Вы находитесь на странице: 1из 10

Drive Name: Master

Drive Address: 1
Driver Name: USB 1
The following parameters have been changed from default values:
ID Name Setup Current value Default value
2 Motor Speed Unit Setup 1 Hz RPM
2 Motor Speed Unit Setup 2 Hz RPM
2 Motor Speed Unit Setup 3 Hz RPM
2 Motor Speed Unit Setup 4 Hz RPM
10 Active Set-up Setup 1 Multi Set-up Set-up 1
10 Active Set-up Setup 2 Multi Set-up Set-up 1
10 Active Set-up Setup 3 Multi Set-up Set-up 1
10 Active Set-up Setup 4 Multi Set-up Set-up 1
20 Display Line 1.1 Small Setup 1 Adjusted Setpoint Reference [Unit]
20 Display Line 1.1 Small Setup 2 Speed [RPM] Reference [Unit]
21 Display Line 1.2 Small Setup 1 Motor Current Analog Input 53
21 Display Line 1.2 Small Setup 2 Power [kW] Analog Input 53
22 Display Line 1.3 Small Setup 1 Feedback 1 [Unit] Motor Current
24 Display Line 3 Large Setup 1 Pump Status Feedback [Unit]
100 Configuration Mode Setup 1 Closed Loop Open Loop
124 Motor Current Setup 1 130 142
124 Motor Current Setup 2 130 142
124 Motor Current Setup 3 130 142
124 Motor Current Setup 4 130 142
125 Motor Nominal Speed Setup 1 2975 1480
125 Motor Nominal Speed Setup 2 2975 1480
125 Motor Nominal Speed Setup 3 2975 1480
125 Motor Nominal Speed Setup 4 2975 1480
130 Stator Resistance (Rs) Setup 1 0.0416 0.0158
130 Stator Resistance (Rs) Setup 2 0.0172 0.0158
130 Stator Resistance (Rs) Setup 3 0.0172 0.0158
130 Stator Resistance (Rs) Setup 4 0.0172 0.0158
131 Rotor Resistance (Rr) Setup 1 0.0128 0.0145
131 Rotor Resistance (Rr) Setup 2 0.0158 0.0145
131 Rotor Resistance (Rr) Setup 3 0.0158 0.0145
131 Rotor Resistance (Rr) Setup 4 0.0158 0.0145
133 Stator Leakage Reactanc... Setup 1 0.1176 0.1626
133 Stator Leakage Reactanc... Setup 2 0.1776 0.1626
133 Stator Leakage Reactanc... Setup 3 0.1776 0.1626
133 Stator Leakage Reactanc... Setup 4 0.1776 0.1626
134 Rotor Leakage Reactance... Setup 1 0.1176 0.2342
134 Rotor Leakage Reactance... Setup 2 0.2558 0.2342
134 Rotor Leakage Reactance... Setup 3 0.2558 0.2342
134 Rotor Leakage Reactance... Setup 4 0.2558 0.2342
135 Main Reactance (Xh) Setup 1 4.845 6.1801
135 Main Reactance (Xh) Setup 2 6.7506 6.1801
135 Main Reactance (Xh) Setup 3 6.7506 6.1801
135 Main Reactance (Xh) Setup 4 6.7506 6.1801
139 Motor Poles Setup 1 2 4
139 Motor Poles Setup 2 2 4
139 Motor Poles Setup 3 2 4
139 Motor Poles Setup 4 2 4
151 Min Speed Normal Magnet... Setup 1 30 15
151 Min Speed Normal Magnet... Setup 2 30 15
151 Min Speed Normal Magnet... Setup 3 30 15
151 Min Speed Normal Magnet... Setup 4 30 15
155 V/f Characteristic - V Setup 1 5.4 2.2
173 Flying Start Setup 1 Enabled Disabled
181 Min Speed for Function ... Setup 1 6 3
181 Min Speed for Function ... Setup 2 6 3
181 Min Speed for Function ... Setup 3 6 3
181 Min Speed for Function ... Setup 4 6 3
302 Minimum Reference Setup 1 4 0
303 Maximum Reference Setup 1 10 1,500.00
