The document is a single line diagram for a 210 MW generator. It shows the electrical components and connections of the generator, including the 230kV main and transfer buses, generator transformer, unit auxiliary transformers, 6.6kV unit buses, and various protection and metering circuits. It provides details on the ratings and connections of components like circuit breakers, current transformers, potential transformers, relays, and other electrical equipment in the generator and switchyard.
The document is a single line diagram for a 210 MW generator. It shows the electrical components and connections of the generator, including the 230kV main and transfer buses, generator transformer, unit auxiliary transformers, 6.6kV unit buses, and various protection and metering circuits. It provides details on the ratings and connections of components like circuit breakers, current transformers, potential transformers, relays, and other electrical equipment in the generator and switchyard.
The document is a single line diagram for a 210 MW generator. It shows the electrical components and connections of the generator, including the 230kV main and transfer buses, generator transformer, unit auxiliary transformers, 6.6kV unit buses, and various protection and metering circuits. It provides details on the ratings and connections of components like circuit breakers, current transformers, potential transformers, relays, and other electrical equipment in the generator and switchyard.
230 kV Main Bus 2 89A 89B 89C 89D 89E2 89E3 C V T 52 89E1 C C S2 S1 Switch Yard Transformer Bay C C S2 S1 C C S2 S1 S2 C C S1 S2 C C S1 C C C C S2 S1 S2 S1 S LA PT LA C C 6.6kV Unit Bus 1B 3B 4 6.6 kV Unit Bus 1A 3A 4 SINGLE LINE DIAGRAM FOR 210 MW GENERATOR Generator Rotor SES Unit Auxiliary Transformer-B Unit Auxiliary Transformer-A Generator- Transformer Excitation Transformer TS-2/Elec. O&A Controls& Battery Division Drawing No.: GRP-1/CWD Sheet No.:1 NGR NGR NGR NGT PT PT C C C S1 S2 230 kV Main Bus 1 230 kV Transfer Bus 230 kV Main Bus 2 89A 89B 89C 89D 89E1 89E2 89E3 U V W Phase Rotation P1 P1 P2 P2 C C S2 S1 C C S2 S1 C C S2 S1 C C S2 S1 C C S2 S1 C C C S2 S1 C C C S1 S2 C C C S1 S2 800/1A, PS Class, K : 1200 V R : 6 , Im: 60 mA@K /2 PV CT PV ] * V * Core-3: To gen.Transf. O/A Diff. Protec. Relay 38 38 800/1A, 5P20, 30 VA ALF:20 Core-2: To gen.Transf. B/U LBB, REF Protec. Relay 27/46 800/1A, 0.5 Class, 30 VA, Isf: 5 ] Core-1: To Metering & Instruments 1200/1A, PS Class, K : 750 V R : 8 , Im: 40 mA@K /2 PV CT PV ] * V * 1200/1A, PS Class, K : 750 V R : 8 , Im: 40 mA@K /2 PV CT PV ] * V * Core-4: To Bus Bar Diff. Protec. Relay Core-5: 38 LA CVT 150VA, 0.5 Cl. To Sync. Circuit in GCPP 230kV P3 115V P3 } BCT To Temp. Indication & Protection Circuit Sw. Yd. Tr. Bay Genr. Tr.