YCAV/YCIV - Latitude / 1st, 2nd Compressors YORK TALK 2 Microgateway / ELINK Micro Board: 031-02478-xxx
Item Ref. Version Date YORK P N Checksum Baud COMMENTS
1 C.A15.14.01 2/15/2005 13A8 4800
2 C.A15.15.01 2/15/2005 3A9E 4800 Opt
3 C.A15.14.03 8/15/2007 98E1 4800
4 C.A15.15.03 8/15/2007 32D7 4800 Opt added p80,p81
5
6
7
8
9
10
Use ASCII page column for interfaces utilizing an ASCII XL Translator or MicroGateway to communicate to a chiller LINC
ENG ASCII GPIC York Talk ISN LINC York Talk N2 ENG
PAGE PAGE Object Point Descriptive Character Address POINT LIST CODE: S =STANDARD O =OPTIONAL N = NOT AVAILABLE PAGE
REF REF Type Type Text Position POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
P03 P01 A. Control ADF 1 Setpoint S S S S P03
P04 P02 A. Control ADF 2 ISN Current Limit S S S S P04
P05 P03 A. Control ADF 3 ISN Sound Limit ( RSL Option must be enabled or this point ignored) S S S S P05
P06 P04 A. Control ADF 4 P06
P07 P05 D. Control BD 1 Start / Stop Command S S S S P07
P08 P06 D. Control BD 2 P08
P09 P07 D. Control BD 3 P09
P10 P08 D. Control BD 4 History Buffer 1 Request S S S S P10
P11 P09 A. Monitor 8 - 11 ADF 5 Leaving Chilled Liquid Temp S S S S P11
P12 P10 A. Monitor 12 - 15 ADF 6 Return Chilled Liquid Temp S S S S P12
P13 P11 A. Monitor 16 - 19 ADF 7 VSD Internal Ambient Temp S S S S P13
P14 P12 A. Monitor 20 - 23 ADF 8 Sys 1 Suction Temperature S S S S P14
P15 P13 A. Monitor 24 - 27 ADF 9 Sys 1 Discharge Temperature S S S S P15
P16 P14 A. Monitor 28 - 31 ADF 10 Outside Ambient Air Temperature S S S S P16
P17 P15 A. Monitor 32 - 35 ADF 11 Sys 1 Oil Temperature S S S S P17
P18 P16 A. Monitor 36 - 39 ADF 12 Sys 1 Oil Pressure S S S S P18
P19 P17 A. Monitor 40 - 43 ADF 13 Sys 1 Suction Pressure S S S S P19
P20 P18 A. Monitor 44 - 47 ADF 14 Sys 1 Discharge Pressure S S S S P20
P21 P19 A. Monitor 48 - 51 ADF 15 Sys 1 Compressor % Full Load Amps S S S S P21
P22 P20 A. Monitor 52 - 55 ADF 16 Sys 1 Total Run Hours S S S S P22
P23 P21 A. Monitor 56 - 59 ADF 17 Sys 1 Total Number of Starts S S S S P23
P24 P22 A. Monitor 60 - 63 ADF 18 Sys 1 Highest Motor Temp S S S S P24
P25 P23 A. Monitor 64 - 67 ADF 19 Sys 2 Highest Motor Temp S S S S P25
P26 P24 A. Monitor 68 - 71 ADF 20 Sys 2 Oil Temperature S S S S P26
P27 P25 A. Monitor 72 - 75 ADF 21 Sys 2 Oil Pressure S S S S P27
P28 P26 A. Monitor 76 - 79 ADF 22 Sys 2 Suction Pressure S S S S P28
P29 P27 A. Monitor 80 - 83 ADF 23 Sys 2 Discharge Pressure S S S S P29
P30 P28 A. Monitor 84 - 87 ADF 24 Sys 2 Compressor % Full Load Amps S S S S P30
P31 P29 A. Monitor 88 - 91 ADF 25 Sys 2 Total Run Hours S S S S P31
