DIMENSIONAMIENTO DE TRANSFORMADORES

PROYECTO
SECCION DE OBRA
LOCALIDADES
PROVINCIA
DEPARTAMENTO

LOCALIDAD

: PEQUEO SISTEMA ELECTRICO TOCACHE II ETAPA - RAMAL PUERTO LOS OLIVOS - TAMBO DE PAJA
: LINEAS Y REDES PRIMARIAS
: PUSHURUMBO, SAN FRANCISCO, LAS PALMAS, BELEN Y MONTE CRISTO.
: TOCACHE Y SHUNTE
: SAN MARTN

ABONADOS
POTENCIALES

LOTES
EXISTENTES
HABITADOS

Cargas
Calif. Elc. Usuarios
Especiales
(W/lote) Domst. (kW)
(N)

Cargas
Serv.
Especiales
Unidades A.P.
Part. (kW)
(kW)

Pot.
Lmp.
(kW)

Serv. Sub Total Prdidas


A.P. (kW) (kW)
(kW)

Total
(kW)

Pot.
Transf.
(kVA)

Pot. Trafo
Normaliza
(kVA)

Pushurumbo

88

21

400

4.2

1.0

5.2

3.00

0.0816

0.24

5.44

0.16

5.61

6.23

10.00

San Francisco

147

38

400

7.6

1.0

8.6

5.00

0.0816

0.41

9.01

0.27

9.28

10.31

15.00

Las Palmas

210

54

400

10.8

1.0

11.8

7.00

0.0816

0.57

12.37

0.37

12.74

14.16

15.00

Belen

94

20

400

4.0

1.0

5.0

3.00

0.0816

0.24

5.24

0.16

5.40

6.00

10.00

Monte Cristo

188

52

400

10.4

1.0

11.4

7.00

0.0816

0.57

11.97

0.36

12.33

13.70

15.00

Shunte

96

25

400

5.0

1.0

6.0

4.00

0.0816

0.33

6.33

0.19

6.52

7.24

10.00

Metal

141

35

400

7.0

1.0

8.0

5.00

0.0816

0.41

8.41

0.25

8.66

9.62

15.00

Pushurumbo Antiguo

27

400

1.8

1.8

2.00

0.0816

0.16

1.96

0.06

2.02

2.25

5.00

Indoamerica

50

16

400

3.2

1.0

4.2

3.00

0.0816

0.24

4.44

0.13

4.58

5.09

10.00

Nueva Meseta

48

14

400

2.8

1.0

3.8

3.00

0.0816

0.24

4.04

0.12

4.17

4.63

5.00

Pampa Hermosa

95

21

400

4.2

1.0

5.2

3.00

0.0816

0.24

5.44

0.16

5.61

6.23

10.00

La Victoria

41

10

400

2.0

0.5

2.5

2.00

0.0816

0.16

2.66

0.08

2.74

3.05

5.00

79.66

88.51

CALCULO DE CAIDA DE TENSION Y PERDIDA DE POTENCIA


TRAMO : SSEE 138/22,9 kV. TOCACHE - SHUNTE - LA VICTORIA MONOFASICO 25 mm2
PROYECTO
SECCION DE OBRA
LOCALIDADES
DISTRITO
PROVINCIA
DEPARTAMENTO

LOCALIDADES

: PEQUEO SISTEMA ELECTRICO TOCACHE II ETAPA / RAMAL-PUERTO LOS OLIVOSTAMBO DE PAJA


: LINEAS Y REDES PRIMARIAS
: PUSHURUMBO, LAS PALMAS, SAN FRANCISCO, BELEN Y MONTE CRISTO, SHUNTE Y
METAL.
: TOCACHE Y SHUNTE.
: TOCACHE
: SAN MARTN

PUNTO

SSEE 138/22,9 Kv,TOCACHE 0


CHAN CHAN
1
PUCAYACU / UCHIZA
2
CUARTO SECTOR LIMON
3
TOCACHE VIEJO
4
YACUSISA
5
PUERTO LOS OLIVOS
6
PUSHURUMBO
7
SAN FRANCISCO
8
LAS PALMAS
9
BELEN
10
MONTE CRISTO
11
SHUNTE
12
LA VICTORIA
12.1

