No Credit Points
1
a 1
b 1
2
3
Required credits
1% 1
3%
2
5% 3
7% 4
10% 5
13% 6
16% 7
20% 8
4
Percentage reduction credits
4% 1
8% 2
12% 3
16% 4
20% 5
24% 6
28% 7
32% 8
36% 9
40% 10
44% 11
48% 12
52% 13
56% 14
60% 15
a 1 to 15
Demonstrate that a percentage of
total energy consumption will be
supplied by onsite renewable
energy
Demonstrate that a percentage of
total energy consumption will be
supplied by onsite renewable
energy
a
b 1
1 to 8
Pear Rating Sytem
1
Remarks
Mixed mode operation (not
available to retail use type )
c
Requirements
Co
2
Sensor at all return points
Ventilation exceeds minimum
requirements by 15%
Renewable Energy (Total credits - 9 )
Thermal Comfort and controls (Total credits - 1 )
Ventilation Quality (Total Credits - 3)
Required percentage Reduction
Improved interior water use reduction (Total credits - 15)
Achieve further reduction in the
proposed building potable water
consumption compared to the
baseline building
Required percentage by renewable energy
1
Compliant thermal zoning
strategy and controls
a
SI.No Credit Points
5
a 1
b 1
c 1
d 1
5
CO Maximum
concentration per 15
minutes
110mg/m
3
NO
2
maximum
Concentration per 1
hour
200 g/m
3
Particulate matter PM
10 per 24 hours
50 g/m
3
Car Park Quality Management (Total credits - 1 )
a
Demostrate that the weighted
average of all refrigerants shall
have a GWP of 10 or less
Demostrate that a permenant
refrigerant leak detection system
shall be installed
Demonstrate that 100% of
gaseous fire system shall have a
GWP of 1 or less
Requirements Remarks
Global Warming impacts of refrigerants and fire suppression systems (Total credits -4)
Demonstrate that an automatic
refrigerant pump down system
shall be installed
Total credit that can be achieved with mechanical
system
33
If the project does not contain any enclosed car parks(75% enclosure), the credit is automatically awarded
Ensure car park ventilation deign
meet the requirements
1