P32 P30 A. Monitor 92 - 95 ADF 26 Sys 2 Total Number of Starts S S S S P32
P33 P31 A. Monitor 96 - 99 ADF 27 VSD Output Frequency S S S S P33
P34 P32 A. Monitor 100 - 103 ADF 28 Sys 1 Flash Tank Feed Valve % Open O O O O P34
P35 P33 A. Monitor 104 - 107 ADF 29 Sys 2 Flash Tank Feed Valve % Open O O O O P35
P36 P34 D. Monitor 108 BD 5 Chiller Run S S S S P36
P37 P35 D. Monitor 109 BD 6 Chiller Alarm S S S S P37
P38 P36 D. Monitor 110 BD 7 Evaporator Heater Status S S S S P38
P39 P37 D. Monitor 111 BD 8 Evaporator Pump Status S S S S P39
P40 P38 D. Monitor 112 BD 9 Sys 1 Compressor Run Status P40
P41 P39 D. Monitor 113 BD 10 Sys 2 Compressor Run Status S S S S P41
P42 P40 D. Monitor 114 BD 11 Sys 1 Economizer Solenoid Valve Status S S S S P42
Std. : See Latitude IOM FORM 101.21 -NM1 for all wiring instructions
Std. : added p80,p81
Revision: YCAV_YCIV Latitude (Rev J _02).xls Tab: YCAV_YCIV (1 & 2 Comps) Property of J ohnson Controls, York, PA Page: 1
4/11/2008
ENG ASCII GPIC York Talk ISN LINC York Talk N2 ENG
PAGE PAGE Object Point Descriptive Character Address POINT LIST CODE: S =STANDARD O =OPTIONAL N = NOT AVAILABLE PAGE
REF REF Type Type Text Position POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
P43 P41 D. Monitor 115 BD 12 Sys 2 Economizer Solenoid Valve Status S S S S P43
P44 P42 D. Monitor 116 BD 13 P44
P45 P43 D. Monitor 117 BD 14 P45
P46 P44 D. Monitor 118 BD 15 P46
P47 P45 D. Monitor 119 BD 16 P47
P48 P46 D. Monitor 120 BD 17 P48
P49 P47 D. Monitor 121 BD 18 P49
P50 P48 D. Monitor 122 BD 19 S1-1 Cooling Type: 0=Water, 1=Glycol S S S S P50
P51 P49 D. Monitor 123 BD 20 Local/Remote Control Mode: 0 =Local, 1 =Remote S S S S P51
P52 P50 D. Monitor 124 BD 21 Display Units Mode: 0 =Imperial, 1 =SI S S S S P52
P53 P51 D. Monitor 125 BD 22 P53
P54 P52 D. Monitor 126 BD 23 P54
P55 P53 D. Monitor 127 BD 24 P55
P56 P54 Code Monitor 128 ADI 1 *Sys 1 Operational Code S S S S P56
P57 P55 Code Monitor 129 ADI 2 *Sys 1 Fault Code S S S S P57
P58 P56 Code Monitor 130 ADI 3 *Sys 2 Operational Code S S S S P58
P59 P57 Code Monitor 131 ADI 4 *Sys 2 Fault Code S S S S P59
P60 P58 Code Monitor 132 ADI 5 Sys 1 Flash Tank Level (%) S S S S P60
P61 P59 Code Monitor 133 ADI 6 Sys 1 Condenser Fan Stages Running (0-6) S S S S P61
P62 P60 Code Monitor 134 ADI 7 Sys 2 Flash Tank Level (%) S S S S P62
P63 P61 Code Monitor 135 ADI 8 Sys 2 Condenser Fan Stages Running (0-6) S S S S P63
P64 P62 Code Monitor 136 ADI 9 Lead System Number S S S S P64
P65 P63 Code Monitor 137 ADI 10 Sys 1 & 2 Debug Code S S S S P65
