Definition& Design, specify, and procure the hardware*software used in the system.

CAP uestion
+hich of the following protection techniques is accepta$le for equipment located in
a %lass I, Division 1 area,
'. ,xplosion)proof apparatus an! non)incen!ive equipment
(. ,xplosion)proof apparatus an! intrinsic safety
%. Dust ignition)proof an! non)incen!ive equipment
D. Hermetically seale! an! intrinsic safety
CAP ans!er
+he best answer is (' explosion)proof apparatus an! intrinsic safety.
Ha-ar!ous location protection techniques are !efine! by .,C /00.1 $.,C 2002 Co!e&.
+he protection techniques are permitte! as follows3
,xplosion proof apparatus4Class I' Division 5 or 2
Intrinsic safety4Class I' Division 5 or 26 Class II' Division 5 or 26 or Class III'
Division 5 or 2
.onincen!ive equipment4Class I' Division 26 Class II' Division 26 or Class III'
Division 5 or 2 $!oes not inclu!e Class 5' Division 5&
Dust ignition proof4Class II' Division 5 or 2 $!oes not inclu!e Class I' Division
5&
Hermetically seale!4Class I' Division 26 Class II' Division 26 Class III' Division
5 or 2 $!oes not inclu!e Class I' Division 5&
1 August 2005
ISA Certified Control Systems Technician (CCST) Program
+his question is from the %evel III stu!y gui!e' Domain 2' %oop chec(ing.
%evel III represents a professional who has a 57)year total of e!ucation' training' an!8or
experience.