Nume Client : . . . . . . . . . . . . . . . . . . . . . .

TOTAL
6/17/2014
-21 IV 4.0 7.00 1.000 CM 1.00
T inter. C 24 W W/mc 0.00 W/mp 0.00
h
Supraf.
de
calcul
H sol h
Supraf.
de
calcul
H sol
l Lvitral. aprox. exact i fer./usi l Lvitral. aprox. exact i fer./usi
perete 1 2.80 0.00 0.00 B -21 0.00 0.00 1.038 perete 2 2.80 0.00 0.00 B -21 0.00 0.00 1.038
fereastra 1 2.00 0.00 0.00 T. Bun -21 0.00 0.060 1.200 fereastra 1 0.00 0.00 T. Bun -21 0.00 0.060 1.200
fereastra 2 0.00 0.00 T. Bun -21 0.00 0.060 1.200 fereastra 2 0.00 0.00 T. Bun -21 0.00 0.060 1.200
fereastra 3 0.00 0.00 T. Bun -21 0.00 0.060 1.200 fereastra 3 0.00 0.00 T. Bun -21 0.00 0.060 1.200
usa 0.00 0.00 T. Bun -21 0.00 0.060 1.200 usa 0.00 0.00 T. Bun -21 0.00 0.060 1.200
perete 3 2.80 0.00 0.00 B -21 0.00 0.00 1.038 perete 4 2.80 0.00 0.00 B -21 0.00 0.00 1.038
fereastra 1 0.00 0.00 T. Bun -21 0.00 0.060 1.200 fereastra 1 0.00 0.00 T. Bun -21 0.00 0.060 1.200
fereastra 2 0.00 0.00 T. Bun -21 0.00 0.060 1.200 fereastra 2 0.00 0.00 T. Bun -21 0.00 0.060 1.200
usa 0.00 0.00 T. Bun -21 0.00 0.060 1.200 usa 0.00 0.00 T. Bun -21 0.00 0.060 1.200
perete 5 2.80 0.00 0.00 B -21 0.00 0.00 1.038 perete 6 2.80 0.00 0.00 B -21 0.00 0.00 1.038
fereastra 0.00 0.00 T. Bun -21 0.00 0.060 1.200 fereastra 0.00 0.00 T. Bun -21 0.00 0.060 1.200
usa 0.00 0.00 T. Bun -21 0.00 0.060 1.200 usa 0.00 0.00 T. Bun -21 0.00 0.060 1.200
perete 7 2.80 0.00 0.00 S 0.70 20 0.00 1.000 perete 8 2.80 0.00 0.00 S 0.70 20 0.00 1.000
usa 2.00 0.00 0.00 T. Slab 20 0.00 0.090 1.200 usa 0.00 0.00 T. Slab 20 0.00 0.090 1.200
usa 0.00 0.00 T. Slab 20 0.00 0.090 1.200 usa 0.00 0.00 T. Slab 20 0.00 0.090 1.200
perete 9 2.80 0.00 0.00 S 0.70 20 0.00 1.000 perete 10 2.80 0.00 0.00 S 0.70 20 0.00 1.000
usa 0.00 0.00 T. Slab 20 0.00 0.090 1.200 usa 0.00 0.00 T. Slab 20 0.00 0.090 1.200
usa 0.00 0.00 T. Slab 20 0.00 0.090 1.200 usa 0.00 0.00 T. Slab 20 0.00 0.090 1.200
perete 11 2.80 0.00 0.00 S 0.70 20 0.00 1.000 perete 12 2.80 0.00 0.00 S 0.70 20 0.00 1.000
usa 0.00 0.00 T. Slab 20 0.00 0.090 1.200 usa 0.00 0.00 T. Slab 20 0.00 0.090 1.200
perete 13 2.80 0.00 0.00 S 0.70 20 0.00 1.000 perete 14 2.80 0.00 0.00 S 0.70 20 0.00 1.000
usa 0.00 0.00 T. Slab 20 0.00 0.090 1.200 usa 0.00 0.00 T. Slab 20 0.00 0.090 1.200
podea 1 3.00 0.00 0.00 P3 20 0.00 0.00 1.000 tavan 1 0.00 3.00 0.00 0.00 T5 10 0.00 0.00 1.038
podea 2 0.00 P3 20 0.00 0.00 1.000 tavan 2 0.00 0.00 0.00 0.00 T5 10 0.00 1.038
podea 3 0.00 P3 20 0.00 0.00 1.000 tavan 3 0.00 0.00 0.00 0.00 T5 10 0.00 1.038
podea 4 0.00 P3 20 0.00 0.00 1.000 tavan 4 0.00 0.00 0.00 0.00 T5 10 0.00 1.038
podea 5 0.00 P3 20 0.00 0.00 1.000 tavan 5 0.00 0.00 0.00 0.00 T5 10 0.00 1.038
fereastra 1 0.00 0.00 T. Bun -21 0.00 0.060 1.200
fereastra 2 0.00 0.00 T. Bun -21 0.00 0.060 1.200
AT 0.00 mediu 1.20 A usi ext. 0.00 Qi1 0 0.00
Ap 0.00 ms 0.50 n-nr.desch. 0 Qi2 0
Rp 0.00 ns 1.40 Qu 0 L rosturi 0.00 0.00
Abc 0.00 V 3/4 6.35 aer 1.20 0
R bc 0.00 Cp 1,011 0
Abcj 0.00 nao 0
m elem.