P66 P64 A. Monitor 138 - 141 ADF 30 Local Leaving Chilled Liquid Setpoint S S S S P66
P67 P65 A. Monitor 142 - 145 ADF 31 Low Leaving Chilled Liquid Temp Cutout S S S S P67
P68 P66 A. Monitor 146 - 149 ADF 32 Sys 1 Flash Tank Drain Valve % Open S S S S P68
P69 P67 A. Monitor 150 - 153 ADF 33 Sys 2 Flash Tank Drain Valve % Open S S S S P69
P70 P68 A. Monitor 154 - 157 ADF 34 Low Suction Pressure Cutout S S S S P70
P71 P69 A. Monitor 158 - 161 ADF 35 VSD DC Bus Voltage S S S S P71
P72 P70 A. Monitor 162 - 165 ADF 36 Remote Leaving Chilled Liquid Setpoint S S S S P72
P73 P71 A. Monitor 166 - 169 ADF 37 Sys 1 Suction Superheat S S S S P73
P74 P72 A. Monitor 170 - 173 ADF 38 Cooling Range S S S S P74
P75 P73 A. Monitor 174 - 177 ADF 39 Sys 1 Discharge Superheat S S S S P75
P76 P74 A. Monitor 178 - 181 ADF 40 Sys 2 Suction Temperature S S S S P76
P77 P75 A. Monitor 182 - 185 ADF 41 Sys 2 Discharge Temperature S S S S P77
P78 P76 A. Monitor 186 - 189 ADF 42 Sys 2 Suction Superheat S S S S P78
P79 P77 A. Monitor 190 - 193 ADF 43 Sys 2 Discharge Superheat S S S S P79
P80 P78 D. Monitor 194 BD 25 Sys 1 Lockout N N S S P80
P81 P79 D. Monitor 195 BD 26 Sys 2 Lockout N N S S P81
P82 P80 D. Monitor 196 BD 27 P82
P83 P81 D. Monitor 197 BD 28 P83
P84 P82 D. Monitor 198 BD 29 P84
NOTE: The Appropriate Product Code Listing Summary Should Accompany Document
Revision: YCAV_YCIV Latitude (Rev J _02).xls Tab: YCAV_YCIV (1 & 2 Comps) Property of J ohnson Controls, York, PA Page: 2
4/11/2008
ENG ASCII Operational Code ENG ASCII Fault Code ENG ASCII Fault Code (cont.)
PAGE PAGE PAGE PAGE PAGE PAGE
P56,58 P54,56 C_OPER.CODE P57,59 P55,57 C_FAULT.CODE P57,59 P55,57 C_FAULT.CODE
63 63 Manual Override 1 1 Low Ambient Temperature 52 53 SPARE
64 64 Daily Schedule Shutdown 2 2 High Ambient Temperature 53 54 SPARE
65 65 Unit Switch OFF 3 3 Low Chilled Liquid Temperature 54 55 SPARE
66 66 Remote Controlled Shutdown 4 4 SPARE0 55 56 SPARE
67 67 Loss of External Communications 5 5 Low RTC Battery Voltage 56 57 SPARE
68 68 Flow Switch Shutdown 6 6 Invalid Number of Comp ressors Selected 57 58 SPARE
69 69 VSD Cooling Shutdown 7 7 VSD Communications Failure 58 59 SPARE
70 70 SPARE 8 8 Pre-charge Low DC Bus Voltage 59 60 SPARE
71 71 SPARE 9 9 Pre-charge DC Bus Voltage Imbalance 60 61 SPARE
72 72 SPARE 10 10 Bus Voltage High DC 61 62 SPARE
73 73 SPARE 11 11 Bus Voltage Low DC 62 62 SPARE
74 74 No Run Permissive 12 12 Voltage Imbalance DC Bus
75 75 Anti-Recycle Timer Active 13 13 High VSD Ambient Temperature
76 76 System Switch OFF 14 14 Phase Input Single
77 77 System Not Running 15 15 VSD Power Supply Fault