N SUMA
S.E. S. E.
0
1
26
1
1
1
1
1
1
1
1
1
1
1

POT
(KVA)

38
0.00
38
25.00
37 1550.00
11
50.00
10
40.00
9
25.00
8
10.00
7
10.00
6
15.00
5
15.00
4
10.00
3
15.00
2
10.00
1
5.00

POT
(Kw)

SUMA
P(total)
(Kw)

S
mm

0.00 1602.00 3 x 70
22.50 1602.00 3 x 70
1395.00 1579.50 3 x 70
45.00
184.50 3 x 50
36.00
139.50 3 x 50
22.50
103.50 3 x 50
9.00
81.00 3 x 50
9.00
72.00 3 x 50
13.50
63.00 3 x 50
13.50
49.50 3 x 50
9.00
36.00 3 x 50
13.50
27.00 3 x 50
9.00
13.50 1 x 35
4.50
4.50 1 x 25

LONG
PROG.
Km
0.010
4.510
6.010
7.410
8.610
14.710
20.010
21.910
23.720
26.880
30.780
36.036
39.981
40.431

LONG
Km
0.010
4.500
1.500
1.400
1.200
6.100
5.300
1.900
1.810
3.160
3.900
5.256
3.945
0.450

F.C.T.
0.0001431
0.0001431
0.0001431
0.0001774
0.0001774
0.0001774
0.0001774
0.0001774
0.0001774
0.0001774
0.0001774
0.0001774
0.0008668
0.0008668

DATOS ELCTRICOS

Vn (KV)
Cos
Vn (KV)
S Cond (mm)
F.c.
F.p.

CAIDA
VOLTAJE
(KV)
0.00052
0.23624
0.07764
0.01049
0.00680
0.02565
0.01744
0.00556
0.00463
0.00635
0.00570
0.00577
0.01057
0.00040

FACTORES K DE LINEA

RESIST. ELCT. (40C)

22.9 K1-3x70mm

0.0001431

R1-70mm

0.54400

K1-3X50mm

0.0001774

R1-50mm

0.71900

13.2 Kt-1X35mm
70-50-35 Kt-1X25mm
0.3
0.1215

0.0008668
0.0011197

R1-35mm
R1-25mm

1.03600
1.46900

0.9

SUMA
CAIDA V
(KV)
0.00052
0.23676
0.31440
0.32490
0.33170
0.35735
0.37479
0.38034
0.38498
0.39133
0.39703
0.40280
0.41337

0.41377

PERDIDAS DE POTENCIA
CADA DE
SUMA CADA
PERD POT SUM PERD
TENSIN % DE TENSIN %
%
(KW)
(KW)
0.00229
1.03161
0.33904
0.04582
0.02970
0.11200
0.07616
0.02427
0.02023
0.02775
0.02491
0.02518
0.04616
0.00176

0.00229
1.03390
1.37294
1.41876
1.44846
1.56046
1.63662
1.66089
1.68112
1.70886
1.73377
1.75895
1.80511

1.80687

0.03287
14.79042
4.79262
0.08067
0.03953
0.11061
0.05886
0.01667
0.01216
0.01311
0.00856
0.00649
0.00528
0.00009

19.96792
19.93506
5.14464
0.35201
0.27135
0.23182
0.12121
0.06235
0.04568
0.03352
0.02041
0.01186
0.00537
0.00009

1.246
1.244
0.326
0.191
0.195
0.224
0.150
0.087
0.073
0.068
0.057
0.044
0.040
0.002

PERD ANUAL DE ENERGIA


PER ENER SUMA PERD (KW(KW-h)
h)
34.98230
15742.03369
5100.98234
85.85668
42.07101
117.72368
62.64684
17.74483
12.94234
13.94925
9.10590
6.90297
5.61722
0.10095

