TABLE FOR FUNCTIONAL PARAMETERS P442

BACKUP PROTECTION 21/67/67N


NG DY 220KV A NHIM - DI LINH, CT MY CT
271
(nh km bng tr s _ _ _ _ _ _ _ _ /CV-MN-P.TT ngy _ _ _ thng _ _ _ nm 2007)

PARAMETERS SETTING RANGE
SETTING
VALUE
DISTANCE
ELEMENT
Line Settings

Line Length 0.3 - 1000Km step 0.025Km 76.38
Line Impedance 0.001 - 500W step 0.001W 1.9
Line Angle -900 - +900 step 1.00 80

Zone Settings

Zone Status Bit 0: Z1X Enable 00011110

Bit 1: Z2 Enable


Bit 2: ZP Enable


Bit 3: Z3 Enable


Bit 4: Z4 Enable


KZ1 Res Comp 0 - 7 step 0.001 0.7
KZ1 Angle 0 - 3600 step 1.00 -11
Z1 0.001/In - 500/In W step 0.001/In W 1.62
Z1X 0.001/In - 500/In W step 0.001/In W 1.62
R1G 0 - 400/In W step 0.01/In W 2.22
R1PH 0 - 400/In W step 0.01/In W 1.5
tZ1 0 - 10s step 0.002s 0s

KZ2 Res Comp 0 - 7 step 0.001 0.7
KZ2 Angle 0 - 3600 step 1.00 -11
Z2 0.001/In - 500/In W step 0.001/In W 2.28
R2G 0 - 400/In W step 0.01/In W 2.5
R2PH 0 - 400/In W step 0.01/In W 1.73
tZ2 0 - 10s step 0.01s 0.5

KZ3/4 Res Comp 0 - 7 step 0.01 0.7
KZ3/4 Angle 0 - 3600 step 1.00 -11
Z3 0.001/In - 500/In W step 0.001/In W 4.1
R3G - R4G 0 - 400/In W step 0.01/In W 2.8
R3PH - R4PH 0 - 400/In W step 0.01/In W 2.16
tZ3 0 - 10s step 0.01s 1.0

Z4 0.001/In - 500/In W step 0.001/In W 0.27
tZ4 0 - 10s step 0.01s 2.0s

Zone P - Direct. Forward or Reverse Forward
KZp Res Comp 0 - 7 step 0.001 0.7
KZp Angle 0 - 3600 step 1.00 -11
Zp 0.001/In - 500/In W step 0.001/In W 4.1
RpG 0 - 400/In W step 0.01/In W 2.8
RpPH 0 - 400/In W step 0.01/In W 2.16
tZp 0 - 10s step 0.01s 1.0

Fault Locator

KZm Mutual Comp 0 - 7 step 0.001 0
KZm Angle 0 - 3600 step 1.00 0
CHANNEL-AIDED
SCHEMES
Distance Schemes

Program Mode Standard Scheme
Standard
Scheme

Open Scheme


Standard Mode Basic + Z1X POP Z2

POP Z1


POP Z2


PUP Z2


PUP Fwd


BOP Z1


BOP Z2


Fault Type Phase to Ground Fault Enable Both Enable

Phase to Phase Fault Enable


Both Enable


Trip Mode Force 3 Poles
1 Pole Z1 Z2 &
Carrier Receive

1 Pole Z1 & Carrier Receive


1 Pole Z1 Z2 & Carrier Receive


Sig. Send Zone None CsZ2

CsZ1


CsZ2


CsZ4


Distance Carrier
Receive
None Permissive Z2

Permissive Z1


Permissive Z2


Permissive Forward


Block Z1


Block Z2


Tp 0 - 1s step 0.002s 0.1
tReversal Guard 0 - 0.15s step 0.002s 0.08s

TOR-SOTF Mode Bit 0 : Z1 Enable 00000011

Bit 1 : Z2 Enable


Bit 2 : Z3 Enable


Bit 3 : All Zones


Bit 4 : Dist. Scheme Enable

Z1 Ext./Chan. Fail Disabled or Enabled Disabled

Weak Infeed

Mode Status Disable Trip & Echo

Echo


Trip & Echo


Single Pole Trip Disabled or Enabled Enabled
V< Thres. 10 - 70V step 5V 55
Trip Time Delay 0 - 1.0s step 0.002s 0.2

