NOTE:

THE SYMBOLS AND ABBREVIATIONS


SHOWN ON THIS SHEET ARE NOT ALL
NECESSARILY USED ON THIS PROJECT.
ELECTRICAL POWER PLANS
ELECTRICAL SYMBOLS & SCHEDULES E0.01
ELECTRICAL LIGHTING & FIRE ALARM PLANS
E1.01
E1.02
ELECTRICAL SPECIFICATIONS E7.01
FIRE ALARM SYMBOLS LEGEND:
120V, 20A DUPLEX RECEPTACLE
120V, 20A DUPLEX GROUND FAULT INTERRUPTER
TYPE RECEPTACLE (GFCI).
JUNCTION BOX
NON-FUSED SAFETY DISCONNECT SWITCH
CIRCUIT HOMERUN WITH (1) HOT, (1) NEUTRAL, AND
(1) GROUND
CIRCUIT HOMERUN WITH (2) HOTS, (1) NEUTRAL,
AND (1) GROUND
CIRCUIT HOMERUN WITH (3) HOTS, (1) NEUTRAL,
AND (1) GROUND
CIRCUIT HOMERUN WITH (3) HOTS AND (1) GROUND
SYMBOLS DESCRIPTION
CEILING SMOKE DETECTOR. INSTALL A 4" OCTAGON BOX WITH
CADDY-BAR SUPPORT WHEN INSTALLED IN LAY-IN CEILING.
CEILING MOUNTED HORN/STROBE. INSTALL A 4" OCTAGON
BOX WITH CADDY-BAR SUPPORT WHEN INSTALLED IN LAY-IN
CEILING. FIRE ALARM CONTRACTOR TO ENSURE ALL VISUAL
DEVICES MEET PROPER SPACING AND ADA REQUIRED
CANDELA SETTINGS PER NFPA 72.
CEILING MOUNTED STROBE. INSTALL A 4" OCTAGON BOX WITH
CADDY-BAR SUPPORT WHEN INSTALLED IN LAY-IN CEILING.
FIRE ALARM CONTRACTOR TO ENSURE ALL VISUAL DEVICES
MEET PROPER SPACING AND ADA REQUIRED CANDELA
SETTINGS PER NFPA 72.
WALL MOUNTED STROBE AT 80" AFF. TO THE BOTTOM OF
DEVICE. INSTALL SINGLE GANG BOX AND 3/4" CONDUIT STUB
ABOVE CEILING WITH INSULATED THROAT CONNECTOR. FIRE
ALARM CONTRACTOR TO ENSURE ALL VISUAL DEVICES MEET
PROPER SPACING AND ADA REQUIRED CANDELA SETTINGS
PER NFPA 72. ALL STROBES TO BE 15/75cd UNLESS NOTED
OTHERWISE.
S
POWER SYMBOLS LEGEND:
DESCRIPTION SYMBOL
1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM TO BASE BUILDING SPECIFICATIONS, LOCAL CODES AND
ORDINANCES, AND INDUSTRY STANDARDS.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO START OF CONSTRUCTION.
3. ALL ELECTRICAL RECEPTACLES, SWITCHES , MISCELLANEOUS DEVICES AND TRIM PLATES SHALL BE BUILDING
STANDARD UNLESS NOTED OTHERWISE.
4. ALL PANELBOARDS SHALL HAVE CIRCUITS CLEARLY LABELED ACCORDING TO TENANT AND AREA SERVED.
5. CONTRACTOR MUST MARK ALL SWITCHES, THERMOSTATS, AND ADA STROBE LOCATION IN THE FIELD FOR REVIEWAND
APPROVAL BY THE ARCHITECT BEFORE INSTALLATION. FAILURE TO DO SO WILL RESULT IN THE CONTRACTOR
RELOCATING SUCH ITEMS WITHOUT ADDED EXPENSE TO THE OWNER, TENANT OR ARCHITECT.
6. THE ARCHITECTURAL POWER PLANS ARE TO BE USED FOR HEIGHTS AND APPROXIMATE LOCATIONS OF RECEPTACLES.
THE MEP POWER PLANS ARE TO BE USED FOR CIRCUITING AND POWER REQUIREMENTS. NOTIFY THE ARCHITECT OF