21252.66001
21217.67771
5475.64402
374.66168
288.80501
246.73400
129.01032
66.36347
48.61864
35.67630
21.72705
12.62115
5.71817
0.10095

CALCULO DE CAIDA DE TENSION Y PERDIDA DE POTENCIA


TRAMO : SSEE 138/22,9 kV. TOCACHE - MONTE CRISTO - PAMPA HERMOSA MONOFASICO 25 mm2
PROYECTO
SECCION DE OBRA
LOCALIDADES
DISTRITO
PROVINCIA
DEPARTAMENTO

LOCALIDADES

: PEQUEO SISTEMA ELECTRICO TOCACHE II ETAPA / RAMAL-PUERTO LOS OLIVOSTAMBO DE PAJA


: LINEAS Y REDES PRIMARIAS
: PUSHURUMBO, LAS PALMAS, SAN FRANCISCO, BELEN Y MONTE CRISTO, SHUNTE Y
METAL.
: TOCACHE Y SHUNTE.
: TOCACHE
: SAN MARTN

PUNTO

SSEE 138/22,9 Kv,TOCACHE 0


CHAN CHAN
1
PUCAYACU / UCHIZA
2
CUARTO SECTOR LIMON
3
TOCACHE VIEJO
4
YACUSISA
5
PUERTO LOS OLIVOS
6
PUSHURUMBO
7
SAN FRANCISCO
8
LAS PALMAS
9
BELEN
10
MONTE CRISTO
11
PAMPA HERMOSA
11.1

N
S.E.
0
1
26
1
1
1
1
1
1
1
1
1
1

SUMA
S. E.
37.00
37.00
36.00
10.00
9.00
8.00
7.00
6.00
5.00
4.00
3.00
2.00
1.00

POT
(KVA)

POT
(Kw)

SUMA
P(total)
(Kw)

S
mm

0.00
0.00 1597.50 3 x 70
25.00
22.50 1597.50 3 x 70
1550.00 1395.00 1575.00 3 x 70
50.00
45.00 180.00 3 x 50
40.00
36.00 135.00 3 x 50
25.00
22.50
99.00 3 x 50
10.00
9.00
76.50 3 x 50
10.00
9.00
67.50 3 x 50
15.00
13.50
58.50 3 x 50
15.00
13.50
45.00 3 x 50
10.00
9.00
31.50 3 x 50
15.00
13.50
22.50 3 x 50
10.00
9.00
9.00 1 X 25

LONG
PROG.
Km
0.010
4.510
6.010
7.410
8.610
14.710
20.010
21.910
23.720
26.880
30.780
36.036
36.666

LONG
Km
0.010
4.500
1.500
1.400
1.200
6.100
5.300
1.900
1.810
3.160
3.900
5.256
0.630

F.C.T.
0.0001431
0.0001431
0.0001431
0.0001774
0.0001774
0.0001774
0.0001774
0.0001774
0.0001774
0.0001774
0.0001774
0.0001774
0.0011197

DATOS ELCTRICOS

Vn (KV)
Cos
Vn (KV)
S Cond (mm)
F.c.
F.p.

FACTORES K DE LINEA

22.9 K1-3x70mm

R1-70mm

0.54400

K1-3X50mm

0.0001774

R1-50mm

0.71900

13.2 Kt-1X35mm
70-50-35 Kt-1X25mm
0.3
0.1215

0.0008668
0.0011197

R1-35mm
R1-25mm

1.03600
1.46900

0.9

SUMA
SUMA CADA
CAIDA
CADA DE
CAIDA V
DE TENSIN
VOLTAJE (KV)
TENSIN %
(KV)
%
0.00052
0.23557
0.07742
0.01024
0.00658
0.02453
0.01647
0.00521
0.00430
0.00578
0.00499
0.00480
0.00145

RESIST. ELCT. (40C)

0.0001431

0.00052
0.23610
0.31352
0.32375
0.33034
0.35487
0.37134
0.37655
0.38085
0.38663
0.39162
0.39642
0.39788