de
constr.
Rc
L
Zona climatica IV Zona eoliana in localitate Adincimea pinzei de apa freatica
0 Necesar termic total denumire / destinatie camera
Setari generale ( pt. intregul imobil ) :
denumire
element
constructie
V - volumul camerei
Temp
ext. a
peret.
W
Coef. Etaj E
Temp
ext. a
peret.
Supraf.
Totala
Aveti mai jos o serie de marimi si valorile lor, conform SR 1907, asa cum le utilizeaza si acest program. O parte provin din pag. Culise, o parte sint rezultatul unor formule de calcul, iar o alta parte sint constante ce pot fi introduse de operator. Atentie sa nu stergeti din greseala vreo
formula. Cei care au cunostinte in domeniu isi pot adapta si mai bine calculele la experienta si nevoile lor, ca si in pagina Culise. Iar cei care se pricep mai putin, aveti grija ce date introduceti aici ! Modificati DOAR daca : 1. sinteti sigur pe ceea ce faceti, sau 2. doriti doar sa
vedeti cum afecteaza modificarea unei valori rezultatul final, dupa care dati un "UNDO" = Ctrl+Z.
N - V
0.60
5.000
QS
Ac
16.200
QT*adaosuri
Ao
QT*ad.+Qi
1.212
QT alege destinatia camerei:
Rm
0.00028
W
m elem.
de
constr.
Rc
denumire
element
constructie
L
Punct Cardinal
Supraf.
Totala
Adaosuri bai
beton simplu / armat
10 vata minerala 20 FB
3.6577
Tabel Definitii Formule
Pt . acest program, .
PODEA izolata inseamna :
TAVAN izolat inseamna :
Evident, aceste valori ale grosimii stratului izolator reprezinta un minimum necesar.
Pt detalii, vezi tabelul din aceasta pagina, celulele AF27:AL47 !!!
9
10
1. pe interior, sub tavan, un strat de polistiren expandat (sau vata
minerala) de 10 cm, cu sau fara gips-carton.
2. pe exterior, placare cu polistiren de 10 cm grosime. Valabil daca
deasupra camerei aveti o alta incapere in care aveti acces, si careia
de fapt ii izolati podeaua (pod la casa etc).
Pentru PODEA si TAVAN, s-a luat in calcul o placa de beton de 15 cm grosime
+ un eventual strat izolator de 5 sau 10 cm (vezi mai jos):
1. pe interior, in sapa, un strat de polistiren extrudat de 5 cm
2. pe exterior, placare cu polistiren expandat de 5 cm, cu sau fara
gips-carton. Valabil daca sub camera aveti o alta incapere in care
aveti acces, si careia de fapt ii izolati tavanul ( beci la casa, sau
casa scarilor la bloc etc).
Rezistenta termica corectata, reala ( R c ) =
Pe cei cu adevarat interesati ii invit sa-si calculeze si mai exact rezistenta termica a peretilor sau a planseelor, cu
ajutorul tabelului din dreapta ( col. T-W). De asemenea, pt. cei care nu stiu, aveti si mai in dreapta o serie de definitii
( K, R, ), precum si o serie de formule de calcul simplificate din acest domeniu. Nota : programul face
calculele pierderilor de caldura conform formulelor din SR 1907, care sint mult mai "stufoase" !
Material component
Grosime
( cm )
Strat izolator
Grosime
( cm )
Grad
izolare
Modul de stabilire al gradului de izolatie al peretilor exteriori sau planseelor -- orientativ!
K R
Daca intilniti materiale de constructie care nu apar in tabel,
le puteti scrie mai jos, astfel incit sa le puteti folosi la calcul:
Denumire, tip, caracteristici, producator
1 0.027
2 0.3
3 0.5
4 0.7
5 0.9
6 1.1
7 1.3
8 1.5
9
1.7
10 1.9 J
E
F
G
H
I
C
D
EPS grafitat (AF Plus; Dalmatina)
B
Termopan
foarte bun
geam termopan, 3 foi de sticla, Low E,
gaz inert, timplarie AL cu rupere punte
termica, lemn stratificat sau PVC cu 5-6
camere.