78 78 System Running 16 16 VSD Logic Board Fault
79 79 Discharge Pressure Limiting 17 17 Motor Current Overload (Hardware)
80 80 Suction Pressure Limiting 18 18 CT Plug Fault
81 81 Motor Current Limiting 19 19 SPARE
82 82 Motor Temperature Limiting 20 20 SPARE
83 83 ISN Motor Current Limiting 21 21 SPARE
84 84 Remote Motor Current Limiting 22 22 SPARE
85 85 System Pumping Down 23 23 SPARE
86 86 VSD PreCharging 24 24 SPARE
87 87 VSD Baseplate Temp Limiting 25 25 SPARE
88 88 VSD Internal Ambient Temp Limiting 26 26 SPARE
89 89 Sound Limiting 27 27 High Discharge Pressure (Software)
90 90 ISN Sound Limiting 28 28 High Differential Oil Pressure
91 91 Remote Sound Limiting 29 29 Low Differential Oil Pressure
92 92 Pulldown Motor Current Limiting 30 30 Low Suction Pressure
93 93 SPARE 31 31 High Discharge Temperature
94 94 SPARE 32 32 High Oil Temperature
95 95 SPARE 33 33 Low Suction Superheat
96 96 SPARE 34 34 Sensor Failure
35 35 Low Motor Current
36 36 High Motor Temperature
37 37 Pre-charge Low DC Bus Voltage
38 38 Pre-charge DC Bus Voltage Imbalance
39 39 High DC Bus Voltage
40 40 Low DC Bus Voltage
41 41 DC Bus Voltage Imbalance
42 42 High Motor Current
43 43 Motor Current Overload (Software)
44 44 IGBT Gate Driver Fault
45 45 High Baseplate Temperature
46 46 Single Phase Input
47 47 VSD Run Signal Fault
48 48 High Discharge Press (Hardware HPCO)
49 49 High Flash Tank Level
50 50 Control Voltage Fault
51 51 Low Discharge Superheat

Revision: YCAV_YCIV Latitude (Rev J _02).xls Tab: YCAV_YCIV (1 & 2 Comps) Property of J ohnson Controls, York, PA Page: 3
4/11/2008
This Page Intentionally Left Blank
Revision: YCAV_YCIV Latitude (Rev J _02).xls Tab: YCAV_YCIV (1 & 2 Comps) Property of J ohnson Controls, York, PA Page: 4
4/11/2008
YCAV/YCIV Latitude / 3rd, 4th Compressors (use with 1,2 list) YORK TALK 2 Microgateway / ELINK Micro Board: 031-02478-xxx
Item Ref. Version Date YORK P N Checksum Baud COMMENTS
1 C.A15.14.01 2/15/2005 13A8 4800
2 C.A15.15.01 2/15/2005 3A9E 4800 Opt
3 C.A15.14.03 8/15/2007 98E1 4800
4 C.A15.15.03 8/15/2007 32D7 4800 Opt added p80,p81
5
6
7
8
9 `
10
Use ASCII page column for interfaces utilizing an ASCII XL Translator or MicroGateway to communicate to a chiller LINC
ENG ASCII GPIC York Talk ISN LINC York Talk N2 ENG
PAGE PAGE Object Point Descriptive Character Address POINT LIST CODE: S =STANDARD O =OPTIONAL N = NOT AVAILABLE PAGE
REF REF Type Type Text Position POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
P03 P01 A. Control ADF 44 P03
P04 P02 A. Control ADF 45 P04
P05 P03 A. Control ADF 46 P05
P06 P04 A. Control ADF 47 P06
