DESIGN BASIS L15 - 25X40M

LOCATION VIZAG
MAIN FRAME
Frame Type : Clear Span, Rigid Frame, Curved Roof
Support FIXED
Building Width : 25 m (I/I RCC Columns)
Building Length : 40 m (O/O RCC Columns)
Bay Spacing : 7 @ 6.0 m
Clear Height : 6.3 m
END WALL / GABLE FRAMES
Interior Column Spacing : 4 @ 6.3 m
PURLIN TYPE
Roof Purlin : Continuous
Spacing 1.5 m C/C
PANEL TYPE
Roof : Galvalume sheet
MAIN FRAME LOADINGS
DESIGN LOADS
1. DEAD LOAD
A). Self Weight of Sheeting , Fastners,electrical & light fittings = 8 Kg/m
B). Pipe Load = 10 Kg/m
C). Self Weight of Purlin = 7 Kg/m
TOTAL DEAD LOAD = 25 Kg/m
D). Weight for cable tray on column (Loading can be seen in staad) = 500 Kg
E). Load at Beam(grid A & H) = 1 Ton
F). Load at Beam(grid B TO G) = 15 Kg/m^2
= 0.15 Ton
2. LIVE LOAD = 75 Kg/m
3. WIND LOAD
Basic Wind Speed =Vb = 50.00 m/s (Ref. Appendix A (Clause 5.2, IS : 875 Part III)
Design Wind Speed =Vz =Vb * k1 * k2 * k3
where k1 =Probability Factor = 1.0
k2 =Terrain, height and structure size factor = 0.98
k3 =Topography Factor = 1.0
Vz = 50.00 * 1.0 * 0.98 * 1.0 = 49.00 m/s
Design Wind Pressure =0.06 Vz^2 = 144.06 Kg/m
H/W = 0.25
L/W = 1.6
Wind Pressure Coefficients
Opening in the building has been considered More than 20 % accordingly internal pressure
coefficient taken as +-0.7 (As per IS- 875 Part III)
-1.00 -0.40 -0.70 -0.70
-0.7 -0.7
0.7 0.7
0.8 -0.6 -0.5 -0.50
Case 1 >>>0 Case 2 >>>90
-1.70 -1.10 -1.40 -1.40
-0.7 -0.7

0.10 Internal suction air pressure -1.3 -1.20 Internal suction air pressure -1.20
Design Case 1(A) Design Case 2(A)
-0.30 0.30 0.00 0.00
0.7 0.7

1.50 Internal positive air pressure 0.10 0.20 Internal positive air pressure 0.20
Design Case 1(B) Design Case 2(B)
LOADING DATA
I. DL = 25 * 6.000 = 150 Kg/m
II. LL = 75 * 6.000 = 450 Kg/m
0.15 T/m 0.15 T/m 0.45 T/m 0.45 T/m






DEAD LOAD LIVE LOAD
Case 1(A) : 0 Wind
III. WL on left column = 0.10 * 144.06 * 6 = 86.44 Kg/m
IV. WL on left roof = -1.70 * 144.06 * 6 = -1469.41 Kg/m
V. WL on right column = -1.30 * 144.06 * 6 = -1123.67 Kg/m
VI. WL on right roof = -1.10 * 144.06 * 6 = -950.80 Kg/m
Case 1(B) : 0 Wind
III. WL on left column = 1.50 * 144.06 * 6 = 1296.54 Kg/m
IV. WL on left roof = -0.30 * 144.06 * 6 = -259.31 Kg/m
V. WL on right column = 0.10 * 144.06 * 6 = 86.44 Kg/m
VI. WL on right roof = 0.30 * 144.06 * 6 = 259.31 Kg/m
-1.47 T/m -0.95 T/m -0.26 T/m 0.26 T/m



0.09 -1.12 T/m 1.30 0.09
T/m T/m T/m

Case 1(A) : Wind Load 0 Case 1(B) : Wind Load 0
Case 2(A) : 90 Wind .
IX. WL on left column = -1.20 * 144.06 * 6 = -1037.23 Kg/m
X. WL on left roof = -1.40 * 144.06 * 6 = -1210.10 Kg/m
XI. WL on right column = -1.20 * 144.06 * 6 = -1037.23 Kg/m
XII. WL on right roof = -1.40 * 144.06 * 6 = -1210.10 Kg/m
Case 2(B) : 90 Wind
IX. WL on left column = 0.20 * 144.06 * 6 = 172.87 Kg/m
X. WL on left roof = 0.00 * 144.06 * 6 = 0.00 Kg/m
XI. WL on right column = 0.20 * 144.06 * 6 = 172.87 Kg/m
XII. WL on right roof = 0.00 * 144.06 * 6 = 0.00 Kg/m
-1.21 T/m -1.21 T/m 0.00 T/m 0.00 T/m



-1.04 -1.04 T/m 0.17 0.17
T/m T/m T/m

Case 2(A) : Wind Load 90 Case 2(B) : Wind Load 90