303 Maximum Reference Setup 2 50 1,500.00
303 Maximum Reference Setup 3 50 1,500.00
303 Maximum Reference Setup 4 50 1,500.00
310 Preset Reference Setup 2 100 0
319 Jog Speed [RPM] Setup 1 600 300
319 Jog Speed [RPM] Setup 2 600 300
319 Jog Speed [RPM] Setup 3 600 300
319 Jog Speed [RPM] Setup 4 600 300
341 Ramp 1 Ramp Up Time Setup 1 60 90
341 Ramp 1 Ramp Up Time Setup 2 60 90
342 Ramp 1 Ramp Down Time Setup 1 60 180
342 Ramp 1 Ramp Down Time Setup 2 60 180
411 Motor Speed Low Limit [... Setup 1 2100 0
412 Motor Speed Low Limit [... Setup 1 35 0
413 Motor Speed High Limit ... Setup 1 3000 1500
413 Motor Speed High Limit ... Setup 2 3000 1500
413 Motor Speed High Limit ... Setup 3 3000 1500
413 Motor Speed High Limit ... Setup 4 3000 1500
416 Torque Limit Motor Mode Setup 1 135.6 139.1
416 Torque Limit Motor Mode Setup 2 140.5 139.1
416 Torque Limit Motor Mode Setup 3 140.5 139.1
416 Torque Limit Motor Mode Setup 4 140.5 139.1
453 Warning Speed High Setup 1 3000 1500
453 Warning Speed High Setup 2 3000 1500
453 Warning Speed High Setup 3 3000 1500
453 Warning Speed High Setup 4 3000 1500
510 Terminal 18 Digital Inp... Setup 1 Latched start Start
510 Terminal 18 Digital Inp... Setup 2 No operation Start
511 Terminal 19 Digital Inp... Setup 1 Stop inverse No operation
513 Terminal 29 Digital Inp... Setup 2 Start No operation
514 Terminal 32 Digital Inp... Setup 1 Set-up select bit 0 No operation
515 Terminal 33 Digital Inp... Setup 1 Set-up select bit 1 No operation
540 Function Relay Setup 1 Cascade Pump 2 No operation
540 Function Relay Setup 2 Cascade Pump 2 No operation
540 Function Relay Setup 3 Cascade Pump 2 No operation
540 Function Relay Setup 4 Cascade Pump 2 No operation
540.1 Function Relay Setup 1 Cascade Pump 3 No operation
540.1 Function Relay Setup 2 Cascade Pump 3 No operation
540.1 Function Relay Setup 3 Cascade Pump 3 No operation
540.1 Function Relay Setup 4 Cascade Pump 3 No operation
615 Terminal 53 High Ref./F... Setup 2 50 1,500.00
615 Terminal 53 High Ref./F... Setup 3 50 1,500.00
615 Terminal 53 High Ref./F... Setup 4 50 1,500.00
625 Terminal 54 High Ref./F... Setup 1 10 100
625 Terminal 54 High Ref./F... Setup 2 10 100
1443 Motor Cosphi Setup 1 0.76 0.82
1443 Motor Cosphi Setup 2 0.83 0.82
1443 Motor Cosphi Setup 3 0.83 0.82
1443 Motor Cosphi Setup 4 0.83 0.82
2002 Feedback 1 Source Unit Setup 1 bar
2002 Feedback 1 Source Unit Setup 2 bar
2012 Reference/Feedback Unit Setup 1 bar
2021 Setpoint 1 Setup 1 5.6 0
2021 Setpoint 1 Setup 2 5 0
2073 Minimum Feedback Level Setup 1 0 -999,999.00
2073 Minimum Feedback Level Setup 2 0 -999,999.00
2073 Minimum Feedback Level Setup 3 0 -999,999.00
2073 Minimum Feedback Level Setup 4 0 -999,999.00
2074 Maximum Feedback Level Setup 1 10 999,999.00
2074 Maximum Feedback Level Setup 2 10 999,999.00
2074 Maximum Feedback Level Setup 3 10 999,999.00