ANY DISCREPANCIES BETWEEN THE MEP AND ARCHITECTURAL POWER PLANS AND OBTAIN CLARIFICATION BEFORE
COMMENCING CONSTRUCTION.
7. ALL COMPACT FLUORESCENT LIGHTING FIXTURES SHALL BE PROVIDED WITH LAMPS AND BALLASTS HAVING AN "END OF
LIFE" PROTECTION FEATURE.
8. FIRE ALARM SYSTEM DEVICES SHALL MEET ALL ADA REQUIREMENTS, SHALL BE INSTALLED BY A LICENSED FIRE ALARM
CONTRACTOR, AND SHALL COMMUNICATE WITH EXISTING BUILDING FIRE ALARM SYSTEM. COORDINATE FIRE ALARM
INSTALLATION WITH MECHANICAL, ELECTRICAL, AND PLUMBING DISCIPLINES.
9. ALL SIZE #10, #12, AND #14 AWG CONDUCTORS SHALL BE SOLID COPPER. SIZE #8 AWG AND LARGER CONDUCTORS
SHALL BE STRANDED COPPER. INSULATION SHALL BE TYPE THHN OR THWN.
10. SEAL ALL CONDUITS OR DATA CABLE PENETRATIONS OF FIRE RATED CONSTRUCTION WITH FACTORY BUILT DEVICES OR
WITH MANUFACTURED FILL, VOID, OR CAVITY MATERIALS "CLASSIFIED" BY UNDERWRITERS LABORATORIES, INC. FOR
USE AS A THROUGH-PENETRATION FIRESTOP.
11. ALL SWITCHES AND DEVICES INDICATED AS GROUPED TOGETHER, SHALL BE GANGED IN ONE COMMON COVER PLATE.
12. FIELD VERIFY PROPOSED LOCATIONS OF NEW ELECTRICAL EQUIPMENT PRIOR TO INSTALLATION IN ORDER TO MAINTAIN
REQUIRED WORKING CLEARANCES PER THE NEC. CONTACT ENGINEER WHERE CONFLICT EXISTS PRIOR TO
INSTALLATION.
13. INSTALL BLANK COVER PLATES OVER MOUNTING BOXES AND JUNCTION BOXES RENDERED EXPOSED DUE TO
EQUIPMENT OR DEVICE REMOVAL.
ELECTRICAL GENERAL NOTES
1
'-6
"
FINISHED FLOOR
RECEPTACLE, VOICE/DATA, ETC.
ALL UNDER COMMON
FACEPLATE.
3
'-6
"
4
'-6
"
6
'-8
"
1'-0"
LIGHT SWITCHES, DIMMERS,
EGRESS BUTTON, INTERCOM
BUTTON, CARD READER, ETC.
(RE: PLANS FOR QUANTITY OF
EACH CLUSTER) ALL UNDER
COMMON FACEPLATE.
THERMOSTAT/SENSOR
DOOR FRAME
FIRE ALARM HORN/STROBE
DEVICE MOUNTING DETAIL
SCALE: N.T.S. 2
SYM KEY FIXTURE MANUFACTURER CATALOG NUMBER
LAMPS
NO. TYPE K TEMP
VOLTS FINISH MOUNTING REMARKS
NOTES:
1. PROVIDE 90 MINUTE BATTERY BACKUP BALLAST FOR ALL LUMINAIRES DESIGNATED WITH ('E') ON LIGHTING PLAN. LUMINAIRES SHALL BE SWITCHED ON AND OFF WITH OTHER
FIXTURES ON CIRCUIT EXCEPT FOR DESIGNATED CORRIDOR NIGHT LIGHTS. PROVIDE UNSWITCHED HOT CONDUCTOR FROM NORMAL CIRCUIT TO EACH EMERGENCY BALLAST.
2. PROVIDE PROGRAM-START BALLAST FOR ALL LUMINAIRES CONNECTED VIA OCCUPANCY SENSORS.
INPUT
WATTS
B
LUMINAIRE SCHEDULE
WHITE A RECESSED 2GR8-232A125-UNV-EB81 COOPER - METALUX 2 F32T8 4100K UNV
RECESSED 2X4
TROFFER
62W
RECESSED 3 F17T8 4100K UNV 51W
X CEILING LPX7SD COOPER - SURE-LITES
-
RED LED
-
UNV EXIT SIGN <5W -
WHITE POLYCARBONATE EXIT SIGN, SINGLE FACE, EMERGENCY BATTERY
BACKUP AND SELF DIAGNOSTICS. ARROWINDICATES DIRECTION OF