Loss of Load

Mode Status Disabled or Enabled Disabled
Chan. Fail Disabled or Enabled Disabled
I< 0.05 - 1.0 In step 0.05 In 0.5In
Window 0.01 - 1.0s step 0.01s 0.04

POWER SWING
BLOCKING
Delta R 0 - 400/In W step 0.01/In W 0.81
Delta X 0 - 400/In W step 0.01/In W 0.81
IN > Status Disabled or Enabled Enabled
IN > (% Imax) 10% - 100% step 1% 40
I2> Status Disabled or Enabled Enabled
I2> (% Imax) 10% - 100% step 1% 30
Imax Line > Status Disabled or Enabled Enabled
Imax Line > 1.0 In - 20 In step 0.01 In 2.0
Unblock. Delay 0 - 30s step 0.1s 0.0

Blocked Zones Bit 0 : Z1&Z1X Block 00001111

Bit 1 : Z2 Block


Bit 2 : Z3 Block


Bit 3 : Zp Block


DIRECTIONAL AND
NON-DIRECTIONAL
OVERCURRENT
PROTECTION

I>1 Function Disabled IEC S Inverse

DT


IEC S Inverse


IEC V Inverse


IEC E Inverse


UK LT Inverse


IEEE M Inverse


IEEE V Inverse


IEEE E Inverse


US Inverse


US ST Inverse


I>1 Direction Non-Directional Directional Fwd

Directional Fwd


Directional Rev


I>1 VTS Block Block or Non-Directional Non-Directional
I>1 Current Set 0.08 In - 4.0 In step 0.01 In 2.4
I>1 Time Delay 0 - 100s step 0.01s

I>1 Time Delay VTS 0 - 100s step 0.01s 1.5s
I>1 TMS 0.025 - 1.2 step 0.025 0.1
I>1 Time Dial 0.5 - 15 step 0.1

I>1 Reset Char DT or Inverse

I>1 tReset 0 - 100s step 0.01s


I>2 Function Disabled DT

DT


IEC S Inverse


IEC V Inverse


IEC E Inverse


UK LT Inverse


IEEE M Inverse


IEEE V Inverse


IEEE E Inverse


US Inverse


US ST Inverse


I>2 Direction Non-Directional Directional Fwd

Directional Fwd


Directional Rev


I>2 VTS Block Block or Non-Directional Non-Directional
I>2 Current Set 0.08 In - 4.0 In step 0.01 In 2.6
I>2 Time Delay 0 - 100s step 0.01s 0.5
I>2 Time Delay VTS 0 - 100s step 0.01s 1.5s
I>2 TMS 0.025 - 1.2 step 0.025

I>2 Time Dial 0.5 - 15 step 0.1

I>2 Reset Char DT or Inverse

I>2 tReset 0 - 100s step 0.01s


I>3 Status Disabled or Enabled Disabled
I>3 Current Set 0.08 In - 32 In step 0.01 In

I>3 Time Delay 0 - 100s step 0.01s


I>4 Status Disabled or Enabled Disabled
I>4 Current Set 0.08 In - 32 In step 0.01 In

I>4 Time Delay 0 - 100s step 0.01s


NEGATIVE
SEQUENCE
OVERCURRENT
PROTECTION

I2> Status Disabled or Enabled Disabled

I2> Direction Non-Directional


Directional Fwd


Directional Rev


I2> VTS Block or Non-Directional

I2> Current Set 0.08 In - 4.0 In step 0.01 In

I2> Time Delay 0 - 100s step 0.01s

I2> Char Angle -950 - +950 step 1.00


BROKEN
CONDUCTOR
DETECTION

Broken Conductor Disabled or Enabled Enabled
I2/I1 0.2 - 1 step 0.01 0.76
I2/I1 Time Delay 0 - 100s step 0.1s 60s

DIRECTIONAL AND
NON-DIRECTIONAL
EARTH FAULT
PROTECTION

IN>1 Fuction Disabled IEC S Inverse

DT


IEC S Inverse


IEC V Inverse


IEC E Inverse


UK LT Inverse


IEEE M Inverse


IEEE V Inverse


IEEE E Inverse


US Inverse


US ST Inverse


IN>1 Direction Non-Directional Directional Fwd

Directional Fwd


Directional Rev


IN>1 VTS Block Block or Non-Directional Non-Directional
IN>1 Current Set 0.08 In - 4.0 In step 0.01 In 0.2
IN>1 Time Delay 0 - 200s step 0.01s