2074 Maximum Feedback Level Setup 4 10 999,999.00
2094 PID Integral Time Setup 1 0.1 8
2222 Low Speed Detection Setup 1 Enabled Disabled
2223 No-Flow Function Setup 1 Sleep Mode Off
2228 No-Flow Low Speed [RPM] Setup 1 2100 0
2229 No-Flow Low Speed [Hz] Setup 1 35 0
2240 Minimum Run Time Setup 1 20 60
2241 Minimum Sleep Time Setup 1 15 30
2242 Wake-up Speed [RPM] Setup 1 2100 0
2243 Wake-up Speed [Hz] Setup 1 35 0
2244 Wake-up Ref./FB Differe... Setup 1 5 10
2245 Setpoint Boost Setup 1 5 0
2246 Maximum Boost Time Setup 1 15 60
2285 Speed at Design Point [... Setup 1 3000 1500
2285 Speed at Design Point [... Setup 2 3000 1500
2285 Speed at Design Point [... Setup 3 3000 1500
2285 Speed at Design Point [... Setup 4 3000 1500
2500 Cascade Controller Setup 1 Basic Cascade Ctrl Disabled
2500 Cascade Controller Setup 2 Basic Cascade Ctrl Disabled
2500 Cascade Controller Setup 3 Basic Cascade Ctrl Disabled
2500 Cascade Controller Setup 4 Basic Cascade Ctrl Disabled
2504 Pump Cycling Setup 1 Enabled Disabled
2506 Number of Pumps Setup 1 3 2
2506 Number of Pumps Setup 2 3 2
2506 Number of Pumps Setup 3 3 2
2506 Number of Pumps Setup 4 3 2
2520 Staging Bandwidth Setup 1 5 10
2521 Override Bandwidth Setup 1 10 100
2523 SBW Staging Delay Setup 1 3 15
2524 SBW Destaging Delay Setup 1 1 15
2525 OBW Time Setup 1 8 10
2528 Stage Function Time Setup 1 5 15
2530 Destage Function Time Setup 1 10 15
2543 Destaging Threshold Setup 1 71 50
2584.1 Pump ON Time Setup 1 1 0
2584.1 Pump ON Time Setup 2 1 0
2584.1 Pump ON Time Setup 3 1 0
2584.1 Pump ON Time Setup 4 1 0
2584.2 Pump ON Time Setup 1 1 0
2584.2 Pump ON Time Setup 2 1 0
2584.2 Pump ON Time Setup 3 1 0
2584.2 Pump ON Time Setup 4 1 0
2901 Pipe Fill Speed [RPM] Setup 1 2100 0
2902 Pipe Fill Speed [Hz] Setup 1 35 0
2913 Derag Speed [RPM] Setup 1 2100 300
2913 Derag Speed [RPM] Setup 2 600 300
2913 Derag Speed [RPM] Setup 3 600 300
2913 Derag Speed [RPM] Setup 4 600 300
2914 Derag Speed [Hz] Setup 1 35 10
2924 Low Speed [RPM] Setup 1 2100 0
2925 Low Speed [Hz] Setup 1 35 0
2928 High Speed [RPM] Setup 1 2100 0
2929 High Speed [Hz] Setup 1 35 0
Drive Name: Slave 1
Drive Address: 1
Driver Name: USB 1
The following parameters have been changed from default values:
ID Name Setup Current value Default value
2 Motor Speed Unit Setup 1 Hz RPM
2 Motor Speed Unit Setup 2 Hz RPM
2 Motor Speed Unit Setup 3 Hz RPM
2 Motor Speed Unit Setup 4 Hz RPM
10 Active Set-up Setup 1 Multi Set-up Set-up 1
10 Active Set-up Setup 2 Multi Set-up Set-up 1
10 Active Set-up Setup 3 Multi Set-up Set-up 1
10 Active Set-up Setup 4 Multi Set-up Set-up 1
21 Display Line 1.2 Small Setup 1 Power [kW] Analog Input 53
24 Display Line 3 Large Setup 1 Speed [RPM] Feedback [Unit]
124 Motor Current Setup 1 130 142
124 Motor Current Setup 2 130 142
124 Motor Current Setup 3 130 142
124 Motor Current Setup 4 130 142