0.00229
1.02871
0.33807
0.04470
0.02874
0.10713
0.07193
0.02275
0.01878
0.02523
0.02179
0.02098
0.00635

0.002286
1.030996
1.369070
1.413775
1.442513
1.549645
1.621572
1.644324
1.663108
1.688334
1.710128
1.731107
1.737456

PERDIDAS DE POTENCIA
PERD POT SUM PERD
%
(KW)
(KW)
0.03268
14.70744
4.76536
0.07678
0.03702
0.10120
0.05250
0.01465
0.01048
0.01083
0.00655
0.00450
0.00053

19.82053
19.78785
5.08041
0.31505
0.23827
0.20125
0.10006
0.04755
0.03290
0.02242
0.01159
0.00504
0.00053

PERD ANUAL DE ENERGIA


PER ENER
SUMA PERD
(KW-h)
(KW-h)

1.241
34.78604
1.239 15653.71951
0.323 5071.95832
0.175
81.71962
0.176
39.40053
0.203
107.70938
0.131
55.87944
0.070
15.59604
0.056
11.15947
0.050
11.52830
0.037
6.97171
0.022
4.79373
0.006
0.56532

21095.78741
21061.00137
5407.28186
335.32354
253.60392
214.20339
106.49401
50.61457
35.01853
23.85906
12.33076
5.35905
0.56532

CALCULO DE CAIDA DE TENSION Y PERDIDA DE POTENCIA


TRAMO : SSEE 138/22,9 kV. TOCACHE - SAN FRANCISCO - DERIVACION NUEVA MESETA MONOFASICO 25 mm2
PROYECTO
SECCION DE OBRA
LOCALIDADES
DISTRITO
PROVINCIA
DEPARTAMENTO

LOCALIDAD

: PEQUEO SISTEMA ELECTRICO TOCACHE II ETAPA / RAMAL-PUERTO LOS OLIVOSTAMBO DE PAJA


: LINEAS Y REDES PRIMARIAS
: PUSHURUMBO, LAS PALMAS, SAN FRANCISCO, BELEN Y MONTE CRISTO, SHUNTE Y
METAL.
: TOCACHE Y SHUNTE.
: TOCACHE
: SAN MARTN

PUNTO

SSEE 138/22,9 Kv,TOCACHE 0


CHAN CHAN
1
PUCAYACU / UCHIZA
2
CUARTO SECTOR LIMON
3
TOCACHE VIEJO
4
YACUSISA
5
PUERTO LOS OLIVOS
6
PUSHURUMBO
7
SAN FRANCISCO
8
NUEVA MESETA
8.1

N SUMA
S.E. S. E.
0
1
26
1
1
1
1
1
1
1

POT
(KVA)

POT
(Kw)

SUMA
P(total)
(Kw)

S
mm

34
0.00
0.00 1557.00 3 x 70
34
25.00
22.50 1557.00 3 x 70
33 1550.00 1395.00 1534.50 3 x 70
7
50.00
45.00 139.50 3 x 50
6
40.00
36.00
94.50 3 x 50
5
25.00
22.50
58.50 3 x 50
4
10.00
9.00
36.00 3 x 50
3
10.00
9.00
27.00 3 x 50
2
15.00
13.50
18.00 3 x 50
1
5.00
4.50
4.50 1 X 25

LONG
LONG
PROG.
Km
Km
0.010
4.510
6.010
7.410
8.610
14.710
20.010
21.910
23.720
25.140

0.010
4.500
1.500
1.400
1.200
6.100
5.300
1.900
1.810
1.420

F.C.T.
0.0001431
0.0001431
0.0001431
0.0001774
0.0001774
0.0001774
0.0001774
0.0001774
0.0001774
0.0011197

DATOS ELCTRICOS

Vn (KV)

FACTORES K DE LINEA

RESIST. ELCT. (40C)