0.80 1.250
Termopan
bun
geam termopan, 2 foi de sticla, Low E,
gaz inert, timplarie AL cu rupere punte
termica, lemn stratificat sau PVC cu 3-4
camere.
1.20 0.833
Termopan
slab
geam termopan, 2 foi de sticla, fara Low
E, fara gaz inert, cu timplarie AL, lemn
statificat sau PVC cu 3 camere.
2.10 0.476
Geam dublu 2
geam cu sticla obisnuita, cu 1 + 2 foi
de sticla, timplarie lemn.
3.30 0.303
Geam dublu 1
geam cu sticla obisnuita, cu 2 foi de
sticla, timplarie lemn.
4.00 0.250
Tip constructiv fereastra - orientativ.
Geam simplu
geam cu o singura foaie de sticla
obisnuita, timplarie lemn.
5.00 0.200
d
cm ! W/mK
aer interior --- 8.000
tencuial var 1.00 0.700
plci de ipsos 1100 kg/m3 0.00 0.410
folie polietilena 0.2 mm 0.00 100.000
vat mineral tip 70 0.00 0.045
Caramida termoeficienta cu goluri verticale Porotherm30 30.00 0.208
BCA Ytong
0.00 0.110
tencuial var-ciment 0.00 0.870
EPS grafitat (AF Plus; Dalmatina) 10.00 0.027
mortar ciment 0.50 0.930
aer exterior --- 24.000
41.50
coeficient punti termice :
rezistenta termica corectata :
nivelul gradului de izolare :
( datele scrise cu rosu pot fi modificate de utilizator )
Lungimea camerei 4.00 m
Latimea camerei 4.00 m
Inaltimea camerei 2.50 m
Suprafata camerei 16.00 mp
Volumul camerei 40.00 mc
Suprafata peretilor exteriori, cu tot cu ferestre / usi 10.00 mp
Suprafata totala a ferestrelor / usilor spre exterior 3.00 mp
Coeficientul de transfer termic ( K ) al ferestrelor / usilor spre exterior 1.50 W/mpK
Temperatura interioara 20 C
Temperatura exterioara -21 C
Pierderile de caldura prin peretii propriu-zisi (doar prin zidarie) 71.75 W
Pierderile de caldura prin ferestrele / usile spre exterior 184.50 W
Pierderea TOTALA de caldura : 256.25 W
Pierderea de caldura raportata la volumul camerei 6.41 W / mc
Pierderea de caldura raportata la suprafata camerei 16.02 W / mp
Formula simplificata de calcul a pierderilor de caldura printr-un perete cu / fara geam este :
Q = [ 1 / ( R perete din calcul tabel * coeficient punti termice ) ] * (suprafata perete - suprafata
geam) * ( T interioara - T exterioara ) + K geam * suprafata geam * ( T interioara - T exterioara )
Exemplu de calcul al pierderilor de caldura care au loc printr-un perete (sau mai multi, vezi cel. W27 -
W28) ca cel setat mai sus, si corespondentul acestora in W/m cub si W/m patrat, pt. o camera cu
dimensiunile si ferestrele de mai jos :
Material component
Calculul exact al rezistentei termice teoretice / reale (corectate)
a unui perete sau planseu, in functie de straturile care il compun :
X
R = d/
m2K/W
0.1250
0.0143
0.0000
0.0000
0.0000
1.4430
0.0000
0.0000
3.7037
0.0054
0.0420
5.3334
0.75
4.0000
col. H/T
pereti ext.
1.00
28%
72%
vezi si
Formule
Procent
din total
pierderi de
caldura :
Exemplu de calcul al pierderilor de caldura care au loc printr-un perete (sau mai multi, vezi cel. W27 -
W28) ca cel setat mai sus, si corespondentul acestora in W/m cub si W/m patrat, pt. o camera cu
dimensiunile si ferestrele de mai jos :
Calculul exact al rezistentei termice teoretice / reale (corectate)
a unui perete sau planseu, in functie de straturile care il compun :
D E F I N I T I I de BAZA:
9. Pereti exteriori, sub CTS, la demisolurile sau la subsolurile incalzite
Punti termice = zona / zone in structura (compozitia) unui element de constructie care "strica" omogenitatea lui, avind o conductivitate termica mai
mare, respectiv o rezistenta termica mai mica decit restul elementului de constructie dat.