#1 3 250 MVA, 240/15kV 14% Imped., Yd1 OLTC- 10% in steps of 1.25% 4 6 From Genr.:1 3 4 21 To GT REF Relay To GT St. By E/F Relay Core-2 Core-1 Ratio: 800/1A Class: PS K : 1200 V Im: 30 mA@K /2 PV PV ] * Ratio: 800/1A Class: 5P Burden: 30 VA ALF: 20 CT Circuits of 230 kV side of Generator-Transformer TS-2/Elec. O&A Controls& Battery Division Drawing No.: GRP-1/CWD, Sheet No.: 3 52 Sh. No. Ratio: 800/1A Class: 5P Burden: 30 VA ALF: 20 750/5A, PS Cl. K 600V, R 1.5 Im 175mA@K /2 PV CT PV ] * V * U V W Phase Rotation To Genr. Tr.:1 3 4 PT-1 PT-2 PT-3 15kV P3 110V P3 15kV P3 110V P3 Class: 0.2 Burden:75VA Class: 0.2 Burden: 75 VA PT-2 3 4 LA H T F u s e Disc. Link Disc. Link Disc. Link Disc. Link Disc. Link Disc. Link Core-8 10000/5A, PS Cl. K 450V,R 5 I 30mA@K /2 PV CT m PV ] * V * 23 Core-9 10000/5A, PS Cl. K 450V, R 5 Im 30mA@K /2 PV CT PV ] * V * 44 Genr. Diff. Core-2 10000/5A, PS Cl. K 450V, R 5 Im 30mA@K /2 PV CT PV ] * V * C C S2 S1 C C S2 S1 C C S2 S1 C C S2 S1 C C S2 S1 C C S2 S1 44 Genr. Diff. Core-1 10000/5A, PS Cl. K 1400V, R 5 Im 75mA@K /2 PV CT PV ] * V * 10000/5A, PS Cl. K 1400V, R >5 Im 75mA@K /2 PV CT PV ] V * 2800/5A, PS Cl. K 750V,R 2 Im 100mA@K /2 PV CT PV ] * V * 2800/5A, PS Cl. K 750V, R 2 Im 100mA@K /2 PV CT PV ] * V * 10000/5A, PS Cl. K 1400V, R 5 Im 75mA@K /2 PV CT PV ] * V * C C S2 S1 38 38 36 36 38 GT O/A Diff. O/A Diff. UAT-B Diff. UAT-A Diff. O/A Diff. Core-4 10000/5A, PS Cl. K 900V,R 5 Im 30mA@K /2 PV CT PV ] * V * C C C C S2 S2 S1 S1 59/63 Fld.Fail,O/L Neg.Seq,P/S Core-7 Core-10A 10000/5A,0.5 Cl. 100 VA Burden Metering Core-10B 74 56 750/5A,5P20 Cl. 30 VA Burden B/U Prot. Core-13B Core-13A 1500/1A,PS Cl. 15 VA Burden 1500/1A,PS Cl. 15 VA Burden 1500/1A, 5P10 Cl. 15 VA Burden 1500/1A,5P10 Cl. 15 VA Burden Core-11B Core-14B Core-14A Core-12B Core-15B Core-15A Core-11A Core-12B 36 36 750/5A, PS Cl. K 600V, R 1.5 Im 175mA@ K /2 PV CT PV ] * V * Diff. Prot. O/C Prot. O/C Prot. Diff. Prot. 74 750/5A,5P20 Cl. 30 VA Burden S2 S2 C C C C S1 S1 S2 S2 C C C C S1 S1 S2 S2 C C C C S1 S1 B/U Prot. Core-6 10000/5A,0.2 Cl. 50 VA Burden To AVR Core-3 10000/5A,0.2 Cl. 50 VA Burden C C C C S2 S2 S1 S1 Rev.P,Load Drop Antic Accpt Test Core-5 10000/5A,0.2 Cl. 50 VA Burden C C C C S2 S2 S1 S1 C C S2 S1 CC CC S2 S2 S1 S1 C C S2 S1 Lo Forw.