0.0001431

R1-70mm

0.54400

K1-3X50mm

0.0001774

R1-50mm

0.71900

Vn (KV)
13.2 Kt-1X35mm
S Cond (mm) 70-50-35 Kt-1X25mm
F.c.
0.3
F.p.
0.1215

0.0008668
0.0011197

R1-35mm
R1-25mm

1.03600
1.46900

Cos

CAIDA
VOLTAJE
(KV)
0.00051
0.22960
0.07543
0.00793
0.00461
0.01450
0.00775
0.00208
0.00132
0.00164

22.9 K1-3x70mm
0.9

SUMA
PERDIDAS DE POTENCIA
CADA DE
SUMA CADA
CAIDA V
PERD POT SUM PERD
TENSIN % DE TENSIN %
%
(KV)
(KW)
(KW)
0.00051
0.23011
0.30554
0.31347
0.31808
0.33258
0.34033
0.34241
0.34374
0.34538

0.00223
1.00263
0.32938
0.03465
0.02012
0.06331
0.03385
0.00910
0.00578
0.00715

0.002228
1.004858
1.334239
1.368885
1.389002
1.452307
1.486155
1.495256
1.501035
1.508190

0.03105
13.97117
4.52343
0.04612
0.01814
0.03534
0.01163
0.00234
0.00099
0.00030

18.64050
18.60945
4.63828
0.11485
0.06874
0.05060
0.01526
0.00364
0.00129
0.00030

1.197
1.195
0.302
0.082
0.073
0.086
0.042
0.013
0.007
0.007

PERD ANUAL DE ENERGIA


PER ENER SUMA PERD (KW(KW-h)
h)
33.04460
14870.07090
4814.46845
49.08285
19.30626
37.60927
12.37469
2.49537
1.05652
0.31855

19839.82744
19806.78284
4936.71194
122.24350
73.16065
53.85439
16.24512
3.87044
1.37507
0.31855

CALCULO DE CAIDA DE TENSION Y PERDIDA DE POTENCIA


TRAMO : SSEE 138/22,9 kV. TOCACHE - PUSHURUMBO - DERIVACION A INDOAMERICA MONOFASICO 25 mm2
PROYECTO
SECCION DE OBRA
LOCALIDADES
DISTRITO
PROVINCIA
DEPARTAMENTO

SECTORES

: PEQUEO SISTEMA ELECTRICO TOCACHE II ETAPA / RAMAL-PUERTO LOS OLIVOS-TAMBO DE


DATOS ELCTRICOS
FACTORES K DE LINEA
PAJA
: LINEAS Y REDES PRIMARIAS
Vn (KV)
22.9 K1-3x70mm
0.0001431

R1-70mm

0.54400

: PUSHURUMBO, LAS PALMAS, SAN FRANCISCO, BELEN Y MONTE CRISTO, SHUNTE Y METAL.
: TOCACHE Y SHUNTE.
: TOCACHE
: SAN MARTN

PUNTO

SSEE 138/22,9 Kv,TOCACHE 0


CHAN CHAN
1
PUCAYACU / UCHIZA
2
CUARTO SECTOR LIMON
3
TOCACHE VIEJO
4
YACUSISA
5
PUERTO LOS OLIVOS
6
PUSHURUMBO
7
PUSHURUMBO ANTIGUO
7.1
INDOAMERICA
7.2

N SUMA
POT (KVA)
S.E. S. E.
0
1
26
1
1
1
1
1
1
1

34
34
33
7
6
5
4
3
2
1

0.00
25.00
1550.00
50.00
40.00
25.00
10.00
10.00
5.00
12888.89

POT (Kw)
0.00
22.50
1395.00
45.00
36.00
22.50
9.00
9.00
4.50
11600.00

SUMA
P(total)
(Kw)

S
mm

13143.50
13143.50
13121.00
11726.00
11681.00
11645.00
11622.50
11613.50
11604.50
11600.00

