - F1N1
DB - F1N2
SMDB - F1K
AHU - 4
AHU - K5
SPARE

ACB

MCCB

SMDB- F1N CONNECTED TO: MDB - 1


DEMAND FACTOR

CONTRACTOR:

0.90

SWA/PVC

XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC

2/4 x 1C
mm2

2/3/4C
mm2

MAX. DEMAND..
220.24 KW

(1) UP TO 60A
(1 PHASE)

KWH METER

R-PHASE
KW

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

4.90
4.50
66.67
3.00
1.00
1.00

5.30
3.90
67.47
3.00
1.00
1.00

4.95
4.55
67.47
3.00
1.00
1.00

15.15
12.95
205.00
9.00
3.00
3.00

81.07

81.67

81.97

244.71

TOTAL CONNECTED LOAD PER PHASE

1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

LV/HV
CT (4)

REMARKS

4P ELCB 100 mA

TOTAL

TOTAL CONNECTED LOAD (3PH)244.71 KW

TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE:

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

H.H.SH. AHMED BIN SAIF AL NAHYAN

SMDB REF: SMDB - CK

LOCATION: ELECT. CABINET


CONCOURSE LEVEL
RATING-AMPS

SR.
No.

1
2
3
4
5
6
7
8
9
10
11
12

FAULT
DUTY
MCB
KA

PVC/XLPE

CABLE SIZE

LENGTH
OF
CABLE
(mtrs)

ECC
SIZE-1C
mm2

CIRCUIT FEEDER DB
NO.

SP/ TP

INCOMER

TP

350
(N/A)

35

XLPE/SWA/PVC

4C 240

1C120

TP
TP
TP
TP
TP
TP
TP
TP
TP
TP
TP
TP

80
40
40
32
25
32
32
25
63
20
20
63

35
35
35
35
35
35
35
35
35
35
35
35

XLPE/SWA/PVC

XLPE/SWA/PVC

4C 25
4C 10
4C 10
4C 6
4C 6
4C 6
4C 6
4C 6
4C 16

1C 16
1C 10
1C 10
1C 6
1C 6
1C 6
1C 6
1C 6
1C 16

XLPE/SWA/PVC

4C 16

1C 16

OUTGOING
DB - CK
DB - CK1
DISHWASHER -145
FRYERTOP -67
HOTPLATE -70
BAKERY OVEN -71
COMBI OVEN -131
HEATER PLATE -125
PASTA COOKER -126
SPARE
SPARE
DECK OVEN

ACB

MCCB

SMDB- CN CONNECTED TO: MDB - 1


DEMAND FACTOR

CONTRACTOR:

0.90

SWA/PVC

XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC

2/4 x 1C
mm2

2/3/4C
mm2

MAX. DEMAND..
134.91 KW

(1) UP TO 60A
(1 PHASE)

KWH METER

R-PHASE
KW

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

7.90
5.70
4.10
2.00
1.40
3.00
3.10
1.30
6.70
2.00
2.00
10.00

11.60
5.60
4.20
2.00
1.30
3.00
3.10
1.40
6.60
2.00
2.00
9.00

7.60
5.80
4.20
2.00
1.30
3.00
4.00
1.30
6.70
2.00
2.00
9.00

27.10
17.10
12.50
6.00
4.00
9.00
10.20
4.00
20.00
6.00
6.00
28.00

49.20

51.80

48.90

149.90

TOTAL CONNECTED LOAD PER PHASE

1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

LV/HV
CT (4)

REMARKS

4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA

4P ELCB 100 mA

TOTAL

TOTAL CONNECTED LOAD (3PH)149.90 KW

TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE: MAY 2010

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

SMDB REF: SMDB - CN

CONSULTANT:

RATING-AMPS
SR. CIRCUIT FEEDER DB
SP/ TP
No.
NO.

INCOMER

1
2
3
3
4
5
6
7
8

OUTGOING
DB - C1N
DB - C2N
DB - C3N
DB - C4N
SMDB - CK
AHU - 2
AHU - 3
AHU - K2
AHU - K4

ACB

MCCB

MCB

FAULT
DUTY
KA

SWA/PVC

M/S. IAN BANHAN & ASSOCIATES

CABLE SIZE
2/4 x 1C
mm2

2/3/4C
mm2

LENGTH
OF
CABLE
(mtrs)

ECC
SIZE-1C
mm2

TP

630
(N/A)

35

XLPE/SWA/PVC

2X4C 185

2X 1C95

TP
TP
TP
TP
TP
TP
TP
TP
TP

40
40
40
63
350
63
63
63
20

35
35
35
35
35
35
35
35
35

XLPE/SWA/PVC

4C 10
4C 10
4C 16
4C 16
4C 240
4C 16
4C 16
4C 16
4C 4

1C 10
1C 10
1C 16
1C 16
1C 120
1C 16
1C 16
1C 16
1C 4

SMDB- CN CONNECTED TO: MDB - 1


DEMAND FACTOR 0.90

CONTRACTOR:

PVC/XLPE

H.H.SH. AHMED BIN SAIF AL NAHYAN

XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC

(1) UP TO 60A
(1 PHASE)

KWH METER

R-PHASE
KW

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

3.40
2.60
7.70
7.50
49.20
8.00
8.00
7.00
1.00

2.65
2.75
6.55
6.85
51.80
8.00
8.00
7.00
1.00

2.80
3.05
6.15
7.50
48.90
8.00
8.00
7.00
1.00

8.85
8.40
20.40
21.85
149.90
24.00
24.00
21.00
3.00

94.40

94.60

92.40

281.40

1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

LV/HV
CT (4)

REMARKS

4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA

TOTAL

TOTAL CONNECTED LOAD (3PH)281.40 KW

TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

TOTAL CONNECTED LOAD PER PHASE

MAX. DEMAND..253.26 KW

LOCATION: ELECT. ROOM


CONCOURSE LEVEL

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE: MAY 2010

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

SMDB REF: SMDB - B1WB

CONSULTANT:

RATING-AMPS
SR.
CIRCUIT FEEDER DB NO. SP/ TP
No.