& Rev. Pwr Genr.B/P Imped. 70/25 21/61 P2 P2 P2 P2 P2 P2 P1 P1 P1 P1 P1 P1 Gen#1 3,50Hz,3 210MW,247MVA 3000RPM,98.7% 15kV 5%,9507A 4 f h 6 63 NGT-40kVA (Cont.) 15kV/240V, 50Hz Taps- 5% in Steps of 2.5% 6 42/76 NGR-1.638 240V/ with 15% in steps of 1.25% W 6 P3 St. E/F C C C C C C S2 S2 S1 S1 Metering Ckt. Metering Ckt. BCT BCT Temp. Indicator Temp. Indicator 6.6kV Unit Bus 1B 3B 4 6.6 kV Unit Bus 1A 3A 4 TS-2/Elec. O&A/Controls& Battery Division Drawing No.: GRP-1/CWD/Sheet No.: 5 6.6kV/110 V PT 6.6kV/110 V PT Excitation Trnsfmr. Rotor E/F 3W 3W UAT #1B 3B 16MVA,3 ,50Hz Dy11,15/6.9kV Offload Taps 5% in steps of 2.5% 4 F 6 6 UAT #1A 3A 16MVA,3 ,50Hz Dy11,15/6.9kV Offload Taps 5% in steps of 2.5% 4 F 6 6 To Sheet 7 To Sheet 7 To Sheet 7 S CT / PT Circuits of Generator & Unit Auxiliary Transformers 15kV P3 110V P3 Genr. PT #2:75 VA, 0.2 Class Connec.: Genr. PT #1: 200 VA, 0.5 Class 15kV P3 110V P3 Connec.: Genr. PT #3: 75 VA, 0.2 Class 15kV P3 110V P3 Connec.: TB-17 Disconnecting Type TB To Voltage Balance Relay Circuit 17 To Voltage Balance Relay Circuit 17 To Voltage Balance Relay Circuit 17 59 63 63 70 42 52 54 76 21 30 23 40 To Genr. Control panel metering GCP-12-98,99,100,101 25 27 29 31 26 28 30 32 Fuses-4A 1 1 2 2 3 3 4 E371 E372 E351 E352 E331 E332 E311 E312 FS-311 FS-312 FS-313 LK-314 Fuses-6.3A 21 22 23 24 TB-1 TB-2 13 15 17 19 20 18 16 14 Fuses-4A 5 9 6 10 7 11 8 E271 E272 E251 E252 E231 E232 E211 E212 FS-211 FS-212 FS-213 LK-214 Fuses-6.3A 9 10 11 12 TB-1 TB-2 5 6 7 8 Fuses-4A 9 10 5 11 6 12 7 E171 E172 E151 E152 E131 E132 E111 E112 FS-111 FS-112 FS-113 LK-114 Fuses-6.3A 1 2 3 4 TB-1 TB-2 To Load Drop Anticipator Low Forward Power Protn. Reverse Power Protection Reverse Power Protection Genr. Pole Slip Protn. Backup Imp. Protn. Under Freq. Protn. Over Voltage Protn. Stator Main E/F Protn. Stator St.by E/F Protn. Over Flux Protn. Field Failure Protn. Stator E/F Protn. To Static Excitation Panels } } } } V1 V2 V3 Discon. Link From Generator Phase side LA PT Circuits of Generator TS-2/Elec. O&A/Controls& Battery Division Drawing No.: GRP-1/CWD/Sheet No.: 7 DAS Spare TB.17 TB.17 TB.17 FS-6 FS-3 FS-9 FS-7 FS-4 FS-10 FS-8 FS-5 FS-11 Lk5 Lk3 Lk7 A A A B B B C C C N N N To Cla.C Prot. Circuit To Closing & Trip Coil-1 To Cla.A Prot Circuit To Bus Isolators To 6.6kV Change over Scheme 84 34 13 80 19 To Tr. Bus Iso. & E/Sw. To Cla.B Prot. Circuit To Trip