This document contains notes, symbols, and schedules for an electrical plan set. It includes:
- A legend listing common electrical symbols like receptacles, junction boxes, and circuit homeruns.
- Notes providing general guidance for the electrical work including following codes, verifying existing conditions, and coordinating with other disciplines.
- A fixture schedule listing lighting fixtures with details like manufacturer, wattage, and mounting type.
- Panel schedules for panels A1 and A1A showing circuit information and load calculations.
The document provides information needed for installing and connecting the electrical system shown in the plan set through its inclusion of symbols, notes, and equipment specifications.
This document contains notes, symbols, and schedules for an electrical plan set. It includes:
- A legend listing common electrical symbols like receptacles, junction boxes, and circuit homeruns.
- Notes providing general guidance for the electrical work including following codes, verifying existing conditions, and coordinating with other disciplines.
- A fixture schedule listing lighting fixtures with details like manufacturer, wattage, and mounting type.
- Panel schedules for panels A1 and A1A showing circuit information and load calculations.
The document provides information needed for installing and connecting the electrical system shown in the plan set through its inclusion of symbols, notes, and equipment specifications.
This document contains notes, symbols, and schedules for an electrical plan set. It includes:
- A legend listing common electrical symbols like receptacles, junction boxes, and circuit homeruns.
- Notes providing general guidance for the electrical work including following codes, verifying existing conditions, and coordinating with other disciplines.
- A fixture schedule listing lighting fixtures with details like manufacturer, wattage, and mounting type.
- Panel schedules for panels A1 and A1A showing circuit information and load calculations.
The document provides information needed for installing and connecting the electrical system shown in the plan set through its inclusion of symbols, notes, and equipment specifications.