6. Plansee care delimiteaza cladirea la partea inferioara, de exterior (la bowindouri, ganguri de trecere etc.)
7. Placi pe sol (peste CTS)
8. Placi la partea inferioara a demisolurilor sau a subsolurilor incalzite (sub CTS)
2. Tamplarie exterioara
3 Plansee peste ultimul nivel, sub terase sau poduri
4. Plansee peste subsoluri neincalzite si pivnite
5. Pereti adiacenti rosturilor inchise
1. Pereti exteriori (exclusiv suprafetele vitrate, inclusiv peretii adiacenti rosturilor deschise)
Nr. Elementul de constructie
REZISTENTA TERMICA CORECTATA MINIMA Rc (min) pt elementele de constructie ale unei
cladiri de locuit:
n prezent, valorile propuse in constructii, ale gradului de protecie termic Rc , pt. asigurarea unui confort termic sporit si pt. reducerea risipei de energie
termica prin pierderile de caldura sunt mrite mai mult, conform C107/1 modificat:
R c (notata si R' ) = rezistenta termica corectata, reala, a materialului respectiv = rezistenta termica teoretica (din tabele) x coeficientul datorat puntilor
termice.
Capacitatea unui element de constructie de a se opune transferului de caldura prin masa lui este exprimata de R = rezistenta termica ( sau rezistivitatea termica ) a
materialului respectiv, si este inversul lui K . Depinde de grosimea materialului analizat. Cu ajutorul lui se pot compara proprietatile termoizolatoare ale unor materiale sau
elemente de constructie eterogene cu grosimi diferite si cu conductivitati termice diferite.
calcul = valoarea reala, folosita in calcule, a conductivitatii termice a unui material; este mai mare decit efectiva si tine cont de umiditatea naturala in conditiile
normale de exploatare ale materialelor.
efectiva = valoarea teoretica a conductivitatii termice a unui material; se calculeaza in laborator de catre producatorii de materiale de constructii, la 10 grade C si cu
materialul in stare perfect uscata; de obicei este valoarea care apare pe eticheta produsului finit.
= (coeficientul de) conductivitate termica a unui material : reprezinta cantitatea de caldura exprimata in Wh care trece printr-o suprafata de 1mp, a unui material cu o
grosime de 1 m, in timp de o ora, la o diferenta de 1 grad C intre cele 2 suprafete ale materialului.
Nivelul de conductivitate termica a unui material este exprimat prin = coeficient de conductivitate termica.
K = coeficientul de tranfer termic : reprezinta cantitatea de caldura exprimata in Wh (watti ora) transmisa printr-un mp de element de constructie timp de o ora la o
diferenta de 1 grad C intre interior si exterior.
Capacitatea de izolare termica a unui element de constructie (de ex. perete exterior, acoperis, pardoseala, etc.) este exprimata de valoarea K = coeficient de transfer
termic ( notata si U ).
Exemple de situatii in care exista punti termice la peretii exteriori :
2* rosturi mai mari intre caramizi, sau "umplute" neglijent cu mortar: cu goluri etc.
8* stilpii de sustinere din beton neizolati termic de la colturile cladirii.
10* ETC.
4* izolatie termica realizata neglijent. Ex.: placi de polistiren intre care exista spatii pe lateral; zone de vata minerala "turtita"; placi de polistiren pe sub care poate
circula aerul de la o placa la alta etc.
5* finisari neglijente ale izolatiei termice in diferite zone : la ferestre, usi, colturi de zid etc.
6* materiale de constructie (BCA, caramizi, vata etc) depozitate si / sau folosite mult timp in conditii improprii (mai ales umezeala), ceea ce le altereaza
proprietatile termoizolante.
7* izolatie proasta a usilor / ferestrelor in faza de montare : spuma poliuretanica (prea) putina sau prost / neglijent amplasata (strat prea subtire, cu goluri etc)
9* caramizi cu goluri verticale ... amplasate orizontal, pe directia interior - exterior ( caz "penal" - vezi poza de la articolul "Asa NU" de pe blog !)
1* buiandrug din beton la ferestre sau usi, la un zid confectionat din materiale de constructie cu o mai buna rezistenta termica decit betonul (din BCA, de exemplu)
3* perete / zone de perete realizate din resturi ( bucati de BCA, caramida etc.), deci cu rosturi mai dese si mai mari decit in cazul bucatilor "standard".
Punti termice = zona / zone in structura (compozitia) unui element de constructie care "strica" omogenitatea lui, avind o conductivitate termica mai
mare, respectiv o rezistenta termica mai mica decit restul elementului de constructie dat.