CHEVRONS, TO BE APPLIED IN FIELD.
2' X 4' RECESSED TROFFER, .125" THICK PRISMATIC LENS, 2-LAMPS,
ELECTRONIC PROGRAM START BALLAST, <10% THD.
2GR8-317A125-UNV-EB81
AE RECESSED 2 4100K UNV F32T8 62W 2GR8-232A125-UNV-EL-EB81 WHITE
WHITE
# of Occupancy
Sensors as
shown on
plans
WattStopper
LIGHTING CONTROLS DIAGRAM -
OPEN AREA101 AND CONFERENCE 101D
SCALE: N.T.S. 1
FIXTURE SAME AS TYPE "A", EQUIPPED WITH EMERGENCY BATTERY BACKUP
BALLAST RATED FOR 1400 LUMENS. SEE NOTE 1.
LIGHTING SYMBOLS LEGEND:
DESCRIPTION
WALL MOUNTED LOW-VOLTGAGE TOGGLE SWITCH:
WATTSTOPPER LMSW-101 OR APPROVED EQUIVALENT
WALL MOUNTED OCCUPANCY SENSOR SWITCH:
WATTSTOPPER LMDW-101 OR APPROVED EQUIVALENT
CEILING-MOUNTED OCCUPANCY SENSOR:
WATTSTOPPER LMDC-100 OR APPROVED EQUIVALENT
DIGITAL SWITCHING POWER PACK: WATTSTOPPER
LMRC-101 OR APPROVED EQUIVALENT
SWITCH ZONE BREAK
CIRCUIT HOMERUN
LOW VOLTAGE CONDUCTORS, PLENUM RATED
SYMBOL
BE RECESSED 3 F17T8 4100K UNV 51W 2GR8-317A125-UNV-EL-EB81 WHITE
RECESSED 2X4
EMERGENCY
TROFFER
RECESSED 2X2
TROFFER
RECESSED 2X2
EMERGENCY
TROFFER
COOPER - METALUX
COOPER - METALUX
COOPER - METALUX
2' X 2' RECESSED TROFFER, .125" THICK PRISMATIC LENS, 3-LAMPS,
ELECTRONIC PROGRAM START BALLAST, <10% THD.
FIXTURE SAME AS TYPE "B", EQUIPPED WITH EMERGENCY BATTERY BACKUP
BALLAST RATED FOR 1400 LUMENS. SEE NOTE 1.
EXISTING
PANEL A1 SERVICE: X SOLID NEUTRAL & GROUND STAINLESS STEEL FRONT
GROUND BUS 120 120/240 /1PH/3W ISOLATED GROUND BUS X SURFACE MOUNT
225 A BUS: MLO 200%NEUTRAL RECESS MOUNT
200 ----- A MCB X NEMA 1 ENCLOSURE FEED-THRU LUGS
10,000 AIC BREAKERS NEMA 3R ENCLOSURE SUB-FEED LUGS
VOLT- SERVING CODE WIRE GND CON- BRKR POLE CCT A C CCT POLE BRKR WIRE GND CON- CODE SERVING VOLT-
AMPS SIZE SIZE DUIT SIZE SIZE DUIT AMPS
750 Office #2 Lights 1 12 12 3/4" 20 1 1 1500 2 1 20 12 12 3/4" 1 Open Area Lights 750
750 Office #3,4,5 Lights 1 12 12 3/4" 20 1 3 1500 4 1 20 12 12 3/4" 1 Office #1,8, Sec. Lts. 750
750 Open Area Lights 1 12 12 3/4" 20 1 5 1500 6 1 20 12 12 3/4" 1 Mail Rm., Stor., Records 750
750 Office #6 & Waiting Lts. 1 12 12 3/4" 20 1 7 1500 8 1 20 12 12 3/4" 1 Office #8 & Lounge Lts. 750
750 Hall, Janitor, R.R. 1 12 12 3/4" 20 1 9 1500 10 1 20 12 12 3/4" 1 Open Area Lights 750
900 Office #1 & 4, Sec. Rec. 3 12 12 3/4" 20 1 11 1800 12 1 20 12 12 3/4" 3 Open Area Recep. 900
900Office 2,3,4,5, Lobby Rec. 3 12 12 3/4" 20 1 13 1800 14 1 20 12 12 3/4" 3 Off. 1,8, Open Area Rec. 900
900 Open Area Recep. 3 12 12 3/4" 20 1 15 1800 16 1 20 12 12 3/4" 3 Open Area, Records 900
