BATTERY CALCULATION WORKSHEET (132kV , 110V DC)
(1)
Period
(6)
Kt
Factor
(7)
Temp
Derating
Factor
(8)
Required
section
Size
(3) x (6) x (7)
= Rated Ah
Section 1 - First 1 Periods Only - If A2 > A1, go to section 2 - No
1 A1 = 53.05 A1-0 = 53.05 M1 = 360.00 t=M1 = 360.00 6.44 1.12 382.64
TOTAL 382.64
Section 2 - First 2 Periods Only - If A3 > A2, go to section 3 - Yes
Section 3 - First 3 Periods Only - If A4 > A3, go to section 4 - No
1 A1 = 53.05 A1-0 = 53.05 M1 = 360.00 t=M1+..M3 = 599.00 9.89 1.12 587.62
2 A2 = 46.5 A2-A1 = -6.55 M2 = 238.98 t=M2+M3 = 239.00 4.66 1.15 -35.10
3 A3 = 242.7 A3-A2 = 196.2 M3 = 0.02 t=M3 = 0.02 0.77 1.33 200.93
TOTAL 753.45
Section 4 - First 4 Periods Only - If A5 > A4, go to section 5 - No
1 A1 = 53.05 A1-0 = 53.05 M1 = 360.00 t=M1+..M4 = 600.00 9.9 1.12 588.22
2 A2 = 46.5 A2-A1 = -6.55 M2 = 238.98 t=M2+..M3 = 240.00 4.67 1.15 -35.18
3 A3 = 242.7 A3-A2 = 196.2 M3 = 0.02 t=M3+M4 = 1.02 0.92 1.32 238.27
4 A4 = 63.9 A4-A3 = -178.8 M4 = 1.00 t=M4 = 1.00 0.92 1.32 -217.13
TOTAL 574.17
Random Equipment Load Only (if needed)
R AR = AR-0 = MR = t = MR = 0.00
Maximum Section Size 753.45 = Uncorrected Size 753.45
Uncorrected Size x Design Margin x Aging factor = 979.49 Ah
Design Margin = 1.00
Aging Factor = 1.30
When the cell size is greater than a standard cell size , the next larger cell is required.
The required cell size is = 979 Ah Therefore cell LB1020P is required
(4)
Duration
of
periods
(Minutes)
+ Random size 0
(3)
change
in
Load
(Amperes)
(5)
End
of
section
(Min)
(2)
Load
(Amperes)
110V DC Battery calc Page 1 of 1