INPUT DATA
Unit Load 1 & 3 of the Station = 500 MW
COC = 3
Mains Frequency = 50 CPS
Inlet Cooling Water Temperature = 44.00 C
Inlet Cooling Water Temperature(Rated) = 42.00 C
Outlet Cooling Water Temperature = 37.60 C
Outlet Cooling Water Temperature(Rated) 33.00 C
Air Wet Bulb Temperature near Cell = 29.30 C
Air Wet Bulb Temperature near Cell(Rated) 27.50 C
Air Dry Bulb Temperature near Cell = 40.80 C
Number of CT Cells on line with water flow = 45
Total = 48
Total Measured Cooling Water Flow = 70426.76 m/hr
Measured CT Fan Flow = 989544.00 m/hr
Analysis
CT water Flow/Cel = 1565 m3/hr
1565040 kg/hr
Rated 2360 m3/hr
2360000 kg/hr
CT Fan air Flow, = 989544.00 m3/hr (Avg.)
CT Fan air Flow(Rated )= = 1252763.82 m3/hr
1.08 kg/m3= 1352984.92 kg/hr
CT Fan air Flow kg/hr (Avg.) @ Density of 1.08 kg/m3= 1068707.52 kg/hr
L/G Ratio of C.T. kg/kg = 1.46 kg/kg
Rated 1.74 kg/kg
CT Range = 44 - 37.6= 6.40
o
C
CT Range(Rated )= 42 - 33= 9.00
o
C
CT Approach = 37.6 - 29.3= 8.30
o
C
CT Approach(Rated )= = 33 - 27.5= 5.50
o
C
% CT Effectiveness = 43.54%
100 x
Approach Range
Range