INDEX SHEET

200 / 300 SERIES PANELS


CI-DS-01-200/300 C & I DISCLAIMER
CI-PJ-01-200 200 EXPANDED PANEL JOINT
CI-PJ-02-200 200 ENGAGED PANEL JOINT
CI-PJ-03-300 300 EXPANDED PANEL JOINT
CI-PJ-04-300 300 ENGAGED PANEL JOINT
CI-PJ-05-200/300 INTERMEDIATE SUPPORT
CI-BS-01-200/300 BASE DETAIL - FLUSH
CI-BS-02-200/300 BASE DETAIL - NOTCHED CONCRETE
CI-BS-03-200/300 BASE DETAIL - OVERHANG W/ SUPPORT
CI-BS-04-200/300 BASE DETAIL - OVERHANG W/ ANGLE
CI-OC-01-200/300 OUTSIDE CORNER WITH PROFILED TRIM
CI-OC-02-200/300 OUTSIDE CORNER WITH FLAT TRIM
CI-OC-03-200/300 OUTSIDE CORNER WITH MITER CUT
CI-IC-01-200/300 INSIDE CORNER WITH PROFILED TRIM
CI-IC-02-200/300 INSIDE CORNER WITH FLAT TRIM
CI-FO-01-200/300 F.O. TWO PIECE HEAD
CI-FO-02-200/300 F.O. HEAD WITH DRIP EDGE
CI-FO-03-200/300 F.O. TWO PIECE JAMB
CI-FO-04-200/300 F.O. ONE PIECE JAMB
CI-FO-05-200/300 F.O. ONE PIECE SILL
CI-FO-06-200/300 F.O. INTERIOR PARTITION
CI-FO-07-200/300 O.H. DOOR TWO PIECE HEAD
CI-FO-08-200/300 O.H. DOOR HEAD WITH DRIP EDGE
CI-FO-09-200/300 O.H. DOOR TWO PIECE JAMB
CI-SJ-01-200/300 STACK JOINT
CI-PR-01-200/300 PARAPET WITH FLUSH TRIM
CI-PR-02-200/300 PARAPET WITH PROFILED TRIM
CI-TL-01-200/300 TRIM END LAP
CI-TL-02-200/300 TRIM END LAP WITH HEM
CI-TL-03-200/300 TRIM END LAP WITH LAP STRIP
CI-TL-04-200/300 TRIM LAP AT F.O.
COMMERCIAL/INDUSTRIAL
DISCLAIMER
200 / 300 SERIES PANELS
DISCLAIMER:
THESE DETAILS ARE PROVIDED AS A GUIDELINE FOR PROPER PANEL AND ASSOCIATED
COMPONENT INSTALLATION, AND ARE BASED ON INDUSTRY ACCEPTED PRACTICES.
LOCATION OF VAPOR BARRIERS AND ASSOCIATED SEALANTS IN THESE DETAILS ARE BASED
ON TYPICAL DESIGN PRACTICES FOR MOST U.S. CLIMACTIC ZONES. (THE PRIMARY VAPOR
BARRIER IS PLACED ON THE "WARM" SIDE IN WINTER).
PROJECTS LOCATED IN AREAS SUBJECT TO EXTREME COLD AND/OR HIGH SNOW LOADS MAY
REQUIRE MODIFICATIONS TO THESE DETAILS - CONTACT KINGSPAN TECHNICAL SERVICES
FOR SPECIFIC PROJECT RECOMMENDATIONS.
EXTERIOR FACE
INTERIOR FACE
2"-6"
WALL PANEL INSTALLATION DIRECTION
14 GA. GALVANIZED HIDDEN CLIP
(1 PER PANEL, PER GIRT)
1
4
" - 14 HEX HEAD
FASTENERS
CONTINUOUS
BUTYL SEALANT
HORIZONTAL SUPPORT
BUTYL SEALANT
(OPTIONAL)
MINOR RIB
INVERTED RIB
42" COVERAGE (1,067mm)
MALE LEG FEMALE POCKET
MALE LEG
FEMALE POCKET
NOTE: FILL FEMALE POCKET(S) 3/4 FULL WITH SEALANT TO PROVIDE PROPER AIR/WATER SEAL
200 SERIES PANEL
200 EXPANDED
PANEL JOINT
200 SERIES PANELS
WALL PANEL INSTALLATION DIRECTION
14 GA. GALVANIZED HIDDEN CLIP
(1 PER PANEL, PER GIRT)
1
4
" - 14 HEX HEAD
FASTENERS
CONTINUOUS BUTYL SEALANT
HORIZONTAL SUPPORT
BUTYL SEALANT
(OPTIONAL)
200 ENGAGED
PANEL JOINT
200 SERIES PANELS
300 SERIES PANEL
EXTERIOR FACE
INTERIOR FACE
2"-6"
42" COVERAGE (1,067mm)
MINOR RIB
MINOR RIB
42" COVERAGE (1,067mm)
300 A SERIES PANEL
MINOR RIB
FLAT
42" COVERAGE (1,067mm)
2"-6"
2"-6" 300 R SERIES PANEL
MINOR RIB
STRIATION
WALL PANEL INSTALLATION DIRECTION
14 GA. GALVANIZED HIDDEN CLIP
(1 PER PANEL, PER GIRT)
1
4
" - 14 HEX HEAD
FASTENERS
CONTINUOUS
BUTYL SEALANT
HORIZONTAL SUPPORT
BUTYL SEALANT
(OPTIONAL)
42" COVERAGE (1,067mm)
300 GS SERIES PANEL
MINOR RIB
FLAT
2"-6"
MALE LEG FEMALE POCKET
MALE LEG
FEMALE POCKET
NOTE: FILL FEMALE POCKET(S) 3/4 FULL WITH SEALANT TO PROVIDE PROPER AIR/WATER SEAL
300 EXPANDED
PANEL JOINT
300 SERIES PANELS
FEMALE JOINT MALE JOINT
WALL PANEL INSTALLATION DIRECTION
14 GA. GALVANIZED HIDDEN CLIP
(1 PER PANEL, PER GIRT)
1
4
" - 14 HEX HEAD
FASTENERS
CONTINUOUS BUTYL SEALANT
HORIZONTAL SUPPORT
BUTYL SEALANT
(OPTIONAL)
300 ENGAGED
PANEL JOINT
300 SERIES PANELS
1
4
" - 14 HEX HEAD FASTENERS
14 GA. GALVANIZED HIDDEN CLIP
(1 PER PANEL, PER GIRT)
1
4
5