125 Motor Nominal Speed Setup 1 2975 1480
125 Motor Nominal Speed Setup 2 2975 1480
125 Motor Nominal Speed Setup 3 2975 1480
125 Motor Nominal Speed Setup 4 2975 1480
130 Stator Resistance (Rs) Setup 1 0.0372 0.0158
130 Stator Resistance (Rs) Setup 2 0.0172 0.0158
130 Stator Resistance (Rs) Setup 3 0.0172 0.0158
130 Stator Resistance (Rs) Setup 4 0.0172 0.0158
131 Rotor Resistance (Rr) Setup 1 0.0134 0.0145
131 Rotor Resistance (Rr) Setup 2 0.0158 0.0145
131 Rotor Resistance (Rr) Setup 3 0.0158 0.0145
131 Rotor Resistance (Rr) Setup 4 0.0158 0.0145
133 Stator Leakage Reactanc... Setup 1 0.1087 0.1626
133 Stator Leakage Reactanc... Setup 2 0.1776 0.1626
133 Stator Leakage Reactanc... Setup 3 0.1776 0.1626
133 Stator Leakage Reactanc... Setup 4 0.1776 0.1626
134 Rotor Leakage Reactance... Setup 1 0.1087 0.2342
134 Rotor Leakage Reactance... Setup 2 0.2558 0.2342
134 Rotor Leakage Reactance... Setup 3 0.2558 0.2342
134 Rotor Leakage Reactance... Setup 4 0.2558 0.2342
135 Main Reactance (Xh) Setup 1 4.3742 6.1801
135 Main Reactance (Xh) Setup 2 6.7506 6.1801
135 Main Reactance (Xh) Setup 3 6.7506 6.1801
135 Main Reactance (Xh) Setup 4 6.7506 6.1801
139 Motor Poles Setup 1 2 4
139 Motor Poles Setup 2 2 4
139 Motor Poles Setup 3 2 4
139 Motor Poles Setup 4 2 4
151 Min Speed Normal Magnet... Setup 1 30 15
151 Min Speed Normal Magnet... Setup 2 30 15
151 Min Speed Normal Magnet... Setup 3 30 15
151 Min Speed Normal Magnet... Setup 4 30 15
155 V/f Characteristic - V Setup 1 4.8 2.2
181 Min Speed for Function ... Setup 1 6 3
181 Min Speed for Function ... Setup 2 6 3
181 Min Speed for Function ... Setup 3 6 3
181 Min Speed for Function ... Setup 4 6 3
303 Maximum Reference Setup 1 50 1,500.00
303 Maximum Reference Setup 2 50 1,500.00
303 Maximum Reference Setup 3 50 1,500.00
303 Maximum Reference Setup 4 50 1,500.00
310 Preset Reference Setup 1 100 0
310 Preset Reference Setup 2 100 0
319 Jog Speed [RPM] Setup 1 600 300
319 Jog Speed [RPM] Setup 2 600 300
319 Jog Speed [RPM] Setup 3 600 300
319 Jog Speed [RPM] Setup 4 600 300
341 Ramp 1 Ramp Up Time Setup 1 60 90
342 Ramp 1 Ramp Down Time Setup 1 60 180
413 Motor Speed High Limit ... Setup 1 3000 1500
413 Motor Speed High Limit ... Setup 2 3000 1500
413 Motor Speed High Limit ... Setup 3 3000 1500
413 Motor Speed High Limit ... Setup 4 3000 1500
416 Torque Limit Motor Mode Setup 1 134.6 139.1
416 Torque Limit Motor Mode Setup 2 140.5 139.1
416 Torque Limit Motor Mode Setup 3 140.5 139.1
416 Torque Limit Motor Mode Setup 4 140.5 139.1
453 Warning Speed High Setup 1 3000 1500
453 Warning Speed High Setup 2 3000 1500
453 Warning Speed High Setup 3 3000 1500
453 Warning Speed High Setup 4 3000 1500
510 Terminal 18 Digital Inp... Setup 2 No operation Start
511 Terminal 19 Digital Inp... Setup 2 Stop inverse No operation
513 Terminal 29 Digital Inp... Setup 2 Latched start No operation