1500 Copier (Note 3) 4 12 12 3/4" 20 1 17 2400 18 1 20 12 12 3/4" 3 Open area, Office, Wt. Rm. 900
900 Mail Rm., Off. 8, Lounge 3 12 12 3/4" 20 1 19 1400 20 1 20 12 12 3/4" 4 Clock & Intercom 500
900 Receptacles Misc. 3 12 12 3/4" 20 1 21 1800 22 1 20 12 12 3/4" 3 Floor Recep. 2nd Fl. 900
900 Floor Recep. 2nd Fl. 3 12 12 3/4" 20 1 23 1800 24 1 30 12 12 3/4" 3 Floor Recep. 2nd Fl. 900
2000 Range - Lounge 4 12 10 3/4" 30 2 25 3800 26 2 20/20 12 12 3/4" 3 Floor Recep. 2nd Fl. 1800
2000 Range - Lounge 4 12 10 3/4" - - 27 6196 28 2 60 6 10 3/4" Subfeed to 4196
900 Ice Box 4 12 12 3/4" 20 1 29 6000 30 - - 6 - - Panel A1A 5100
CONNECTED LOAD PHASE TOTAL 20300 15996
CONNECTED LOAD PHASE AMPS 169 133
NOTES:
1. INCREASE CONDUCTORS ONE WIRE SIZE FOR EVERY80 FT. RUN. INCREASE CONDUCTORS ONE WIRE SIZE FOR EVERY250 FT. RUN.
2. FIELD VERIFYEQUIPMENT LOADS. INCREASE CONDUCTORS ONE WIRE SIZE FOR EVERY80 FT. RUN.
TOTAL 3. CONTRACTOR SHALL RELOCATE EXISTINGCIRCUIT SERVINGCOPIER
FROMCIRCUIT #28 TOCIRCUIT #17
1 INTERIOR LIGHTING 125% 5,625 4,680 10,305
2 EXTERIOR LIGHTING 125% 0 0 0
RECEPTACLES:
3 GENERAL PURPOSE NEC220.44 5,485 7,145 12,630
4 DEDICATED 100% 5,900 2,500 8,400
5 AIR CONDITIONING 100% 2,196 2,196 4,392
6 WATER HEATER 100% 0 0 0
7 ELECTRIC HEAT 100% 0 0 0
8 MOTORS 100% 0 0 0
9 LARGEST MOTOR 125% 0 0 0
10 KITCHEN 100% 0 0 0
19,206 16,521 35,727
TOTAL PHASE AMPS PER NEC 19,206 160
TOTAL VA PER NEC
CODE
DEMAND
FACTOR
TOTAL A TOTAL C
NEW
PANEL A1A SERVICE: X SOLID NEUTRAL & GROUND STAINLESS STEEL FRONT
GROUND BUS 120 120/240 /1PH/3W ISOLATED GROUND BUS X SURFACE MOUNT
100 A BUS: MLO 200% NEUTRAL RECESS MOUNT
100 ----- A MCB X NEMA 1 ENCLOSURE FEED-THRULUGS
10,000 AIC BREAKERS NEMA 3R ENCLOSURE SUB-FEED LUGS
VOLT- SERVING CODE WIRE GND CON- BRKR POLE CCT A C CCT POLE BRKR WIRE GND CON- CODE SERVING VOLT-
AMPS SIZE SIZE DUIT SIZE SIZE DUIT AMPS
500 Breakroom Rec. 4 12 12 3/4" 20 1 1 1000 2 1 20 12 12 3/4" 3 Rec. Rm. by Elevator 500
1080 Office 102, 103 3 12 12 3/4" 20 1 3 2160 4 1 20 12 12 3/4" 3 Meeting 104, File 101 1080
500 Breakroom Rec. 4 12 12 3/4" 20 1 5 1000 6 1 20 12 12 3/4" 4 Breakroom Rec. 500
1980 ACCU-1 5 12 12 3/4" 20 2 7 2196 8 2 15 12 12 3/4" 5 FCU-1 216
1980 - 5 12 - - - - 9 2196 10 - - 12 - - 5 - 216
744 Lighting - Offices 1 12 12 3/4" 20 1 11 744 12 1 20 12 12 3/4" SPACE
SPACE 12 12 3/4" 20 1 13 0 14 1 20 12 12 3/4" SPACE
SPACE 12 12 3/4" 20 1 15 0 16 1 20 12 12 3/4" SPACE
SPACE 12 12 3/4" 20 1 17 0 18 1 20 12 12 3/4" SPACE
SPACE 12 12 3/4" 20 1 19 0 20 1 20 12 12 3/4" SPACE
CONNECTED LOAD PHASE TOTAL 4196 5100
CONNECTED LOAD PHASE AMPS 35 43
