TRANSFORMER DATA SHEET

M&M CHOCOLATE DOCUMENT NUMBER;MM/TR02/2009


GENERAL ACCESSORIES
DESCRIPTION M&M SPECIFICATION REQUIREMENT VENDOR SPECS
EQUIPMENTS MM/TR02 RATING AND CONNECTION PLATE
QUANTITY ONE CONSERVATOR
SERVICE OUTDOOR CONSERVATOR FOR OLTC Conservator for OLTC
PARALLEL OPERATION NO FIRST FILL OF COOLANT +10%SPARES
RATED KVA 1250 FILLING HOLE
FREQUENCY 50Hz (PLUS OR MINUS 3%) FILTER PRESS CONNECTION
PHASE 3 DRAIN VALVE AND PLUG
VOLTAGE RATIO 11/0.433KV LIFTING HOOKS
CONNECTION CORE LIFTING EYES
PRIMARY HT CABLE JACKING PADS
SECONDARY BUS DUCT SKID BASE
VECTOR GROUP Dyn11 BIDIRECTIONAL ROLLER
MATERIAL OF WINDING COPPER WHEELS
CLASS OF INSULATION CLASS A HAND HOLE
TYPE OF COOLING ONAN INSPECTION COVER ON TANK
EXTERNAL NEUTRAL BUSHING RADIATOR FLANGE AND ISOLATOR VALVE
PRIMARY NA RADIATOR
SECONDARY REQUIRED THERMO BRACKETS
TERTIARY NA
RATING OF NEUTRAL REF CT SILICA GEL BREAKER
IMPEDANCE VALUE 5.00% COOLANT LEVEL INDICATOR
TOLERANCE IN IMPEDANCE VALUE No(-Ve) TOL MAGNETIC LEVEL GAUGE WITH CONTACT
COPPER LOSSES * BUCHHOLZ RELAY WITH TWO CONTACT
IRON LOSSES * BUCHHOLZ RELAY BYPASS FACILITIES
TOLERANCE IN IMPEDANCE VALUE NIL PRESSURE RELIEF VALVE
SYSTEM FAULT LEVEL PRESSURE RELIEF DIAPHRAGM
PRIMARY PRESSURE SWITCH
SECONDARY PRESSURE/VACUUM GAUGE
TAPPING ON PRIMARY WINDING STEPS NA INDICATING THERMOMETER
ON LOAD TAP CHANGER PLUS OR MINUS 10% OIL TEMP INDICATOR WITH TWO CONTACT
LOCAL AND REMOTE PANEL FOR OLTC REQUIRED WINDING TEMP INDICATOR WITH TWO CONTACT
OFF LOAD TAP CHANGER WITH EXTERNAL HANDLE REQUIRED MOTORS FOR COOLING FANS
CONNECTION TO PRIMARY CONTROL PANEL FOR STARTERS OF FANS
CABLE SIZE AND QUANTITY 1x 3cx300SQMM XLPE CABLE MARSHALLING BOX
CONNECTION TO SECONDARY PRIMARY DISCONNECT CHAMBER
BUS DUCT AL BUS DUCT SECONDARY DISCONNECT CHAMBER
CABLE SIZE AND QUANTITY NA O/H CONDUCTOR CONNECTORS
ENTRY TOP SPARK HORN ON BUSHING
DIS.BET GLAND PLATE&TERMINAL IN CABLE BOX EARTHING TERMINAL
PRIMARY 700MM
SECONDARY NA
PAINTING TYPE AND SHADE EPOXY SHADE 631
AIR CLEARANCE BETWEEN HV AND LV TERMINAL
LIMITING DIMENSION IN TRANSFORMER DEPTH TO BE WITH IN 2600MM
LV MB

ORIENTATION OF PRIMARY AND SECONDARY


HV
DIM,WT AND OLTC DATA BY VENDOR
TRANSFORMER
A)HEIGHT *
B)BREADTH *
C)WIDTH *
D)WEIGHT WITH OIL *
WEIGHT OF OIL *
QTY OF OIL (LTRS) *
DESIGN DATA FROM VENDOR *
MANUFACTURER *
FULL LOAD CURRENT PRIMARY;* SECONDARY;*
FULL LOAD CURRENT SECONDARY *
NO LOAD CURRENT PRIMARY *
NO LOAD CURRENT SECONDARY BY RESISTANCE *
%RESISTANCE *
%IMPEDANCE *
%REACTANCE *
COPPER LOSS@75DEG *
IRON LOSS @75DEG *
TOLERANCE IN LOSSES *
TOLERANCE IN IMPEDANCE VALUE *
%REGULATION AT PF=1&PF=0.8 *
%EFF AT PF=1@100%,75%,50% LOAD *
MAX EFF AND LOAD WHICH OCCURS *
PERMISSIBLE OVERLOAD AND DURATION *
NOISE LEVEL AT ONE METER DISTANCE *
AIR CLEARANCE BETWEEN HV AND LV TERMINALS *
BUSHING DISTANCE AND CREEPAGE DISTANCE *
* -VENDOR AND MANUFACTURER TO PROVIDE THE DATA