0.77 0.50 0.40
5.00 3.00 2.00
2.90 1.65 1.10
1.10 1.10 0.90
4.50 4.50 3.00
4.80 4.80 4.20
2.90 2.40 2.00 9. Pereti exteriori, sub CTS, la demisolurile sau la subsolurile incalzite
Punti termice = zona / zone in structura (compozitia) unui element de constructie care "strica" omogenitatea lui, avind o conductivitate termica mai
mare, respectiv o rezistenta termica mai mica decit restul elementului de constructie dat.
6. Plansee care delimiteaza cladirea la partea inferioara, de exterior (la bowindouri, ganguri de trecere etc.) 4.50 4.50 3.00
7. Placi pe sol (peste CTS)
8. Placi la partea inferioara a demisolurilor sau a subsolurilor incalzite (sub CTS)
2. Tamplarie exterioara
3 Plansee peste ultimul nivel, sub terase sau poduri
4. Plansee peste subsoluri neincalzite si pivnite
5. Pereti adiacenti rosturilor inchise
1. Pereti exteriori (exclusiv suprafetele vitrate, inclusiv peretii adiacenti rosturilor deschise) 1.80 1.40 1.20
Nr. Elementul de constructie
Rc(minim)
[m2K/W]
REZISTENTA TERMICA CORECTATA MINIMA Rc (min) pt elementele de constructie ale unei
cladiri de locuit:
dupa
1 ianuarie
2011
Rc(minim)
[m2K/W]
Rc(minim)
[m2K/W]
n prezent, valorile propuse in constructii, ale gradului de protecie termic Rc , pt. asigurarea unui confort termic sporit si pt. reducerea risipei de energie
termica prin pierderile de caldura sunt mrite mai mult, conform C107/1 modificat:
dupa
1 ianuarie
1998
inainte de
1 ianuarie
1998
R c (notata si R' ) = rezistenta termica corectata, reala, a materialului respectiv = rezistenta termica teoretica (din tabele) x coeficientul datorat puntilor
termice.
Capacitatea unui element de constructie de a se opune transferului de caldura prin masa lui este exprimata de R = rezistenta termica ( sau rezistivitatea termica ) a
materialului respectiv, si este inversul lui K . Depinde de grosimea materialului analizat. Cu ajutorul lui se pot compara proprietatile termoizolatoare ale unor materiale sau
elemente de constructie eterogene cu grosimi diferite si cu conductivitati termice diferite.
calcul = valoarea reala, folosita in calcule, a conductivitatii termice a unui material; este mai mare decit efectiva si tine cont de umiditatea naturala in conditiile
normale de exploatare ale materialelor.
efectiva = valoarea teoretica a conductivitatii termice a unui material; se calculeaza in laborator de catre producatorii de materiale de constructii, la 10 grade C si cu
materialul in stare perfect uscata; de obicei este valoarea care apare pe eticheta produsului finit.
= (coeficientul de) conductivitate termica a unui material : reprezinta cantitatea de caldura exprimata in Wh care trece printr-o suprafata de 1mp, a unui material cu o
grosime de 1 m, in timp de o ora, la o diferenta de 1 grad C intre cele 2 suprafete ale materialului.
Nivelul de conductivitate termica a unui material este exprimat prin = coeficient de conductivitate termica.
K = coeficientul de tranfer termic : reprezinta cantitatea de caldura exprimata in Wh (watti ora) transmisa printr-un mp de element de constructie timp de o ora la o
diferenta de 1 grad C intre interior si exterior.
Capacitatea de izolare termica a unui element de constructie (de ex. perete exterior, acoperis, pardoseala, etc.) este exprimata de valoarea K = coeficient de transfer
termic ( notata si U ).
4* izolatie termica realizata neglijent. Ex.: placi de polistiren intre care exista spatii pe lateral; zone de vata minerala "turtita"; placi de polistiren pe sub care poate
circula aerul de la o placa la alta etc.
5* finisari neglijente ale izolatiei termice in diferite zone : la ferestre, usi, colturi de zid etc.
6* materiale de constructie (BCA, caramizi, vata etc) depozitate si / sau folosite mult timp in conditii improprii (mai ales umezeala), ceea ce le altereaza
proprietatile termoizolante.
7* izolatie proasta a usilor / ferestrelor in faza de montare : spuma poliuretanica (prea) putina sau prost / neglijent amplasata (strat prea subtire, cu goluri etc)
9* caramizi cu goluri verticale ... amplasate orizontal, pe directia interior - exterior ( caz "penal" - vezi poza de la articolul "Asa NU" de pe blog !)
1* buiandrug din beton la ferestre sau usi, la un zid confectionat din materiale de constructie cu o mai buna rezistenta termica decit betonul (din BCA, de exemplu)
3* perete / zone de perete realizate din resturi ( bucati de BCA, caramida etc.), deci cu rosturi mai dese si mai mari decit in cazul bucatilor "standard".