1
2
3
4
5
6

ACB

MCCB

FAULT
DUTY
MCB
KA

PVC/XLPE
SWA/PVC

H.H.SH. AHMED BIN SAIF AL NAHYAN


M/S. IAN BANHAN & ASSOCIATES

CABLE SIZE
2/4 x 1C
mm2

2/3/4C
mm2

LENGTH
OF
CABLE
(mtrs)

ECC
SIZE-1C
mm2

INCOMER

TP

160
(N/A)

35

XLPE/SWA/PVC

4C 70

1C 35

OUTGOING
INDUCTION COOK TOP -8
INDUCTION COOK TOP -8
DISH WASHER -38
DB - B1WB
SPARE
INDUCTION COOK TOP -8

TP
TP
TP
TP
TP
TP

32
32
32
63
20
32

35
35
35
35
35
35

XLPE/SWA/PVC

XLPE/SWA/PVC

4C 6
4C 6
4C 6
4C 16

1C 6
1C 6
1C 6
1C 16

XLPE/SWA/PVC

4C 6

1C 6

SMDB- B1N CONNECTED TO: MDB - 1


DEMAND FACTOR

CONTRACTOR:

0.90

XLPE/SWA/PVC
XLPE/SWA/PVC

(1) UP TO 60A
(1 PHASE)

KWH METER
1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

REMARKS

R-PHASE
KW

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

2.30
2.30
3.30
11.40
1.00
2.00

2.30
2.40
3.30
11.40
1.0
2.00

2.40
2.30
3.20
11.10
1.0
2.00

7.00
7.00
9.80
33.90
3.00
6.00

4P ELCB 100 mA
4P ELCB 100 mA
4P ELCB 100 mA

22.30

22.40

22.00

66.70

TOTAL

LV/HV
CT (4)

4P ELCB 100 mA
4P ELCB 100 mA

TOTAL CONNECTED LOAD (3PH) 66.70 KW

TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

TOTAL CONNECTED LOAD PER PHASE

MAX. DEMAND..
60.03 KW

LOCATION: ELECTRICAL CABINET


BASEMENT 1

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618


HV CT A

PROJECT:

PULLMAN HOTEL TOWER


3B+C+1+34+MECH.FLOORS
PLANNED COMPLETION DATE: MAY 2010

DETAILS OF CONNECTED LOAD / MAX. DEMAND

AREA: JLT, DUBAI

OWNER:

PLOT No: 393-929

SMDB REF: SMDB - B1N

CONSULTANT:

RATING-AMPS
SR.
No.

1
2
3
4
5
6
7
8
9
10

FAULT
DUTY
MCB
KA

PVC/XLPE

H.H.SH. AHMED BIN SAIF AL NAHYAN


M/S. IAN BANHAN & ASSOCIATES

CABLE SIZE

LENGTH
OF
CABLE
(mtrs)

ECC
SIZE-1C
mm2

CIRCUIT FEEDER DB
NO.

SP/ TP

INCOMER

TP

400
(N/A)

35

XLPE/SWA/PVC

4C 300

1C 150

TP
TP
TP
TP
TP
TP
TP
TP
TP
TP

40
40
63
63
160
40
40
40
32
40

35
35
35
35
35
35
35
35
35
35

XLPE/SWA/PVC

4C 10
4C 10
4C 16
4C 16
4C 70
4C 10
4C 10
4C 10
4C 10
4C 10

1C 10
1C 10
1C 16
1C 16
1C 35
1C 10
1C 10
1C 10
1C 10
1C 10

OUTGOING
DB - B3N
DB - B2N
AHU - 1
AHU - K1
SMDB - B1WB
DB - B1N1
DB - B1N2
DB - B1N3
DB-SHOP
AHU-K3

ACB

MCCB

SMDB- B1N CONNECTED TO: MDB - 2


DEMAND FACTOR

CONTRACTOR:

0.90

SWA/PVC

XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC
XLPE/SWA/PVC

2/4 x 1C
mm2

2/3/4C
mm2

(1) UP TO 60A
(1 PHASE)

KWH METER

R-PHASE
KW

Y-PHASE
KW

B-PHASE
KW

TOTAL
KW

5.65
6.21
5.00
5.00
22.30
6.35
2.30
5.50
1.00
4.00

5.50
5.95
5.00
5.00
22.4
5.7
2.50
5.50
1.0
4.0

5.05
5.81
5.00
5.00
22.0
7.0
2.50
5.50
1.0
4.0

16.20
17.97
15.00
15.00
66.70
19.00
7.30
16.50
3.00
12.00

63.31

62.55

62.81

188.67

1 Ph 3 Ph
(1)
(2)

3 Ph
(3)

LV/HV
CT (4)

REMARKS

4P ELCB 100 mA
4P ELCB 100 mA

4P ELCB 100 mA
4P ELCB 100 mA

TOTAL

TOTAL CONNECTED LOAD (3PH)188.67 KW

TEL No. 04 885 1700

LIGHTWAY ELECTRICAL WORKS LLC, TEL : 04-3867355 ,FAX: 04-3938521

Type of Meter (Rating of Incomer) :

CONNECTED LOAD-KW

TOTAL CONNECTED LOAD PER PHASE

MAX. DEMAND..
169.80 KW

LOCATION: LV ROOM
BASEMENT 1

(2) UP TO 100A

(3) 125-160A
(3 PHASE)

(4) LV CT

Fax No. 04 885 1618