Coil-2 To Cla.A Prot. Circuit To OTI/WTI 48/66 13 78 68 Source-1 Source-2 21 22 J51 FS51 J53 J55 J52 FS52 J54 J56 J71 FS71 J73 J75 J72 FS72 J74 J76 IP2 IP1 5P3 1P1 4P3 5P4 1P2 4P4 IP2 IP1 2P3 2P4 IP4 IP3 5P1 2P1 4P1 5P2 2P2 4P2 IP4 IP3 IP3 IP4 + + - - DCS-1 DCS-3 DCS-2 O F F O F F O N O N 1 6 A 1 6 A SL1 SL2 4kW 4kW S o u r c e - 1 S o u r c e - 2 I n d e p e n d e n t PB-1 80A J1A 9 10 B52 B51 J1 J2 J3 J4 TB13/14 TB13/15 TB13/16 TB13/13 J3A 80B 9 10 PB-2 B53 B54 G r o u p - B G r o u p - A FS-55 FS-65 FS-53 FS-63 FS-69 FS-59 FS-67 FS-73 FS-57 FS-56 FS-66 FS-54 FS-64 FS-70 FS-60 FS-68 FS-74 FS-58 K421 K422 K201 K202 K401 K402 J5A J6A 13/17 13/19 13/17 13/19 J5B J6B K411 K412 K601 K602 J70 J80 K431 K432 To GCDP Syn.& GRP SKE Relay To LBB Protn.& Aux. Relay FS-61 FS-62 K549 K550 FS-71 FS-72 K13 K352 220 Volts DC Distribution Scheme Original TS-2/Elec. O&A/Controls& Battery Division Drawing No.: GRP-1/CWD/Sheet No.: 9 80A T B 2 2 L101 L201 3 4 B35 21 22 L201 L202 3 4 C35 23 24 80B To Ann. Circuit } 1 2 80B T B 1 3 H19 H19A 1 2 80A H17 H18 7 8 9 10 S p a r e } All Fuses are 6A rated 23 24 T B 1 3 T B 1 3 200 ms. TDDO 200 ms. TDDO 4A Panel-1 Panel-3 Panel-1 Panel-3 Panel-3 Panel-3 (+) (+) (--) (--) 4A I i I i I i I i I iIiI i I i I i I i I i I i I i I i I i I iIiI i I i I i I i I i 3 4 H1 Phase H2 IP2 IP1 IP4 IP3 ACS-1 O F F O N Neutral H3 H4 H5 H6 H11 H12 H7 H9 1 2 Dr.Sw. HS PSS Cab. ll. I Th. Heater P. Socket H11A FS21 FS22 Lk21 Lk22 ACS-1 Supply Source Unit III II I SHP Feeder 8 8 8 10 3 4 ACS-2 Supply Source Unit III II I Feeder 2 2 2 240 V, 50 Hz 16A 2A 11 12 H51 H52 IP2 IP1 IP4 IP3 ACS-2 O F F O N TB.13 Panel-3 TB.3 Panel-1 4kW Phase Neutral SL-3 FS-23 LK-23 FS-24 LK-24 FS-25 FS-26 A1 A2 a1 a2 H53 H54 H55 H56 H57 H58 H13 H14 H15 H16 2A 2A 4A 4A To U/F Timer To Rotor E/F 9 10 80AC 415/240 V 25 VA 80AC T B 2 3 L181 L281 1 2 33 34 U203 U204 3 4 27 28 80AC Spare TS-2/Elec. O&A/Controls& Battery Division Drawing No.: GRP-1/CWD/Sheet No.: 11 AC Distribution Scheme (Cubicle Illumination, Heater & Power Socket Circuits) I i I i I i I i I i I iIiIiIiIiI i I I i I i I i I i Location at TG 13.5 Level m Col. E 55 Col. E 21 Col. E 14 (The above Transformer is not used) 220 Volts, UPS 56 30 Location Inside UCR behind Siemenns ICUFO1 panel Inside UCR behind Siemenns 2CDAO1 panel Outside UCR near column E23 T T N N I I N N ByP ByP N T N T M O A A M O A O M Generator Breaker Control Circuit; T B . 