Punti termice = zona / zone in structura (compozitia) unui element de constructie care "strica" omogenitatea lui, avind o conductivitate termica mai
mare, respectiv o rezistenta termica mai mica decit restul elementului de constructie dat.
fluxul termic = Tint. - Text.
( W )
1 d
R c
c
n n
unde :
t1 + t2
2
Exemple :
75 + 65
= 50
T t1/t2 = -
t interior
T 75/65 =
-
20
f = un factor de corectie. Unii
producatori de radiatoare ofera
tabele cu valorile lui f, in functie
de temp. de tur /retur /interior, si
cu valori ale lui n calculate de
ei.
caldura degajata
de un radiator la
temperaturile de
tur / retur t1 / t2 si
la o oarecare
temp. t interior
caldura degajata
de un radiator la
temperaturile de
tur / retur 75 / 65
si la o oarecare
temp. t interior
q 75/65
x
f =
n = exponent termic, dat de
producatorii de radiatoare, care
difera, pt. fiecare model de
radiator, cu inaltimea lui. Are valori
cuprinse intre 1,1 si 1,5 , insa
poate fi aproximat linistit la
valoarea de 1,30.
T 75/65 T 75/65
T t1/t2 T t1/t2
coeficient de corectie
datorat prezentei
eventualelor punti termice
R c =
q t1 / t2
=
R teoretica
x

rezistenta termica
corectata, reala, a
peretelui
calculat cu
valorile din
tabele
R teoretica = ( R1 + R2 + +Rn ) + 0,167
rezistenta termica
totala a peretelui,
teoretica
R1, R2, Rn = rezistenta termica a stratului 1, 2, n din
care e alcatuit peretele
0,167 = rezistenta termica insumata a straturilor de aer de pe
cele 2 suprafate ale peretelui.
rezistenta
termica
teoretica
d = grosime
material
c = conductivitate
termica de calcul, reala
; R teoretica =
coeficientul de
transfer termic
inversul
rezistentei
termice
corectate, reale
diferenta de
temp. : interior
minus exterior
K
=
coeficientul de
transfer termic
K
x
S
x
Q
=
suprafata
perete
( m2 )
T C
F O R M U L E simplificate :
2
50 + 40
2
90 + 70
2
1.3 1.3
25
50
= 0.4061
Deci un radiator, care la temp. de tur / retur de 75 / 65 si la o temp. a
camerei t interior de 20 C, degaja 1000 W, atunci la temp. de tur / retur
de 50 / 40 si la o temp. a camerei t interior tot de 20 C, va degaja doar
406 W, adica aprox. 40 %. De aceea, in acest caz, trebuie ales un
radiator cu o dimensiune mult mai mare, care la 75/65 sa ofere (1000 /
0,4061) = 2,463 W, iar la 50 / 40 tot acei 1000 W initiali, necesari
camerei.
f 50/40
= = 0.5
T 90/70 =
-
20 = 60
= 50
T 50/40 =
-
20 = 25
T 75/65 =
-
20
1.
FS S S-M M M-B B
minim 0.30 0.61 1.01 1.51 2.11 2.71
maxim 0.60 1.00 1.50 2.10 2.70 3.40
0.35 0.70 1.10 1.60 2.20 2.80
0.26 0.53 0.83 1.20 1.65 2.10
Pt. peretii interiori am folosit o valoare de calcul a rezistentei termice corectate Rc de :
T1 T2 T3 T4 T5 T6
0.30 0.30 2.10 0.30 2.10 0.30
P1 P2 P3 P4 P5 P6
0.30 0.30 1.20 0.30 1.20 0.40
2. Adaosul pt. orientarea camerei : un procent cu care se mareste sau se micsoreaza QT = fluxul termic prin transmisie, al intregii camere.
Nord Sud Est Vest N - E N - V S - E S - V
5.00 -5.00 0.00 0.00 5.00 5.00 -5.00 -5.00
3.
T1 T2 T3 T4 T5 T6 T7
10 -16 -16 -10 -10 -21 -21
P1 P2 P3 P4 P5 P6 P7
20 8 8 -21 -21 8 8
In cazul unui acoperis izolat termic al podului, temp. de calcul creste, fata de temp. din tabelul de mai sus, cu :
4. Valorile Ac = adaosul pt. compensarea efectului suprafetelor reci, in functie de Rm = rezistenta termica medie a incaperii = CM*AT*(tint-text) / QT
Rm 0.60 0.70 0.80 1.00 1.20 1.40 1.60 1.80 2.00 2.30 2.60
Ac 16.20 14.25 12.30 11.00 9.70 8.90 8.35 7.75 7.45 7.00 6.60
G.Dublu2
0.090
0.48
2.10
T. Slab
0.060
4.00
0.110
0.30
3.30 coeficienti K
tip fereastra
0.170
0.20 0.83
1.20
T. Bun
5.00
0.140
0.25
G.Simplu G.Dublu1
coeficienti R
coeficienti i
Punct Cardinal
Tavan : valoarea temp.