SHOWN ON THIS SHEET ARE NOT ALL NECESSARILY USED ON THIS PROJECT. ELECTRICAL POWER PLANS ELECTRICAL SYMBOLS & SCHEDULES E0.01 ELECTRICAL LIGHTING & FIRE ALARM PLANS E1.01 E1.02 ELECTRICAL SPECIFICATIONS E7.01 FIRE ALARM SYMBOLS LEGEND: 120V, 20A DUPLEX RECEPTACLE 120V, 20A DUPLEX GROUND FAULT INTERRUPTER TYPE RECEPTACLE (GFCI). JUNCTION BOX NON-FUSED SAFETY DISCONNECT SWITCH CIRCUIT HOMERUN WITH (1) HOT, (1) NEUTRAL, AND (1) GROUND CIRCUIT HOMERUN WITH (2) HOTS, (1) NEUTRAL, AND (1) GROUND CIRCUIT HOMERUN WITH (3) HOTS, (1) NEUTRAL, AND (1) GROUND CIRCUIT HOMERUN WITH (3) HOTS AND (1) GROUND SYMBOLS DESCRIPTION CEILING SMOKE DETECTOR. INSTALL A 4" OCTAGON BOX WITH CADDY-BAR SUPPORT WHEN INSTALLED IN LAY-IN CEILING. CEILING MOUNTED HORN/STROBE. INSTALL A 4" OCTAGON BOX WITH CADDY-BAR SUPPORT WHEN INSTALLED IN LAY-IN CEILING. FIRE ALARM CONTRACTOR TO ENSURE ALL VISUAL DEVICES MEET PROPER SPACING AND ADA REQUIRED CANDELA SETTINGS PER NFPA 72. CEILING MOUNTED STROBE. INSTALL A 4" OCTAGON BOX WITH CADDY-BAR SUPPORT WHEN INSTALLED IN LAY-IN CEILING. FIRE ALARM CONTRACTOR TO ENSURE ALL VISUAL DEVICES MEET PROPER SPACING AND ADA REQUIRED CANDELA SETTINGS PER NFPA 72. WALL MOUNTED STROBE AT 80" AFF. TO THE BOTTOM OF DEVICE. INSTALL SINGLE GANG BOX AND 3/4" CONDUIT STUB ABOVE CEILING WITH INSULATED THROAT CONNECTOR. FIRE ALARM CONTRACTOR TO ENSURE ALL VISUAL DEVICES MEET PROPER SPACING AND ADA REQUIRED CANDELA SETTINGS PER NFPA 72. ALL STROBES TO BE 15/75cd UNLESS NOTED OTHERWISE. S POWER SYMBOLS LEGEND: DESCRIPTION SYMBOL 1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM TO BASE BUILDING SPECIFICATIONS, LOCAL CODES AND ORDINANCES, AND INDUSTRY STANDARDS. 2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO START OF CONSTRUCTION. 3. ALL ELECTRICAL RECEPTACLES, SWITCHES , MISCELLANEOUS DEVICES AND TRIM PLATES SHALL BE BUILDING STANDARD UNLESS NOTED OTHERWISE. 4. ALL PANELBOARDS SHALL HAVE CIRCUITS CLEARLY LABELED ACCORDING TO TENANT AND AREA SERVED. 5. CONTRACTOR MUST MARK ALL SWITCHES, THERMOSTATS, AND ADA STROBE LOCATION IN THE FIELD FOR REVIEWAND APPROVAL BY THE ARCHITECT BEFORE INSTALLATION. FAILURE TO DO SO WILL RESULT IN THE CONTRACTOR RELOCATING SUCH ITEMS WITHOUT ADDED EXPENSE TO THE OWNER, TENANT OR ARCHITECT. 6. THE ARCHITECTURAL POWER PLANS ARE TO BE USED FOR HEIGHTS AND APPROXIMATE LOCATIONS OF RECEPTACLES. THE MEP POWER PLANS ARE TO BE USED FOR CIRCUITING AND POWER REQUIREMENTS. NOTIFY THE ARCHITECT OF ANY DISCREPANCIES BETWEEN THE MEP AND ARCHITECTURAL POWER PLANS AND OBTAIN CLARIFICATION BEFORE COMMENCING CONSTRUCTION. 7. ALL COMPACT FLUORESCENT LIGHTING FIXTURES SHALL BE PROVIDED WITH LAMPS AND BALLASTS HAVING AN "END OF LIFE" PROTECTION FEATURE. 