IN>1 Time Delay VTS 0 - 200s step 0.01s 1.5s
IN>1 TMS 0.025 - 1.2 step 0.025 0.3
IN>1 Time Dial 0.5 - 15 step 0.1

IN>1 Reset Char DT or Inverse

IN>1 tReset 0 - 100s step 0.01s


IN>2 Status Disabled or Enabled Enabled

IN>2 Direction Non-Directional Directional Fwd

Directional Fwd


Directional Rev


IN>2 VTS Block Block or Non-Directional Non-Directional
IN>2 Current Set 0.08 In - 32 In step 0.01In 3.0
IN>2 Time Delay 0 - 200s step 0.01s 0.3
IN>2 Time Delay VTS 0 - 200s step 0.01s 0.3

IN> Directional

IN> Char. Angle -950 - +950 step 10 - 600
Polarisation Zero Sequence or Negative Sequence Zero Sequence

CHANNEL AIDED
DIRECTIONAL
EARTH FAULT
PROTECTION

Aided DEF Status Disabled or Enabled Disabled
Polarisation Zero Sequence or Negative Sequence Zero Sequence
V> Voltage Set 0.05 - 20V step 0.05V 2V
IN Forward> 0.05 In - 4.0 In step 0.01In 0.1
Time Delay 0 - 10s step 0.1s 0.2
Scheme Logic Shared, Blocking or Permissive Permissive
Tripping Three Phase or Single Phase 3-Phase

VOLTAGE
PROTECTION
V< & V> Mode Bit 0 : V<1 Trip 00000100

Bit 1 : V<2 Trip


Bit 2 : V>1 Trip


Bit 3 : V>2 Trip

Undervoltage

V< Measur't Mode Phase-Phase or Phase-Neutral Phase-Phase
V<1 Function Disabled, DT or IDMT Disabled
V<1 Voltage Set 10 - 120V step 1.0V

V<1 Time Delay 0 - 100s step 0.01s

V<1 TMS 0.5 - 100 step 0.5

V<2 Status Enabled or Disabled Disabled
V<2 Voltage Set 10 - 120V step 1.0V

V<2 Time Delay 0 - 100s step 0.01s

V<2 Poledead Inh Enabled or Disabled


Overvoltage

V> Measur't Mode Phase-Phase or Phase-Neutral Phase-Phase
V>1 Function Disabled, DT or IDMT DT
V>1 Voltage Set 60 - 185V step 1.0V 128V
V>1 Time Delay 0 - 100s step 0.01s 1.0s
V>1 TMS 0.5 - 100 step 0.5

V>2 Status Enabled or Disabled Disabled
V>2 Voltage Set 60 - 185V step 1.0V

V>2 Time Delay 0 - 100s step 0.01s


CIRCUIT BREAKER
FAILURE
Breaker Fail

CB Fail 1 Status Enabled, Disabled Enabled
CB Fail 1 Time 0 - 10s step 0.01s 0.15s
CB Fail 2 Status Enabled, Disabled Enabled
CB Fail 2 Time 0 - 10s step 0.01s 0.3s

CBF Non I Reset I< Only Prot Reset & I<

CB Open & I<


Prot Reset & I<


CBF Ext Reset I< Only I< Only

CB Open & I<


Prot Reset & I<

Undercurrent

I< Current Set 0.05 In - 3.2 In step 0.01 In 0.2 In

VOLTAGE
TRANSFORMER
SUPERVISION

VTS Time Delay 1 - 20s step 1.0s 1s
VTS I2> & I0> Inhibit 0 - 1.0 In step 0.01 In 0.05In
Detect 3P Enabled or Disabled Enabled
Threshold 3P U< 10 - 70V step 1.0V 30V
Delta I> 0.01 - 5.0A step 0.01A 0.1In