1 9 / 3 E20 W31 W32 U30 U34 U29 U33 GCDP GCDP GCDP GCDP K5/GCDP GCDP GCDP GCDP GCDP GCDP GCDP AT T AC C 52CS AT T AC C 52CS AT T AC C 52CS E24 43CS 43CS V7 W23 K193 K195(BT) 3.9 4.10p 3.10p 3.10 6TBr. 1K195 89TRA 89TRB 3k143 K143(BT) T5 T6 89TRC 51 56 5k145 52TR-A 52TR-B 52TR-C K151(BT) 53 53 53 51 51 58 K149(BT) (BT) k147 32k151 3T8T K197 W21 GCDP V5 GCDP 16K197 T5 89D T6 17 GCDP V23 V74 V75 SS V77 V76 25G 25X St.Ex.panel SS V70 V12 V3 k W19 59 V72 V73 V71 E22 19/TB.19 20 TB.19 E18 96GT 50LLBx 19 195C 95C 86T4 K4 K3 K2 K1 K 4 A K 4 B TB.18/2 K 1 A 19 20 38 38 37 37 86G3 86GB 30 29 89E2 89E2 T17 T17 T18 T8 T8 T18 89E1 89E1 T17 T7 20 90 K169 167 168 169 165 4-32 4-3 4-31 166 V15 V16 95A 195A 95B 195B 95C 195C 32GX 32GX 86GB 86GB 86G1 86G1 86G2 86G2 1 3 2 4 19 21 20 22 15 17 15 17 11 11 12 12 16 18 16 18 95A 195A 95B 195B 17 17 18 K75 K76 4KW 4KW K16A K102A K3A K39A K91A K95A TB.18 TB.19 TB.18 TB.18 16 30 3 21 26 27 4-4 4-12 4-2 4-8 400 MS TDDO 400 MS TDDO LK 5A LK 6A T B . 1 9 / 1 T B . 1 9 / 8 TB.19/4 T B . 1 9 / 1 6 T B . 1 9 / 1 8 K 602 K
6 0 1 K 202 K
2 0 1 18 4-17 TB.19/18 4-11 9 10 4-9 R 95 R 195 TB.19/17 TB.19/4 4-10 12 21 19 16 15 11 20 13 14 18 8 17 K15 Rem. Closing J3 Local Closing K25 Local Tripping K5 Rem. Tripping K3 Protn. Tripping K91 Trip Ckt. Sup. K2 Neg. Terminal K11 Lc.Trp. K13 Rem. Tripping K39 Protn. Tripping K93 Trip Ckt. Sup. K16 Neg. Terminal C i r c u i t
B r e a k e r
I n t e r n a l D e t a i l s TB.20/25 TB.20/26 L170 L270 95C To Ann.TC1 Fault (B35) TB.20/27 TB.20/28 L171 L271 195C To Ann.TC2 Fault (C35) Elec. O&A/Controls&Battery/St.-1GRP/Sheet No.: 13 82 63 19 34 48 82 K102 K16 K15 T N I 43CS T N I 43CS 43CS T T N N I I 43CS (Guard Realy) (Ch.Syn. Relay) Sh. No.: TB5 TB6 TB18/1 TB18/15 TB18/29 TB18/14 TB18/28 / / (Rev. Flag) (Rev. Flag) K101 K101A 12 21 19 16 15 13 14 18 8 17 Remote Closing J3 Local Closing K25 Local Tripping K5 Rem.Man. Tripping K3 Protn. Tripping K91 Trip Ckt. Sup. K2 Neg. Terminal K11 Local Tripping K13 Rem. Tripping K39 Protn. Tripping K93 Trip Ckt. Sup. 52 CC 94 M2 Local Remote K1 K15 K23 K17 K21 K27 K29 K33 52b-2 52 a-2 PBS-1 PBS-2 52 a-1 52 b-1 52 a-3 52 b-3 52 TC1 52 TC2 K4 K8 K45 K25 K5 PBS-3 K11 K43 K3 K91 K39 K93 M2 L1 H12 L i m i t
S w i t c h A s s e m b l y M M6 M4 Motor Starter FS-e M1 H11 M5 M3 FS-c FS-a CFS-17 CFS-18 LK-a H1 J9 J10 H2 H3 H4 H5 H6 HEATER P. Socket H9 Lamp Holder FS-b FS-d J4 Gr.-A Neg. Spring Charge Indication K2 K16 K71 K73 Gr.-A Gr.-B Neg. Neg. Rem. Spring Ch. Ind. 43A 11 20 11 C i r c u i t
B r e a k e r
I n t e r n a l