exterioare de calcul C :
Daca valoarea calculata a Rm difera de valorile de mai sus, se va alege Ac care corespunde valorii imediat inferioare a Rm. De ex., daca Rm este 0,9,
se va alege valoarea de la 0,8 ( adica Ac = 12,30 ), iar daca Rm este 4,5, atunci se va alege Ac = 5,75, corespunzatoare lui Rm = 4,00.
M-am hotarit sa dau o tenta de "open source" acestui program, prezentind modul de calcul si oferind posibilitatea utilizatorului
care se pricepe sa modifice anumite date utilizate de "program", pt. obtinerea unor rezultate adaptate experientei si preferintelor sale.
valoarea de calcul a rezistentei
termice ( R c ) pt. PODEA :
valorile rezist. termice
( R ) pt. fiecare nivel :
valoarea de calcul a rezistentei
termice ( R c ) pt. TAVAN :
valoarea de calcul a rezistentei
termice ( R c ) pt. peretii exteriori :
- valorile scrise cu rosu pot fi modificate ! -
Date referitoare la izolatia peretilor exteriori si interiori, a tavanului si podelei, precum si a suprafetelor vitrate : valorile rezistentei termice dupa care se face
clasificarea gradului de izolatie a peretilor exteriori, a tavanului, a podelei si a suprafetelor vitrate, precum si valorile de calcul pt. fiecare treapta, folosite pt.
calcularea pierderilor de caldura. Pt. geamuri, valorile coeficientul de infiltratie " i ".
coeficienti *
clasificarea gradului de izolare :
Temperaturile exterioare de calcul pt. tavan cu pod sau fara, izolat sau neizolat, si pt. podea cu beci, in functie de zona climatica setata :
Podea : valoarea temp.
exterioare de calcul C :
5. Viteza de calcul a vintului, in functie de zona eoliana a cladirii si de amplasamentul acesteia, in localitate sau inafara localitatii :
Acestea sint valabile pt. nivelurile 1 - 12 ale cladirilor, si pina la altitudinea de 1.100 m.
v v v v
I 8.0 16.00 10.0 21.54
II 5.0 8.55 7.0 13.39
III 4.5 7.45 6.0 10.90
IV 4.0 6.35 4.0 6.35
6.
4 6 8 10 <-- valori SR
0 - 4,5 4,5 - 7 7 - 9 9 - 10 <-- valori program
0.0 0.768 0.645 0.574 0.530 0 - 0,5
1.0 0.490 0.430 0.398 0.377 0,5-1,5
2.0 0.448 0.380 0.347 0.327 1,5 -
^ valori SR
7. Valorile recomandate pt. nao = numarul de schimburi de aer necesar in incapere in conditii de confort fiziologic :
8. Valorile unor constante, utilizate de program :
CM E
1.00 1.000
9.
%
10. O harta a Romaniei, cu impartirea pe zone CLIMATICE :
m tavan Notare m per. ext. m podea
nao*Vol. = 0,007*Nr. Persoane
Daca valoarea calculata a Rm difera de valorile de mai sus, se va alege Ac care corespunde valorii imediat inferioare a Rm. De ex., daca Rm este 0,9,
se va alege valoarea de la 0,8 ( adica Ac = 12,30 ), iar daca Rm este 4,5, atunci se va alege Ac = 5,75, corespunzatoare lui Rm = 4,00.
H ( m )
h (m)
in localitate inafara localitatii
Zona
eoliana
Rezistenta termica specifica a benzii de contur, Rbc, pt. o grosime a fundatiei de 45 cm, in functie de adincimea de ingropare a pardoselii ( h ) si de
adincimea pinzei de apa freatica ( H ). Folosita la calcularea Qs = pierderile de caldura prin sol.
Bineinteles, valoarea implicita este zero, insa o puteti modifica aici :
Valoare 1.000 1.038
"Factorul de supradimensionare" = o nascocire pur personala, adresata celor care NU se pot abtine sa nu supradimensioneze radiatoarele si care, oricit de
precis ar face calculele, se tot intreaba "N-o fi prea putin ?" :) . Reprezinta procentul ( % ) cu care se doreste marirea necesarului termic al fiecarei camere, fata
de valoarea rezultata din calcule facute de acest program.