CURRENT
TRANSFORMER
SUPERVISION

CTS Status Enabled or Disabled Disabled
CTS VN< Inhibit 0.5 - 22V step 0.5V

CTS IN> Set 0.08 In - 4.0 In step 0.01In

CTS Time Delay 0 - 10s step 1.0s


CHECK
SYNCHRONISATIO
N

C/S Check Scheme
for A/R
Bit 0 : Live Bus/Dead Line 00000000

Bit 1 : Dead Bus/Live Line


Bit 2 : Live Bus/Live Line


C/S Check Scheme
for Man CB
Bit 0 : Live Bus/Dead Line 00000000

Bit 1 : Dead Bus/Live Line


Bit 2 : Live Bus/Live Line


V< Dead Line 5 - 30V step 1.0V

V> Live Line 30 - 120V step 1.0V

V< Dead Bus 5 - 30V step 1.0V

V> Live Bus 30 - 120V step 1.0V

Diff Voltage 0.5 - 40V step 0.1V

Diff Frequence 0.02 - 1.0Hz step 0.01Hz

Diff Phase 50 - 900 step 2.50

Bus - Line Delay 0.1 - 2.0s step 0.1s


AUTO RECLOSE

1P Trip Mode 1, 1/3, 1/3/3, 1/3/3/3.

3P Trip Mode 3, 3/3, 3/3/3, 3/3/3/3.

1P Rcl-DT 1 0.1 - 5.0s step 0.01s

3P Rcl-DT 1 0.1 - 60s step 0.01s

Dead Time 2 1 - 3600s step 1.0s default
Dead Time 3 1 - 3600s step 1.0s default
Dead Time 4 1 - 3600s step 1.0s default
Reclaim Time 1 - 600s step 1.0s 180s
Close Pulse 0.1 - 10s step 0.01s 0.2s
A/R Inhibit Wind 1 - 3600s step 1.0s 5s
C/S on 3P Rcl DT1

Enabled

Autoreclose
Lockout
Block A/R Bit 0 : At tZ2
1111111111111
1

Bit 1 : At tZ3


Bit 2 : At tZp


Bit 3 : LoL Trip


Bit 4 : I2> Trip


Bit 5 : I>1 Trip


Bit 6 : I>2 Trip


Bit 7 : V<1 Trip


Bit 8 : V<2 Trip


Bit 9 : V>1 Trip


Bit 10 : V>2 Trip


Bit 11 : IN>1 Trip


Bit 12 : IN>2 Trip


Bit 13 : Aided DEF Trip


CT and VT Ratio
Settings
Current transformer

Primary 1 - 30000A step 1A 600
Secondary 1 or 5 Amps 5
Voltage transformer

Primary 100V - 1000kV step 1V 230000
Secondary 80 - 140V 110

Configuration


Active setting

Group 1
Setting group 1

Enabled
Distance

Enabled
Power Swing

Enabled
Back up I>

Enabled
Neg. Sequence O/C

Disabled
Broken conductor

Enabled
Earth fault O/C

Enabled
Aided DEF

Enabled
Volt Protection

Enabled
CB Fail & I<

Enabled
Supervision

Enabled
System check

Disabled
Internal A/R

Disabled
Input labels

Visible
Output labels

Visible
CT& VT ratios

Visible
Event recorder

Visible
Disturbance recorder

Visible
Measure't Setup

Visible
Comms. Setting

Visible
Setting values

secondary
Circuit Breaker
Status Monitoring
None/52A/52B/52A and 52B 52A and 52B

Circuit Breaker

Control
CB control by Disabled/Local/Remote/Local+Remote/Opto/ Opto+Local

Opto+Local/Opto+Remote/Opto+Local+Remot
e

Manual close pulse
time
0.1s - 10s 0.2s
Trip pulse time 0.1s - 5s 0.2s
Man close delay 0.01s - 600s 2s
Healthy window 0.01s - 9999s 5.0s
C/S window 0.01s - 9999s 5.0s
A/R Single pole Disabled/Enabled Disabled
A/R Three pole Disabled/Enabled Disabled

Circuit Breaker
Condition
Monitoring

Lockout reset by None/CB close/User interface CB close
Manual close reset
delay
0.01s - 600s 5s

INPUTS

Circuit Breaker
Position
VT'S Line MCB
Position
Breaker Fail Init

Signal Received

Chanel Out of
Service

OUTPUTS

Tripping coil A

Tripping coil B

Tripping coil C

Trip and Lockout -
Tripping 1
Trip and Lockout -
Tripping 2
Auto Reclose Init

Phase A
Auto Reclose Init
Phase B
Auto Reclose Init
Phase C
Block Auto Reclose

Signal send



GHI CH:

_Tn hiu trip 1, 3 pha
vng 1, vng 2 t b
Backup protection c
a vo b Main
protection

khi ng chc nng
t ng li.