8. FIRE ALARM SYSTEM DEVICES SHALL MEET ALL ADA REQUIREMENTS, SHALL BE INSTALLED BY A LICENSED FIRE ALARM CONTRACTOR, AND SHALL COMMUNICATE WITH EXISTING BUILDING FIRE ALARM SYSTEM. COORDINATE FIRE ALARM INSTALLATION WITH MECHANICAL, ELECTRICAL, AND PLUMBING DISCIPLINES. 9. ALL SIZE #10, #12, AND #14 AWG CONDUCTORS SHALL BE SOLID COPPER. SIZE #8 AWG AND LARGER CONDUCTORS SHALL BE STRANDED COPPER. INSULATION SHALL BE TYPE THHN OR THWN. 10. SEAL ALL CONDUITS OR DATA CABLE PENETRATIONS OF FIRE RATED CONSTRUCTION WITH FACTORY BUILT DEVICES OR WITH MANUFACTURED FILL, VOID, OR CAVITY MATERIALS "CLASSIFIED" BY UNDERWRITERS LABORATORIES, INC. FOR USE AS A THROUGH-PENETRATION FIRESTOP. 11. ALL SWITCHES AND DEVICES INDICATED AS GROUPED TOGETHER, SHALL BE GANGED IN ONE COMMON COVER PLATE. 12. FIELD VERIFY PROPOSED LOCATIONS OF NEW ELECTRICAL EQUIPMENT PRIOR TO INSTALLATION IN ORDER TO MAINTAIN REQUIRED WORKING CLEARANCES PER THE NEC. CONTACT ENGINEER WHERE CONFLICT EXISTS PRIOR TO INSTALLATION. 13. INSTALL BLANK COVER PLATES OVER MOUNTING BOXES AND JUNCTION BOXES RENDERED EXPOSED DUE TO EQUIPMENT OR DEVICE REMOVAL. ELECTRICAL GENERAL NOTES 1 '-6 " FINISHED FLOOR RECEPTACLE, VOICE/DATA, ETC. ALL UNDER COMMON FACEPLATE. 3 '-6 " 4 '-6 " 6 '-8 " 1'-0" LIGHT SWITCHES, DIMMERS, EGRESS BUTTON, INTERCOM BUTTON, CARD READER, ETC. (RE: PLANS FOR QUANTITY OF EACH CLUSTER) ALL UNDER COMMON FACEPLATE. THERMOSTAT/SENSOR DOOR FRAME FIRE ALARM HORN/STROBE DEVICE MOUNTING DETAIL SCALE: N.T.S. 2 SYM KEY FIXTURE MANUFACTURER CATALOG NUMBER LAMPS NO. TYPE K TEMP VOLTS FINISH MOUNTING REMARKS NOTES: 1. PROVIDE 90 MINUTE BATTERY BACKUP BALLAST FOR ALL LUMINAIRES DESIGNATED WITH ('E') ON LIGHTING PLAN. LUMINAIRES SHALL BE SWITCHED ON AND OFF WITH OTHER FIXTURES ON CIRCUIT EXCEPT FOR DESIGNATED CORRIDOR NIGHT LIGHTS. PROVIDE UNSWITCHED HOT CONDUCTOR FROM NORMAL CIRCUIT TO EACH EMERGENCY BALLAST. 2. PROVIDE PROGRAM-START BALLAST FOR ALL LUMINAIRES CONNECTED VIA OCCUPANCY SENSORS. INPUT WATTS B LUMINAIRE SCHEDULE WHITE A RECESSED 2GR8-232A125-UNV-EB81 COOPER - METALUX 2 F32T8 4100K UNV RECESSED 2X4 TROFFER 62W RECESSED 3 F17T8 4100K UNV 51W X CEILING LPX7SD COOPER - SURE-LITES - RED LED - UNV EXIT SIGN <5W - WHITE POLYCARBONATE EXIT SIGN, SINGLE FACE, EMERGENCY BATTERY BACKUP AND SELF DIAGNOSTICS. ARROWINDICATES DIRECTION OF CHEVRONS, TO BE APPLIED IN FIELD. 