Вы находитесь на странице: 1из 2

Project: Keadue WWTP Upgrade Works Section: Aeration Tank Design Calculations By:

Ken Geelan

Job No. :

`
1

Drawing Ref:

Checked By:

Date:

Reference:

Calculations

Output

Aeration Tank Design


INSERT RELEVANT DATA INTO HIGHLIGHTED AREAS

Inputs Population Eqivalent = 550 PE

Flow Per Person =

225

l/person/day

Dry Weather Flow (DWF) =

BOD Per Person =

60

mg/l m3/d g/m3 g/m3

Prim. Effl. Flow Rate, Qo = Prim. Effl. BOD, So =

371

60

Aeration tank MLSS, X =

1500

Design Vol. Loading, VL = (kg BOD/day/m ) % volatile MLSS, %Vol =


3

0.5

75% g/m3

Prim. Effl. TSS, Xo = Calculations Aeration tank volume, V = Aeration Tank Area, A = OverFlowrate - OR = . Aeration tank HRT = Aeration tank F:M = (kg BOD/day/kg MLVSS) Recycle Activated Sludge Flow Rate, Qr = Waste Activated Sludge Flow Rate, Qw =

100

45 24.75 15

m3 m2

2.9 0.44

hr

95

m3/d

m3/d

Aeration tank F:M = (kg BOD/day/kg MLVSS)

0.44

Project: Keadue WWTP Upgrade Works Section: Aeration Tank Design Calculations By:
Ken Geelan

Job No. :

Calculation Sheet No :
2

Drawing Ref:

Checked By:

Date:

Reference:

Calculations

Output

Waste / Recycle Activated Sludge Sludge SS conc., Xw = 7000 g/m


3 3

Aeration tank vol., V =

45

Aeration tank MLSS, X =

1500

g/m3 days

Sludge ret. time, SRT =

12

Removal Rates BOD Removal = t/a+bt Empirical Constants -a -b Remaining BOD After Removed (mg/l) = 0.018 0.02 38%

38% 37.14 mg/l

TSS Removal = t/a+bt Empirical Constants -a -b Remaining TSS After Removed =

60% 0.0075 0.014 60% 39.77 mg/l

Equations used for Calculations:

Qr = Qo(X - Xo)/(Xw - X) Qw = (V*X)/(SRT*Xw) F:M = (So*Qo)/(%Vol*X*VMG) V = (So*Qo/1000)/VL HRT = 24*VMG/Qo F:M = (So*Qo)/(%Vol*X*VMG)