P07 P05 D. Control BD 30 P07
P08 P06 D. Control BD 31 P08
P09 P07 D. Control BD 32 P09
P10 P08 D. Control BD 33 P10
P11 P09 A. Monitor 8 - 11 ADF 48 Leaving Chilled Liquid Temp S S S S P11
P12 P10 A. Monitor 12 - 15 ADF 49 Return Chilled Liquid Temp S S S S P12
P13 P11 A. Monitor 16 - 19 ADF 50 VSD Internal Ambient Temp 2 S S S S P13
P14 P12 A. Monitor 20 - 23 ADF 51 Sys 3 Suction Temperature S S S S P14
P15 P13 A. Monitor 24 - 27 ADF 52 Sys 3 Discharge Temperature S S S S P15
P16 P14 A. Monitor 28 - 31 ADF 53 P16
P17 P15 A. Monitor 32 - 35 ADF 54 Sys 3 Oil Temperature S S S S P17
P18 P16 A. Monitor 36 - 39 ADF 55 Sys 3 Oil Pressure S S S S P18
P19 P17 A. Monitor 40 - 43 ADF 56 Sys 3 Suction Pressure S S S S P19
P20 P18 A. Monitor 44 - 47 ADF 57 Sys 3 Discharge Pressure S S S S P20
P21 P19 A. Monitor 48 - 51 ADF 58 Sys 3 Compressor % Full Load Amps S S S S P21
P22 P20 A. Monitor 52 - 55 ADF 59 Sys 3 Total Run Hours S S S S P22
P23 P21 A. Monitor 56 - 59 ADF 60 Sys 3 Total #of Starts S S S S P23
P24 P22 A. Monitor 60 - 63 ADF 61 Sys 3 Highest Motor Temp S S S S P24
P25 P23 A. Monitor 64 - 67 ADF 62 Sys 4 Highest Motor Temp S S S S P25
P26 P24 A. Monitor 68 - 71 ADF 63 Sys 4 Oil Temperature S S S S P26
P27 P25 A. Monitor 72 - 75 ADF 64 Sys 4 Oil Pressure S S S S P27
P28 P26 A. Monitor 76 - 79 ADF 65 Sys 4 Suction Pressure S S S S P28
P29 P27 A. Monitor 80 - 83 ADF 66 Sys 4 Discharge Pressure S S S S P29
P30 P28 A. Monitor 84 - 87 ADF 67 Sys 4 Compressor % Full Load Amps S S S S P30
P31 P29 A. Monitor 88 - 91 ADF 68 Sys 4 Total Run Hours S S S S P31
P32 P30 A. Monitor 92 - 95 ADF 69 Sys 4 Total #of Starts S S S S P32
P33 P31 A. Monitor 96 - 99 ADF 70 VSD Output Frequency 2 S S S S P33
P34 P32 A. Monitor 100 - 103 ADF 71 Sys 3 Flask Tank Feed Valve % Open O O O O P34
P35 P33 A. Monitor 104 - 107 ADF 72 Sys 4 Flask Tank Feed Valve % Open O O O O P35
P36 P34 D. Monitor 108 BD 34 P36
P37 P35 D. Monitor 109 BD 35 P37
P38 P36 D. Monitor 110 BD 36 P38
P39 P37 D. Monitor 111 BD 37 P39
P40 P38 D. Monitor 112 BD 38 Sys 3 Compressor Run Status P40
P41 P39 D. Monitor 113 BD 39 Sys 4 Compressor Run Status S S S S P41
P42 P40 D. Monitor 114 BD 40 Sys 3 Economizer Solenoid Valve Status S S S S P42
Std. : See Latitude IOM FORM 101.21 -NM1 for all wiring instructions
Std. : added p80,p81
Revision: YCAV_YCIV Latitude (Rev J _02).xls Tab: YCAV_YCIV (3 or 4 Comps) Property of J ohnson Controls, York, PA Page: 5
4/11/2008
ENG ASCII GPIC York Talk ISN LINC York Talk N2 ENG
PAGE PAGE Object Point Descriptive Character Address POINT LIST CODE: S =STANDARD O =OPTIONAL N = NOT AVAILABLE PAGE