3 x 70
3 x 70
3 x 70
3 x 50
3 x 50
3 x 50
3 x 50
3 x 50
1 X 25
1 X 25

LONG
PROG.
Km
0.010
4.510
6.010
7.410
8.610
14.710
20.010
21.910
22.060
24.930

LONG
Km
0.010
4.500
1.500
1.400
1.200
6.100
5.300
1.900
0.150
2.870

F.C.T.
0.0001431
0.0001431
0.0001431
0.0001774
0.0001774
0.0001774
0.0001774
0.0001774
0.0011197
0.0011197

Cos

K1-3X50mm

0.0001774

R1-50mm

0.71900

Vn (KV)
13.2 Kt-1X35mm
S Cond (mm) 70-50-35 Kt-1X25mm
F.c.
0.3
F.p.
0.1215

0.0008668
0.0011197

R1-35mm
R1-25mm

1.03600
1.46900

CAIDA
VOLTAJE
(KV)
0.00431
1.93820
0.64496
0.66691
0.56944
2.88575
2.50244
0.89641
0.44633
8.53644

0.9

RESIST. ELCT. (40C)

SUMA
PERDIDAS DE POTENCIA
CADA DE
SUMA CADA
CAIDA V
PERD POT SUM PERD
TENSIN % DE TENSIN %
%
(KV)
(KW)
(KW)
0.00431
1.94251
2.58747
3.25438
3.82382
6.70957
9.21201
10.10842
10.55475
19.09120

0.01881
8.46376
2.81642
2.91227
2.48665
12.60152
10.92771
3.91445
1.94903
37.27705

0.018808
2.21241
8.482565 995.58304
11.298988 330.72578
14.211257 325.83724
16.697908 277.14956
29.299429 1400.17309
40.227136 1211.84726
44.141582 433.76325
46.090616 210.24856
83.367668 4019.63658

9207.17678
9204.96437
8209.38134
7878.65556
7552.81832
7275.66875
5875.49566
4663.64840
4229.88514
4019.63658

70.051
70.034
62.567
67.190
64.659
62.479
50.553
40.157
36.450
34.652

PERD ANUAL DE ENERGIA


PER ENER
SUMA PERD (KW(KW-h)
h)
2354.75300
1059638.85080
352004.67408
346801.61105
294981.36764
1490260.22973
1289817.51536
461671.57973
223775.95714
4278259.99653

9799566.53506
9797211.78206
8737572.93126
8385568.25718
8038766.64613
7743785.27849
6253525.04876
4963707.53340
4502035.95367
4278259.99653

CLCULO DE N DE UNIDADES DE ALUMBRADO PBLICO


PROYECTO
SECCION DE OBRA
LOCALIDADES
PROVINCIA
DEPARTAMENTO

LOCALIDAD

N DE
ACOMETIDAS
PROY.

Pushurumbo

21

3.30

0.0816

360.00

2.00

3.00

San Francisco

38

3.30

0.0816

360.00

4.00

5.00

Las Palmas

54

3.30

0.0816

360.00

6.00

7.00

Belen

20

3.30

0.0816

360.00

2.00

3.00

Monte Cristo

49

3.30

0.0816

360.00

6.00

7.00

Shunte

25

3.30

0.0816

360.00

3.00

4.00

Metal

35

3.30

0.0816

360.00

4.00

5.00

Pushurumbo Antiguo

3.30

0.0816

360.00

1.00

2.00

KALP
(kWh/Us.)

Pot. Lmp. Horas de Uso Unidades A.P.


(kW)
/ mes
/DGE

Unidades
A.P. Proy

Indoamerica

16

3.30

0.0816

360.00

2.00

3.00

Nueva Meseta

14

3.30

0.0816

360.00

2.00

3.00

Pampa Hermosa

21

3.30

0.0816

360.00

2.00

3.00

La Victoria

10

3.30

0.0816

360.00

1.00

2.00

NORMA REFERENCIAL : R.D.N 017-2004-EM/DGE (Alumbrado de Vas Pblicas en reas Rurales)