2' X 4' RECESSED TROFFER, .125" THICK PRISMATIC LENS, 2-LAMPS, ELECTRONIC PROGRAM START BALLAST, <10% THD. 2GR8-317A125-UNV-EB81 AE RECESSED 2 4100K UNV F32T8 62W 2GR8-232A125-UNV-EL-EB81 WHITE WHITE # of Occupancy Sensors as shown on plans WattStopper LIGHTING CONTROLS DIAGRAM - OPEN AREA101 AND CONFERENCE 101D SCALE: N.T.S. 1 FIXTURE SAME AS TYPE "A", EQUIPPED WITH EMERGENCY BATTERY BACKUP BALLAST RATED FOR 1400 LUMENS. SEE NOTE 1. LIGHTING SYMBOLS LEGEND: DESCRIPTION WALL MOUNTED LOW-VOLTGAGE TOGGLE SWITCH: WATTSTOPPER LMSW-101 OR APPROVED EQUIVALENT WALL MOUNTED OCCUPANCY SENSOR SWITCH: WATTSTOPPER LMDW-101 OR APPROVED EQUIVALENT CEILING-MOUNTED OCCUPANCY SENSOR: WATTSTOPPER LMDC-100 OR APPROVED EQUIVALENT DIGITAL SWITCHING POWER PACK: WATTSTOPPER LMRC-101 OR APPROVED EQUIVALENT SWITCH ZONE BREAK CIRCUIT HOMERUN LOW VOLTAGE CONDUCTORS, PLENUM RATED SYMBOL BE RECESSED 3 F17T8 4100K UNV 51W 2GR8-317A125-UNV-EL-EB81 WHITE RECESSED 2X4 EMERGENCY TROFFER RECESSED 2X2 TROFFER RECESSED 2X2 EMERGENCY TROFFER COOPER - METALUX COOPER - METALUX COOPER - METALUX 2' X 2' RECESSED TROFFER, .125" THICK PRISMATIC LENS, 3-LAMPS, ELECTRONIC PROGRAM START BALLAST, <10% THD. FIXTURE SAME AS TYPE "B", EQUIPPED WITH EMERGENCY BATTERY BACKUP BALLAST RATED FOR 1400 LUMENS. SEE NOTE 1. EXISTING PANEL A1 SERVICE: X SOLID NEUTRAL & GROUND STAINLESS STEEL FRONT GROUND BUS 120 120/240 /1PH/3W ISOLATED GROUND BUS X SURFACE MOUNT 225 A BUS: MLO 200%NEUTRAL RECESS MOUNT 200 ----- A MCB X NEMA 1 ENCLOSURE FEED-THRU LUGS 10,000 AIC BREAKERS NEMA 3R ENCLOSURE SUB-FEED LUGS VOLT- SERVING CODE WIRE GND CON- BRKR POLE CCT A C CCT POLE BRKR WIRE GND CON- CODE SERVING VOLT- AMPS SIZE SIZE DUIT SIZE SIZE DUIT AMPS 750 Office #2 Lights 1 12 12 3/4" 20 1 1 1500 2 1 20 12 12 3/4" 1 Open Area Lights 750 750 Office #3,4,5 Lights 1 12 12 3/4" 20 1 3 1500 4 1 20 12 12 3/4" 1 Office #1,8, Sec. Lts. 750 750 Open Area Lights 1 12 12 3/4" 20 1 5 1500 6 1 20 12 12 3/4" 1 Mail Rm., Stor., Records 750 750 Office #6 & Waiting Lts. 1 12 12 3/4" 20 1 7 1500 8 1 20 12 12 3/4" 1 Office #8 & Lounge Lts. 750 750 Hall, Janitor, R.R. 1 12 12 3/4" 20 1 9 1500 10 1 20 12 12 3/4" 1 Open Area Lights 750 900 Office #1 & 4, Sec. Rec. 3 12 12 3/4" 20 1 11 1800 12 1 20 12 12 3/4" 3 Open Area Recep. 900 900Office 2,3,4,5, Lobby Rec. 3 12 12 3/4" 20 1 13 1800 14 1 20 12 12 3/4" 3 Off. 1,8, Open Area Rec. 900 900 Open Area Recep. 3 12 12 3/4" 20 1 15 1800 16 1 20 12 12 3/4" 3 Open Area, Records 900 1500 Copier (Note 3) 4 12 12 3/4" 20 1 17 2400 18 1 20 12 12 3/4" 3 Open area, Office, Wt. Rm. 900 900 Mail Rm., Off. 8, Lounge 3 12 12 3/4" 20 1 19 1400 20 1 20 12 12 3/4" 4 Clock & Intercom 500 900 Receptacles Misc. 3 12 12 3/4" 20 1 21 1800 22 1 20 12 12 3/4" 3 Floor Recep. 