REF REF Type Type Text Position POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
P43 P41 D. Monitor 115 BD 41 Sys 4 Economizer Solenoid Valve Status S S S S P43
P44 P42 D. Monitor 116 BD 42 P44
P45 P43 D. Monitor 117 BD 43 P45
P46 P44 D. Monitor 118 BD 44 P46
P47 P45 D. Monitor 119 BD 45 P47
P48 P46 D. Monitor 120 BD 46 P48
P49 P47 D. Monitor 121 BD 47 P49
P50 P48 D. Monitor 122 BD 48 P50
P51 P49 D. Monitor 123 BD 49 P51
P52 P50 D. Monitor 124 BD 50 P52
P53 P51 D. Monitor 125 BD 51 P53
P54 P52 D. Monitor 126 BD 52 P54
P55 P53 D. Monitor 127 BD 53 P55
P56 P54 Code Monitor 128 ADI 11 Sys 3 Operational Code S S S S P56
P57 P55 Code Monitor 129 ADI 12 Sys 3 Fault Code S S S S P57
P58 P56 Code Monitor 130 ADI 13 Sys 4 Operational Code S S S S P58
P59 P57 Code Monitor 131 ADI 14 Sys 4 Fault Code S S S S P59
P60 P58 Code Monitor 132 ADI 15 Sys 3 Flash Tank Level % S S S S P60
P61 P59 Code Monitor 133 ADI 16 Sys 3 Condenser Fan Stage ( 0-6 ) S S S S P61
P62 P60 Code Monitor 134 ADI 17 Sys 4 Flash Tank Level % S S S S P62
P63 P61 Code Monitor 135 ADI 18 Sys 4 Condenser Fan Stage ( 0-6 ) S S S S P63
P64 P62 Code Monitor 136 ADI 19 P64
P65 P63 Code Monitor 137 ADI 20 Sys 3 & 4 Debug Code S S S S P65
P66 P64 A. Monitor 138 - 141 ADF 73 P66
P67 P65 A. Monitor 142 - 145 ADF 74 P67
P68 P66 A. Monitor 146 - 149 ADF 75 Sys 3 Flash Tank Drain Valve % Open S S S S P68
P69 P67 A. Monitor 150 - 153 ADF 76 Sys 4 Flash Tank Drain Valve % Open S S S S P69
P70 P68 A. Monitor 154 - 157 ADF 77 P70
P71 P69 A. Monitor 158 - 161 ADF 78 VSD DC Bus Voltage 2 S S S S P71
P72 P70 A. Monitor 162 - 165 ADF 79 P72
P73 P71 A. Monitor 166 - 169 ADF 80 Sys 3 Suction Superheat S S S S P73
P74 P72 A. Monitor 170 - 173 ADF 81 P74
P75 P73 A. Monitor 174 - 177 ADF 82 Sys 3 Discharge Superheat S S S S P75
P76 P74 A. Monitor 178 - 181 ADF 83 Sys 4 Suction Temperature S S S S P76
P77 P75 A. Monitor 182 - 185 ADF 84 Sys 4 Discharge Temperature S S S S P77
P78 P76 A. Monitor 186 - 189 ADF 85 Sys 4 Suction Superheat S S S S P78
P79 P77 A. Monitor 190 - 193 ADF 86 Sys 4 Discharge Superheat S S S S P79
P80 P78 D. Monitor 194 BD 54 Sys 3 Lockout N N S S P80
P81 P79 D. Monitor 195 BD 55 Sys 4 Lockout N N S S P81
P82 P80 D. Monitor 196 BD 56 P82
P83 P81 D. Monitor 197 BD 57 P83
P84 P82 D. Monitor 198 BD 58 P84
NOTE: The Appropriate Product Code Listing Summary Should Accompany Document
Revision: YCAV_YCIV Latitude (Rev J _02).xls Tab: YCAV_YCIV (3 or 4 Comps) Property of J ohnson Controls, York, PA Page: 6
4/11/2008
ENG ASCII Operational Code ENG ASCII Fault Code ENG ASCII Fault Code (cont.)