DIMENSIONAMIENTO DE TRANSFORMADORES
PROYECTO
SECCION DE OBRA
LOCALIDADES
PROVINCIA
DEPARTAMENTO

LOCALIDAD

Pushurumbo
San Francisco
Las Palmas
Belen
Monte Cristo
Shunte
Metal
Pushurumbo Antiguo
Indoamerica
Nueva Meseta
Pampa Hermosa
La Victoria

: PEQUEO SISTEMA ELECTRICO TOCACHE II ETAPA - RAMAL PUERTO LOS OLIVOS - TAMBO DE PAJA
: LINEAS Y REDES PRIMARIAS
: PUSHURUMBO, SAN FRANCISCO, LAS PALMAS, BELEN Y MONTE CRISTO.
: TOCACHE Y SHUNTE
: SAN MARTN

ABONADOS
POTENCIALES

LOTES
EXISTENTES
HABITADOS

88

21

147

38

210

54

94

20

188

52

96

25

141

35

27

50

16

48

14

95

21

41

10

Cargas
Calif. Elc. Usuarios
Especiales
(W/lote) Domst. (kW)
(N)

400
400
400
400
400
400
400
400
400
400
400
400

4.2
7.6
10.8
4.0
10.4
5.0
7.0
1.8
3.2
2.8
4.2
2.0

Cargas
Serv.
Especiales
Unidades A.P.
Part. (kW)
(kW)

2
2
2
2
2
2
2

1.0
1.0
1.0
1.0
1.0
1.0
1.0

2
2
2
1

1.0
1.0
1.0
0.5

5.2
8.6
11.8
5.0
11.4
6.0
8.0
1.8
4.2
3.8
5.2
2.5

3.00
5.00
7.00
3.00
7.00
4.00
5.00
2.00
3.00
3.00
3.00
2.00

Pot.
Lmp.
(kW)

0.0816
0.0816
0.0816
0.0816
0.0816
0.0816
0.0816
0.0816
0.0816
0.0816
0.0816
0.0816

Serv. Sub Total Prdidas


A.P. (kW) (kW)
(kW)

0.24
0.41
0.57
0.24
0.57
0.33
0.41
0.16
0.24
0.24
0.24
0.16

5.44
9.01
12.37
5.24
11.97
6.33
8.41
1.96
4.44
4.04
5.44
2.66

Total
(kW)

0.16 5.61
0.27 9.28
0.37 12.74
0.16 5.40
0.36 12.33
0.19 6.52
0.25 8.66
0.06 2.02
0.13 4.58
0.12 4.17
0.16 5.61
0.08 2.74

Pot.
Transf.
(kVA)

6.23
10.31
14.16
6.00
13.70
7.24
9.62
2.25
5.09
4.63
6.23
3.05

Pot. Trafo
Normaliza
(kVA)
10.00
15.00
15.00
10.00
15.00
10.00
15.00
5.00
10.00
5.00
10.00
5.00

CALCULO DE CAIDA DE TENSION Y PERDIDA DE POTENCIA


TRAMO : SSEE 138/22,9 kV. TOCACHE - MONTE CRISTO - METAL
PROYECTO
SECCION DE OBRA
LOCALIDADES
DISTRITO
PROVINCIA
DEPARTAMENTO

: PEQUEO SISTEMA ELECTRICO TOCACHE II ETAPA / RAMAL-PUERTO LOS OLIVOSTAMBO DE PAJA


: LINEAS Y REDES PRIMARIAS
: PUSHURUMBO, LAS PALMAS, SAN FRANCISCO, BELEN Y MONTE CRISTO, SHUNTE Y
METAL.
: TOCACHE Y SHUNTE.
: TOCACHE
: SAN MARTN

PUNTO
SSEE 138/22,9 Kv,TOCACHE
CHAN CHAN
PUCAYACU / UCHIZA
CUARTO SECTOR LIMON
TOCACHE VIEJO
YACUSISA
PUERTO LOS OLIVOS
PUSHURUMBO
SAN FRANCISCO
LAS PALMAS
BELEN
MONTE CRISTO
SHUNTE
METAL