D e t a i l s Generator Breaker Local Panel Circuits 94 94 (Anti- Pumping Relay) A u x i l i a r y C o n t a c t s (From 3) J (From 4) J 220 V DC Spring Ch. Motor AC Single phase Supply Generator Breaker Auto Trip Indication 19B K41 K7 K5 K6 52b 52b2 L13 L9 L22 L23 U45 U 4 7 U 2 2 U46 U48 U23 3-23 3-25 3 4 3-24 3-26 3-22 AT T AC AC C 52CS AT T C 52CS 5 1 6 2 11 9 12 10 C1 C2 C1-1 C2-1 C1-2 GB Auto Trip Ind. TB3/36 TS-2/Elec. O&A/Controls & Battery Division Drawing No.: GRP-1/CWD/Sheet No.: 15 I i I i I i I i I iIiI i I i I i I i I i I i I i I i I i I iIiI i I i I i I i I i I i I i I i I i I iIiI i I i I i I i I i To Cla.C Prot. Circuit To Closing & Trip Coil-1 To Cla.A Prot Circuit To Bus Isolators To 6.6kV Change over Scheme 84 34 13 80 19 To Tr. Bus Iso. & E/Sw. To Cla.B Prot. Circuit To Trip Coil-2 To Cla.A Prot. Circuit To OTI/WTI 48/66 13 78 68 Source-1 Source-2 21 22 J51 FS51 J53 J55 J52 FS52 J54 J56 J71 FS71 J73 J75 J72 FS72 J74 J76 IP2 IP1 5P3 1P1 4P3 5P4 1P2 4P4 IP2 IP1 2P3 2P4 IP4 IP3 5P1 2P1 4P1 5P2 2P2 4P2 IP4 IP3 IP3 IP4 + + - - DCS-1 DCS-3 DCS-2 O F F O F F O N O N 1 6 A 1 6 A SL1 SL2 4kW 4kW S o u r c e - 1 S o u r c e - 2 I n d e p e n d e n t PB-1 80A J1A 9 10 B52 B51 J1 J2 J3 J4 TB13/14 TB13/15 TB13/16 TB13/13 J3A 80B 9 10 PB-2 B53 B54 G r o u p - B G r o u p - A FS-55 FS-65 FS-53 FS-63 FS-69 FS-59 FS-67 FS-73 FS-57 FS-56 FS-66 FS-54 FS-64 FS-70 FS-60 FS-68 FS-74 FS-58 K421 K422 K201 K202 K401 K402 J5A J6A 13/39 13/40 13/17 13/19 J5B J6B K411 K412 K601 K602 J70 J80 K431 K432 To GCDP Syn.& GRP SKE Relay To LBB Protn.& Aux. Relay FS-61 FS-62 K549 K550 FS-71A FS-72A K13 K352 220 Volts DC Distribution Scheme MODIFIED TS-2/Elec. O&A/Controls& Battery Division Drawing No.: GRP-1/CWD/Sheet No.: 9 80A T B 2 2 L101 L201 3 4 B35 21 22 L201 L202 3 4 C35 23 24 80B To Ann. Circuit } 1 2 80B T B 1 3 H19 H19A 1 2 80A H17 H18 7 8 9 10 S p a r e } All Fuses are 6A rated 23 24 T B 1 3 T B 1 3 200 ms. TDDO 200 ms. TDDO 4A Panel-1 Panel-3 Panel-1 Panel-3 Panel-3 Panel-3 (+) (+) (--) (--) 4A I i I i I i I i I iIiI i I i I i I i I i I i I i I i I i I iIiI i I i I i I i I i C C S2 S1 15 P3 230kV P3 115V P3 To Sheet 3 15kV P3 110V P3 I i I i I i I i I i I iIiIiIiIiI i I I i I i I i I i 9 10 80AC I i I i I i I i I i I iIiIiIiIiI i I I i I i I i I i I i I i I i I i IiIiIiIiI i I i I i I i 89TRA 89TRB I i I i I i I i IiIiIiIiI i I i I i I i NGT-40kVA (Cont.) 15kV/240V, 50Hz Taps- 5% in Steps of 2.5% 6 NGR-1.638 240V/ with 15% in steps of 1.25% W 6 P3 N FS-101 FS-102