2nd Fl. 900 900 Floor Recep. 2nd Fl. 3 12 12 3/4" 20 1 23 1800 24 1 30 12 12 3/4" 3 Floor Recep. 2nd Fl. 900 2000 Range - Lounge 4 12 10 3/4" 30 2 25 3800 26 2 20/20 12 12 3/4" 3 Floor Recep. 2nd Fl. 1800 2000 Range - Lounge 4 12 10 3/4" - - 27 6196 28 2 60 6 10 3/4" Subfeed to 4196 900 Ice Box 4 12 12 3/4" 20 1 29 6000 30 - - 6 - - Panel A1A 5100 CONNECTED LOAD PHASE TOTAL 20300 15996 CONNECTED LOAD PHASE AMPS 169 133 NOTES: 1. INCREASE CONDUCTORS ONE WIRE SIZE FOR EVERY80 FT. RUN. INCREASE CONDUCTORS ONE WIRE SIZE FOR EVERY250 FT. RUN. 2. FIELD VERIFYEQUIPMENT LOADS. INCREASE CONDUCTORS ONE WIRE SIZE FOR EVERY80 FT. RUN. TOTAL 3. CONTRACTOR SHALL RELOCATE EXISTINGCIRCUIT SERVINGCOPIER FROMCIRCUIT #28 TOCIRCUIT #17 1 INTERIOR LIGHTING 125% 5,625 4,680 10,305 2 EXTERIOR LIGHTING 125% 0 0 0 RECEPTACLES: 3 GENERAL PURPOSE NEC220.44 5,485 7,145 12,630 4 DEDICATED 100% 5,900 2,500 8,400 5 AIR CONDITIONING 100% 2,196 2,196 4,392 6 WATER HEATER 100% 0 0 0 7 ELECTRIC HEAT 100% 0 0 0 8 MOTORS 100% 0 0 0 9 LARGEST MOTOR 125% 0 0 0 10 KITCHEN 100% 0 0 0 19,206 16,521 35,727 TOTAL PHASE AMPS PER NEC 19,206 160 TOTAL VA PER NEC CODE DEMAND FACTOR TOTAL A TOTAL C NEW PANEL A1A SERVICE: X SOLID NEUTRAL & GROUND STAINLESS STEEL FRONT GROUND BUS 120 120/240 /1PH/3W ISOLATED GROUND BUS X SURFACE MOUNT 100 A BUS: MLO 200% NEUTRAL RECESS MOUNT 100 ----- A MCB X NEMA 1 ENCLOSURE FEED-THRULUGS 10,000 AIC BREAKERS NEMA 3R ENCLOSURE SUB-FEED LUGS VOLT- SERVING CODE WIRE GND CON- BRKR POLE CCT A C CCT POLE BRKR WIRE GND CON- CODE SERVING VOLT- AMPS SIZE SIZE DUIT SIZE SIZE DUIT AMPS 500 Breakroom Rec. 4 12 12 3/4" 20 1 1 1000 2 1 20 12 12 3/4" 3 Rec. Rm. by Elevator 500 1080 Office 102, 103 3 12 12 3/4" 20 1 3 2160 4 1 20 12 12 3/4" 3 Meeting 104, File 101 1080 500 Breakroom Rec. 4 12 12 3/4" 20 1 5 1000 6 1 20 12 12 3/4" 4 Breakroom Rec. 500 1980 ACCU-1 5 12 12 3/4" 20 2 7 2196 8 2 15 12 12 3/4" 5 FCU-1 216 1980 - 5 12 - - - - 9 2196 10 - - 12 - - 5 - 216 744 Lighting - Offices 1 12 12 3/4" 20 1 11 744 12 1 20 12 12 3/4" SPACE SPACE 12 12 3/4" 20 1 13 0 14 1 20 12 12 3/4" SPACE SPACE 12 12 3/4" 20 1 15 0 16 1 20 12 12 3/4" SPACE SPACE 12 12 3/4" 20 1 17 0 18 1 20 12 12 3/4" SPACE SPACE 12 12 3/4" 20 1 19 0 20 1 20 12 12 3/4" SPACE CONNECTED LOAD PHASE TOTAL 4196 5100 CONNECTED LOAD PHASE AMPS 35 43 NOTES: 1. INCREASE CONDUCTORS ONE WIRE SIZE FOREVERY80 FT. RUN. INCREASE CONDUCTORS ONE WIRE SIZE FOREVERY250 FT. RUN. 2. FIELD VERIFYEQUIPMENT LOADS. INCREASE CONDUCTORS ONE WIRE SIZE FOREVERY80 FT. RUN. TOTAL 3. PROVIDE LOCKABLE CIRCUIT BREAKER FORALL UNDERCABINET WATERHEATERS PERNEC 422.31 AND 422.35. 