0
1
2
3
4
5
6
7
8
9
10
11
12
13

N SUMA
S.E. S. E.
0
1
26
1
1
1
1
1
1
1
1
1
1
1

POT
(KVA)

38
0.00
38
25.00
37 1550.00
11
50.00
10
40.00
9
25.00
8
10.00
7
10.00
6
15.00
5
15.00
4
10.00
3
15.00
2
10.00
1
15.00

POT
(Kw)

SUMA
P(total)
(Kw)

S
mm

0.00 1611.00 3 x 70
22.50 1611.00 3 x 70
1395.00 1588.50 3 x 70
45.00 193.50 3 x 50
36.00 148.50 3 x 50
22.50 112.50 3 x 50
9.00
90.00 3 x 50
9.00
81.00 3 x 50
13.50
72.00 3 x 50
13.50
58.50 3 x 50
9.00
45.00 3 x 50
13.50
36.00 3 x 50
9.00
22.50 1 x 35
13.50
13.50 1 x 35

LONG
PROG.
Km
0.010
4.510
6.010
7.410
8.610
14.710
20.010
21.910
23.720
26.880
30.780
36.036
39.981
43.896

LONG
Km
0.010
4.500
1.500
1.400
1.200
6.100
5.300
1.900
1.810
3.160
3.900
5.256
3.945
3.915

F.C.T.
0.0001431
0.0001431
0.0001431
0.0001774
0.0001774
0.0001774
0.0001774
0.0001774
0.0001774
0.0001774
0.0001774
0.0001774
0.0008668
0.0008668

DATOS ELCTRICOS

Vn (KV)
Cos
Vn (KV)
S Cond (mm)
F.c.
F.p.

CAIDA
VOLTAJE
(KV)
0.00053
0.23757
0.07808
0.01101
0.00724
0.02788
0.01938
0.00625
0.00529
0.00751
0.00713
0.00769
0.01762
0.01049

FACTORES K DE LINEA

RESIST. ELCT. (40C)

22.9 K1-3x70mm

0.0001431

R1-70mm

0.54400

K1-3X50mm

0.0001774

R1-50mm

0.71900

13.2 Kt-1X35mm
70-50-35
0.3
0.1215

0.0008668

R1-35mm

1.03600

0.9

SUMA
CAIDA V
(KV)
0.00053
0.23809
0.31618
0.32718
0.33442
0.36230
0.38168
0.38793
0.39322
0.40073
0.40786

0.41555
0.43317

0.44366

PERDIDAS DE POTENCIA
CADA DE
SUMA CADA
PERD POT SUM PERD
TENSIN % DE TENSIN %
%
(KW)
(KW)
0.00231
1.03740
0.34097
0.04806
0.03161
0.12174
0.08462
0.02730
0.02312
0.03279
0.03113
0.03357
0.07694
0.04581

0.002305
1.039709
1.380680
1.428738
1.460351
1.582091
1.666711
1.694013
1.717132
1.749926
1.781060

1.814627
1.891566

1.937378

0.03324
14.95707
4.84740
0.08873
0.04479
0.13068
0.07267
0.02110
0.01588
0.01831
0.01337
0.01153
0.01466
0.00524

20.25476
20.22152
5.26445
0.41705
0.32832
0.28353
0.15285
0.08019
0.05909
0.04320
0.02490
0.01153
0.01990
0.00524

PERD ANUAL DE ENERGIA


PER ENER
SUMA PERD
(KW-h)
(KW-h)

1.257
35.37646
1.255 15919.40732
0.331 5159.27881
0.216
94.43724
0.221
47.67464
0.252
139.08752
0.170
77.34178
0.099
22.45830
0.082
16.90429
0.074
19.48283
0.055
14.22797
0.032
12.27195
0.088
15.60340
0.039
5.57451

21579.12702
21543.75056
5624.34324
465.06444
370.62720
322.95256
183.86504
106.52325
84.06495
67.16066
47.67783
33.44986
21.17791
5.57451