PAGE PAGE PAGE PAGE PAGE PAGE
P56,58 P54,56 C_OPER.CODE P57,59 P55,57 C_FAULT.CODE P57,59 P55,57 C_FAULT.CODE
63 63 Manual Override 1 1 Low Ambient Temperature 52 53 SPARE
64 64 Daily Schedule Shutdown 2 2 High Ambient Temperature 53 54 SPARE
65 65 Unit Switch OFF 3 3 Low Chilled Liquid Temperature 54 55 SPARE
66 66 Remote Controlled Shutdown 4 4 SPARE0 55 56 SPARE
67 67 Loss of External Communications 5 5 Low RTC Battery Voltage 56 57 SPARE
68 68 Flow Switch Shutdown 6 6 Invalid Number of Comp ressors Selected 57 58 SPARE
69 69 VSD Cooling Shutdown 7 7 VSD Communications Failure 58 59 SPARE
70 70 SPARE 8 8 Pre-charge Low DC Bus Voltage 59 60 SPARE
71 71 SPARE 9 9 Pre-charge DC Bus Voltage Imbalance 60 61 SPARE
72 72 SPARE 10 10 Bus Voltage High DC 61 62 SPARE
73 73 SPARE 11 11 Bus Voltage Low DC 62 62 SPARE
74 74 No Run Permissive 12 12 Voltage Imbalance DC Bus
75 75 Anti-Recycle Timer Active 13 13 High VSD Ambient Temperature
76 76 System Switch OFF 14 14 Single Phase Input
77 77 System Not Running 15 15 VSD Power Supply Fault
78 78 System Running 16 16 VSD Logic Board Fault
79 79 Discharge Pressure Limiting 17 17 Motor Current Overload (Hardware)
80 80 Suction Pressure Limiting 18 18 CT Plug Fault
81 81 Motor Current Limiting 19 19 SPARE
82 82 Motor Temperature Limiting 20 20 SPARE
83 83 ISN Motor Current Limiting 21 21 SPARE
84 84 Remote Motor Current Limiting 22 22 SPARE
85 85 System Pumping Down 23 23 SPARE
86 86 VSD PreCharging 24 24 SPARE
87 87 VSD Baseplate Temp Limiting 25 25 SPARE
88 88 VSD Internal Ambient Temp Limiting 26 26 SPARE
89 89 Sound Limiting 27 27 High Discharge Pressure (Software)
90 90 ISN Sound Limiting 28 28 High Differential Oil Pressure
91 91 Remote Sound Limiting 29 29 Low Differential Oil Pressure
92 92 Pulldown Motor Current Limiting 30 30 Low Suction Pressure
93 93 SPARE 31 31 High Discharge Temperature
94 94 SPARE 32 32 High Oil Temperature
95 95 SPARE 33 33 Low Suction Superheat
96 96 SPARE 34 34 Sensor Failure
35 35 Low Motor Current
36 36 High Motor Temperature
37 37 Pre-charge Low DC Bus Voltage
38 38 Pre-charge DC Bus Voltage Imbalance
39 39 High DC Bus Voltage
40 40 Low DC Bus Voltage
41 41 DC Bus Voltage Imbalance
42 42 High Motor Current
43 43 Motor Current Overload (Software)
44 44 IGBT Gate Driver Fault
45 45 High Baseplate Temperature
46 46 Single Phase Input
47 47 VSD Run Signal Fault
48 48 High Discharge Press (Hardware HPCO)
49 49 High Flash Tank Level
50 50 Control Voltage Fault
51 51 Low Discharge Superheat



Revision: YCAV_YCIV Latitude (Rev J _02).xls Tab: YCAV_YCIV (3 or 4 Comps) Property of J ohnson Controls, York, PA Page: 7