514 Terminal 32 Digital Inp... Setup 1 Set-up select bit 0 No operation
514 Terminal 32 Digital Inp... Setup 2 Set-up select bit 0 No operation
515 Terminal 33 Digital Inp... Setup 1 Set-up select bit 1 No operation
540 Function Relay Setup 1 Drive ready No operation
615 Terminal 53 High Ref./F... Setup 1 50 1,500.00
615 Terminal 53 High Ref./F... Setup 2 50 1,500.00
615 Terminal 53 High Ref./F... Setup 3 50 1,500.00
615 Terminal 53 High Ref./F... Setup 4 50 1,500.00
1443 Motor Cosphi Setup 1 0.74 0.82
1443 Motor Cosphi Setup 2 0.83 0.82
1443 Motor Cosphi Setup 3 0.83 0.82
1443 Motor Cosphi Setup 4 0.83 0.82
2285 Speed at Design Point [... Setup 1 3000 1500
2285 Speed at Design Point [... Setup 2 3000 1500
2285 Speed at Design Point [... Setup 3 3000 1500
2285 Speed at Design Point [... Setup 4 3000 1500
2913 Derag Speed [RPM] Setup 1 600 300
2913 Derag Speed [RPM] Setup 2 600 300
2913 Derag Speed [RPM] Setup 3 600 300
2913 Derag Speed [RPM] Setup 4 600 300
Drive Name: Slave 2
Drive Address: 1
Driver Name: USB 1
The following parameters have been changed from default values:
ID Name Setup Current value Default value
2 Motor Speed Unit Setup 1 Hz RPM
2 Motor Speed Unit Setup 2 Hz RPM
2 Motor Speed Unit Setup 3 Hz RPM
2 Motor Speed Unit Setup 4 Hz RPM
10 Active Set-up Setup 1 Multi Set-up Set-up 1
10 Active Set-up Setup 2 Multi Set-up Set-up 1
10 Active Set-up Setup 3 Multi Set-up Set-up 1
10 Active Set-up Setup 4 Multi Set-up Set-up 1
21 Display Line 1.2 Small Setup 1 Power [kW] Analog Input 53
24 Display Line 3 Large Setup 1 Speed [RPM] Feedback [Unit]
124 Motor Current Setup 1 134 142
124 Motor Current Setup 2 134 142
124 Motor Current Setup 3 134 142
124 Motor Current Setup 4 134 142
125 Motor Nominal Speed Setup 1 2975 1480
125 Motor Nominal Speed Setup 2 2975 1480
125 Motor Nominal Speed Setup 3 2975 1480
125 Motor Nominal Speed Setup 4 2975 1480
130 Stator Resistance (Rs) Setup 1 0.0398 0.0158
130 Stator Resistance (Rs) Setup 2 0.0167 0.0158
130 Stator Resistance (Rs) Setup 3 0.0167 0.0158
130 Stator Resistance (Rs) Setup 4 0.0167 0.0158
131 Rotor Resistance (Rr) Setup 1 0.0139 0.0145
131 Rotor Resistance (Rr) Setup 2 0.0153 0.0145
131 Rotor Resistance (Rr) Setup 3 0.0153 0.0145
131 Rotor Resistance (Rr) Setup 4 0.0153 0.0145
133 Stator Leakage Reactanc... Setup 1 0.1075 0.1626
133 Stator Leakage Reactanc... Setup 2 0.1723 0.1626
133 Stator Leakage Reactanc... Setup 3 0.1723 0.1626
133 Stator Leakage Reactanc... Setup 4 0.1723 0.1626
134 Rotor Leakage Reactance... Setup 1 0.1075 0.2342
134 Rotor Leakage Reactance... Setup 2 0.2482 0.2342
134 Rotor Leakage Reactance... Setup 3 0.2482 0.2342
134 Rotor Leakage Reactance... Setup 4 0.2482 0.2342
135 Main Reactance (Xh) Setup 1 4.7924 6.1801
135 Main Reactance (Xh) Setup 2 6.549 6.1801
135 Main Reactance (Xh) Setup 3 6.549 6.1801
