I.7.

3
'28%/( :,1'2: 6,*+7 */$66
&URVV W\SH
Limiting conditions
Maximum operating pressure vs temperature 13 bar at 200 Deg C
Maximum body design conditions
Max. allowable pressure 23 bar g
Max. allowable temperature 320 Deg C
Cold hydraulic test 35 bar g
Installation
Should be fitted on the outlet of a steam trap, on blast discharge type at least 1 m from the trap.
No. Parts Materials
1. Body GG 25 Cast iron
2. Cover GG 25 Cast iron
3. Glass Borosilicate Glass
4. Cover Bolt Ck 35, 1.1181 Stainless steel
5. Gasket Teflon
Dimensions mm
in 1/2 3/4 1 1 1/2 2 2 1/2 3 4 5 6 8 10 12 14 16
SZE
mm 15 20 25 40 50 65 80 100 125 150 200 250 300 350 400
L 150 150 200 200 220 270 270 318 380 380 460 - - - -
H 100 100 145 165 180 180 215 245 290 290 340 - - - -
PN16
E 36 36 62 65 73 120 118 155 210 210 260 - - - -
Weight
(kg) 9 17 19 30