1.038 1.200
m geam
scoli, crese, spitale
0.00022
0.00033
0.00028
destinatia incaperii nao (m3/s)/m3
0.792
1.190
1.000
nao (m3/h)/m3
camere de locuit
bucatarii
bai
- 12 C - 15 C - 18 C
cu verde = zona I cu galben = zona II cu albastru = zona III cu maro = zona IV
11. De asemenea, o harta cu impartirea Romaniei pe zone EOLIENE :
FB Pt. peretii exteriori
3.41
10.00 - valorile scrise cu rosu pot fi modificate.
3.50 --> valoarea propusa ( din tabel ) pt. calculul rezistentei termice, pt. fiecare nivel.
2.63 --> valoarea de calcul corectata, REALA, obtinuta astfel : valoarea
propusa mai sus x coeficientul de mai jos:
0.700
T7
2.10
P7
1.20
Adaosul pt. orientarea camerei : un procent cu care se mareste sau se micsoreaza QT = fluxul termic prin transmisie, al intregii camere.
I II III IV
-12 -15 -18 -21
-8 -11 -13 -16
11 10 9 8
In cazul unui acoperis izolat termic al podului, temp. de calcul creste, fata de temp. din tabelul de mai sus, cu : 6 grade C.
Valorile Ac = adaosul pt. compensarea efectului suprafetelor reci, in functie de Rm = rezistenta termica medie a incaperii = CM*AT*(tint-text) / QT
3.00 3.50 4.00 5.00 6.00 8.00 10.00
6.40 6.00 5.75 5.50 5.25 5.00 4.80
T.f. bun
0.060 0.030
1.25
0.80
0.83
1.20
T. Bun
Daca valoarea calculata a Rm difera de valorile de mai sus, se va alege Ac care corespunde valorii imediat inferioare a Rm. De ex., daca Rm este 0,9,
se va alege valoarea de la 0,8 ( adica Ac = 12,30 ), iar daca Rm este 4,5, atunci se va alege Ac = 5,75, corespunzatoare lui Rm = 4,00.
Temp. in pod neizolat
Temp. sol/beci NEincalzit
M-am hotarit sa dau o tenta de "open source" acestui program, prezentind modul de calcul si oferind posibilitatea utilizatorului
care se pricepe sa modifice anumite date utilizate de "program", pt. obtinerea unor rezultate adaptate experientei si preferintelor sale.
0.75
Coeficientul general care ia in calcul
existenta puntilor termice din pereti;
scade valoarea reala a rezistentei
termice calculate.
Date referitoare la izolatia peretilor exteriori si interiori, a tavanului si podelei, precum si a suprafetelor vitrate : valorile rezistentei termice dupa care se face
clasificarea gradului de izolatie a peretilor exteriori, a tavanului, a podelei si a suprafetelor vitrate, precum si valorile de calcul pt. fiecare treapta, folosite pt.
calcularea pierderilor de caldura. Pt. geamuri, valorile coeficientul de infiltratie " i ".
Temperaturile exterioare de calcul pt. tavan cu pod sau fara, izolat sau neizolat, si pt. podea cu beci, in functie de zona climatica setata :
Zona climatica setata
Temp. ext. aferenta zonei
Viteza de calcul a vintului, in functie de zona eoliana a cladirii si de amplasamentul acesteia, in localitate sau inafara localitatii :
Acestea sint valabile pt. nivelurile 1 - 12 ale cladirilor, si pina la altitudinea de 1.100 m.
Valorile recomandate pt. nao = numarul de schimburi de aer necesar in incapere in conditii de confort fiziologic :

Daca valoarea calculata a Rm difera de valorile de mai sus, se va alege Ac care corespunde valorii imediat inferioare a Rm. De ex., daca Rm este 0,9,
se va alege valoarea de la 0,8 ( adica Ac = 12,30 ), iar daca Rm este 4,5, atunci se va alege Ac = 5,75, corespunzatoare lui Rm = 4,00.
Rezistenta termica specifica a benzii de contur, Rbc, pt. o grosime a fundatiei de 45 cm, in functie de adincimea de ingropare a pardoselii ( h ) si de
adincimea pinzei de apa freatica ( H ). Folosita la calcularea Qs = pierderile de caldura prin sol.
"Factorul de supradimensionare" = o nascocire pur personala, adresata celor care NU se pot abtine sa nu supradimensioneze radiatoarele si care, oricit de
precis ar face calculele, se tot intreaba "N-o fi prea putin ?" :) . Reprezinta procentul ( % ) cu care se doreste marirea necesarului termic al fiecarei camere, fata
de valoarea rezultata din calcule facute de acest program.
m per. int.
1.000 1.200
m geam
- 21 C
cu maro = zona IV