NOTES:
1. INCREASE CONDUCTORS ONE WIRE SIZE FOREVERY80 FT. RUN. INCREASE CONDUCTORS ONE WIRE SIZE FOREVERY250 FT. RUN.
2. FIELD VERIFYEQUIPMENT LOADS. INCREASE CONDUCTORS ONE WIRE SIZE FOREVERY80 FT. RUN.
TOTAL 3. PROVIDE LOCKABLE CIRCUIT BREAKER FORALL UNDERCABINET WATERHEATERS
PERNEC 422.31 AND 422.35.
1 INTERIOR LIGHTING 125% 0 930 930
2 EXTERIOR LIGHTING 125% 0 0 0
RECEPTACLES:
3 GENERAL PURPOSE NEC220.44 500 2,160 2,660
4 DEDICATED 100% 1,500 0 1,500
5 AIR CONDITIONING 100% 2,196 2,196 4,392
6 WATER HEATER 100% 0 0 0
7 ELECTRIC HEAT 100% 0 0 0
8 MOTORS 100% 0 0 0
9 LARGEST MOTOR 125% 0 0 0
10 KITCHEN 100% 0 0 0
4,196 5,286 9,482
TOTAL PHASE AMPS PER NEC 5,286 44
TOTAL VA PER NEC
CODE
DEMAND
FACTOR
TOTAL A TOTAL C
EXISTING
PANEL
"A1"
120/240V/1
225A MLO
30 SPACES
G
N
(3) #1
(1) #6 G.
1-1/2" C.
NEW
PANEL
"A1A"
120/240V/1
100A MLO
20 SPACES
G
N
(3) #6
(1) #10 G.
3/4" C.
ELECTRICAL PARTIAL ONE-LINE DIAGRAM
SCALE: N.T.S. 3
ELECTRICAL LOAD ANALYSIS
MHMRA PARTIAL RENOVATION OF BRISTOW CENTER
RICE & GARDNER CONSULTANTS, INC.
TOTAL AREA 4,210 sq.ft. SERVICE VOLTAGE
USE : OFFICE 2,675 sq.ft. 120/240V/1ph/3W
USE : CORR./RESTROOM 1,478 sq.ft. 277/480V/3ph/4W
USE : STORAGE 57 sq.ft. 120/208V/3ph/4W
120.000
LOAD DESCRIPTION CONNECTED DESIGN PH. A PH. C NEUTRAL
LOAD KVA AMPS AMPS AMPS
LIGHTS
CONNECTED LOAD KW 8.24 37.5 31.2 37.5
DESIGN LOAD BYSQ. FT.
PER NEC 220.12
OFFICE 3.50 W/sq.ft. 9.36
CORR./RR. 0.50 W/sq.ft. 0.74
STORAGE 0.25 W/sq.ft. 0.01
W/sq.ft. 0.00
OUTSIDE LIGHTING 0.00
SIGN LIGHTING 0.00
+ 25% 2.53
TOTAL LIGHTING 12.64 52.7 52.7 52.7
RECEPTACLES
GENERAL (NEC 220.44) 15.26 KW 15.26 56.7 70.5 70.5
DEDICATED (100%) 8.40 KW 8.40 49.2 20.8 49.2
AIR CONDITIONING 4.39 KW 4.39 18.3 18.3 18.3
WATER HEATER 0.00 KW 0.00 0.0 0.0 0.0
ELECTRIC HEAT 0.00 KW 0.00 0.0 0.0 0.0
MOTORS 0.00 KW 0.00 0.0 0.0 0.0
LARGEST MOTOR 0.00 KW 0.00 0.0 0.0 0.0
KITCHEN 0.00 KW 0.00 0.0 0.0 0.0
MISC/FUTURE 0.00 KW 0.00 0.0 0.0 0.0
TOTAL 40.7 176.8 162.3 176.8
TOTAL LOAD 177 AMPS
TOTAL CAPACITY 225 AMPS
SPARE CAPACITY 48 AMPS
2/12/2014
ELECTRICAL
E0.01
SYMBOLS AND
SCHEDULES
Drawn:
Sheet:
Checked:
Project:
Date:
02/12/14
02/12/14
&
6161 Savoy Drive; Suite #1212 Houston, TX 77036
PH. 713.482.2300 Fax 713-482-2314
Firm #F-9057
Sheet Title
Revision/Issues
02.12.2014
L
i
m
i
t
e
d

R
e
n
o
v
a
t
i
o
n

o
f

t
h
e

B
r
i
s
t
o
w

C
e
n
t
e
r
C
H
P

P
r
j

N
o
:

1
2
-
0
4
2
2
6
2
7

C
A
R
O
L
I
N
E

S
T
R
E
E
T
,

H
O
U
S
T
O
N
,

T
E
X
A
S
Issue for COH Permitting
and TDLR Review
M
H
M
R
A

O
F

H
A
R
R
I
S

C
O
U
N
T
Y