1 INTERIOR LIGHTING 125% 0 930 930 2 EXTERIOR LIGHTING 125% 0 0 0 RECEPTACLES: 3 GENERAL PURPOSE NEC220.44 500 2,160 2,660 4 DEDICATED 100% 1,500 0 1,500 5 AIR CONDITIONING 100% 2,196 2,196 4,392 6 WATER HEATER 100% 0 0 0 7 ELECTRIC HEAT 100% 0 0 0 8 MOTORS 100% 0 0 0 9 LARGEST MOTOR 125% 0 0 0 10 KITCHEN 100% 0 0 0 4,196 5,286 9,482 TOTAL PHASE AMPS PER NEC 5,286 44 TOTAL VA PER NEC CODE DEMAND FACTOR TOTAL A TOTAL C EXISTING PANEL "A1" 120/240V/1 225A MLO 30 SPACES G N (3) #1 (1) #6 G. 1-1/2" C. NEW PANEL "A1A" 120/240V/1 100A MLO 20 SPACES G N (3) #6 (1) #10 G. 3/4" C. ELECTRICAL PARTIAL ONE-LINE DIAGRAM SCALE: N.T.S. 3 ELECTRICAL LOAD ANALYSIS MHMRA PARTIAL RENOVATION OF BRISTOW CENTER RICE & GARDNER CONSULTANTS, INC. TOTAL AREA 4,210 sq.ft. SERVICE VOLTAGE USE : OFFICE 2,675 sq.ft. 120/240V/1ph/3W USE : CORR./RESTROOM 1,478 sq.ft. 277/480V/3ph/4W USE : STORAGE 57 sq.ft. 120/208V/3ph/4W 120.000 LOAD DESCRIPTION CONNECTED DESIGN PH. A PH. C NEUTRAL LOAD KVA AMPS AMPS AMPS LIGHTS CONNECTED LOAD KW 8.24 37.5 31.2 37.5 DESIGN LOAD BYSQ. FT. PER NEC 220.12 OFFICE 3.50 W/sq.ft. 9.36 CORR./RR. 0.50 W/sq.ft. 0.74 STORAGE 0.25 W/sq.ft. 0.01 W/sq.ft. 0.00 OUTSIDE LIGHTING 0.00 SIGN LIGHTING 0.00 + 25% 2.53 TOTAL LIGHTING 12.64 52.7 52.7 52.7 RECEPTACLES GENERAL (NEC 220.44) 15.26 KW 15.26 56.7 70.5 70.5 DEDICATED (100%) 8.40 KW 8.40 49.2 20.8 49.2 AIR CONDITIONING 4.39 KW 4.39 18.3 18.3 18.3 WATER HEATER 0.00 KW 0.00 0.0 0.0 0.0 ELECTRIC HEAT 0.00 KW 0.00 0.0 0.0 0.0 MOTORS 0.00 KW 0.00 0.0 0.0 0.0 LARGEST MOTOR 0.00 KW 0.00 0.0 0.0 0.0 KITCHEN 0.00 KW 0.00 0.0 0.0 0.0 MISC/FUTURE 0.00 KW 0.00 0.0 0.0 0.0 TOTAL 40.7 176.8 162.3 176.8 TOTAL LOAD 177 AMPS TOTAL CAPACITY 225 AMPS SPARE CAPACITY 48 AMPS 2/12/2014 ELECTRICAL E0.01 SYMBOLS AND SCHEDULES Drawn: Sheet: Checked: Project: Date: 02/12/14 02/12/14 & 6161 Savoy Drive; Suite #1212 Houston, TX 77036 PH. 713.482.2300 Fax 713-482-2314 Firm #F-9057 Sheet Title Revision/Issues 02.12.2014 L i m i t e d
R e n o v a t i o n
o f
t h e
B r i s t o w
C e n t e r C H P
P r j
N o :
1 2 - 0 4 2 2 6 2 7
C A R O L I N E
S T R E E T ,
H O U S T O N ,
T E X A S Issue for COH Permitting and TDLR Review M H M R A