135 Main Reactance (Xh) Setup 4 6.549 6.1801
139 Motor Poles Setup 1 2 4
139 Motor Poles Setup 2 2 4
139 Motor Poles Setup 3 2 4
139 Motor Poles Setup 4 2 4
151 Min Speed Normal Magnet... Setup 1 30 15
151 Min Speed Normal Magnet... Setup 2 30 15
151 Min Speed Normal Magnet... Setup 3 30 15
151 Min Speed Normal Magnet... Setup 4 30 15
155 V/f Characteristic - V Setup 1 5.3 2.2
181 Min Speed for Function ... Setup 1 6 3
181 Min Speed for Function ... Setup 2 6 3
181 Min Speed for Function ... Setup 3 6 3
181 Min Speed for Function ... Setup 4 6 3
303 Maximum Reference Setup 1 50 1,500.00
303 Maximum Reference Setup 2 50 1,500.00
303 Maximum Reference Setup 3 50 1,500.00
303 Maximum Reference Setup 4 50 1,500.00
310 Preset Reference Setup 1 100 0
310 Preset Reference Setup 2 100 0
319 Jog Speed [RPM] Setup 1 600 300
319 Jog Speed [RPM] Setup 2 600 300
319 Jog Speed [RPM] Setup 3 600 300
319 Jog Speed [RPM] Setup 4 600 300
341 Ramp 1 Ramp Up Time Setup 1 60 90
342 Ramp 1 Ramp Down Time Setup 1 60 180
413 Motor Speed High Limit ... Setup 1 3000 1500
413 Motor Speed High Limit ... Setup 2 3000 1500
413 Motor Speed High Limit ... Setup 3 3000 1500
413 Motor Speed High Limit ... Setup 4 3000 1500
416 Torque Limit Motor Mode Setup 1 135.3 139.1
416 Torque Limit Motor Mode Setup 2 140.3 139.1
416 Torque Limit Motor Mode Setup 3 140.3 139.1
416 Torque Limit Motor Mode Setup 4 140.3 139.1
453 Warning Speed High Setup 1 3000 1500
453 Warning Speed High Setup 2 3000 1500
453 Warning Speed High Setup 3 3000 1500
453 Warning Speed High Setup 4 3000 1500
510 Terminal 18 Digital Inp... Setup 2 No operation Start
511 Terminal 19 Digital Inp... Setup 2 Stop inverse No operation
513 Terminal 29 Digital Inp... Setup 2 Latched start No operation
514 Terminal 32 Digital Inp... Setup 1 Set-up select bit 0 No operation
514 Terminal 32 Digital Inp... Setup 2 Set-up select bit 0 No operation
515 Terminal 33 Digital Inp... Setup 1 Set-up select bit 1 No operation
540 Function Relay Setup 1 Drive ready No operation
615 Terminal 53 High Ref./F... Setup 1 50 1,500.00
615 Terminal 53 High Ref./F... Setup 2 50 1,500.00
615 Terminal 53 High Ref./F... Setup 3 50 1,500.00
615 Terminal 53 High Ref./F... Setup 4 50 1,500.00
1443 Motor Cosphi Setup 1 0.75 0.82
1443 Motor Cosphi Setup 2 0.83 0.82
1443 Motor Cosphi Setup 3 0.83 0.82
1443 Motor Cosphi Setup 4 0.83 0.82
2285 Speed at Design Point [... Setup 1 3000 1500
2285 Speed at Design Point [... Setup 2 3000 1500
2285 Speed at Design Point [... Setup 3 3000 1500
2285 Speed at Design Point [... Setup 4 3000 1500
2913 Derag Speed [RPM] Setup 1 600 300
2913 Derag Speed [RPM] Setup 2 600 300
2913 Derag Speed [RPM] Setup 3 600 300
2913 Derag Speed [RPM] Setup 4 600 300
3081 Brake Resistor (ohm) Setup 1 7 6.6
3081 Brake Resistor (ohm) Setup 2 7 6.6
3081 Brake Resistor (ohm) Setup 3 7 6.6
3081 Brake Resistor (ohm) Setup 4 7 6.6