3"
.75 .75
0.28"
.
7
2
14 GA. GALVANIZED HIDDEN CLIP
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
INTERMEDIATE
SUPPORT
200 / 300 SERIES PANELS
14 GA. GALVANIZED HIDDEN CLIP
(1 PER PANEL, PER GIRT)
1
4
" - 14 HEX HEAD FASTENERS
BASE TRIM
MIN 16 GA. GALVANIZED
BASE ANGLE
FASTENER TO CONCRETE
(NOT BY KINGSPAN)
POP RIVETS
BASE FLASHING
CONTINUOUS BUTYL
SEALANT BELOW BASE
FLASHING
CONTINUOUS BUTYL SEALANT
SEALANT MARRIAGE BEAD TO
VERTICAL PANEL JOINT
NOTE: SEE DETAIL CI-TL-01-200/300 AND CI-TL-02-200/300 FOR TYPICAL
TRIM LAP INSTRUCTIONS
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
BASE DETAIL - FLUSH
200 / 300 SERIES PANELS
14 GA. GALVANIZED HIDDEN CLIP
(1 PER PANEL, PER GIRT)
1
4
" - 14 HEX HEAD FASTENERS
FASTENER TO CONCRETE
(NOT BY KINGSPAN)
CONTINUOUS BUTYL SEALANT
CONTINUOUS BUTYL SEALANT W/
MARRIAGE BEAD TO VERTICAL
PANEL JOINT
BASE TRIM
POP RIVETS
BASE FLASHING
CONTINUOUS BUTYL
SEALANT BELOW BASE
FLASHING
1
1
2
"
(
T
Y
P
.
)
MIN. 16 GA. GALVANIZED
BASE ANGLE
NOTE: SEE DETAIL CI-TL-01-200/300 AND CI-TL-02-200/300 FOR TYPICAL
TRIM LAP INSTRUCTIONS
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
BASE DETAIL - NOTCHED
CONCRETE
200 / 300 SERIES PANELS
14 GA. GALVANIZED HIDDEN CLIP
(1 PER PANEL, PER GIRT)
1
4
" - 14 HEX HEAD FASTENERS
FASTENER TO CONCRETE
(NOT BY KINGSPAN)
CONTINUOUS BUTYL SEALANT
BASE TRIM
POP RIVETS
1
1
2
"
(
T
Y
P
.
)
CONTINUOUS BUTYL SEALANT W/
MARRIAGE BEAD TO VERTICAL
PANEL JOINT
MIN. 16 GA. GALVANIZED
BASE ANGLE
NOTE: SEE DETAIL CI-TL-01-200/300 AND CI-TL-02-200/300 FOR TYPICAL
TRIM LAP INSTRUCTIONS
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
BASE DETAIL -
OVERHANG W/
SUPPORT
200 / 300 SERIES PANELS
14 GA. GALVANIZED HIDDEN CLIP
(1 PER PANEL, PER GIRT)
1
4
" - 14 HEX HEAD FASTENERS
BASE TRIM
FASTENER TO CONCRETE
(NOT BY KINGSPAN)
POP RIVETS
BUTYL SEALANT
1
1
2
"
(
T
Y
P
.
)
CONTINUOUS BUTYL SEALANT W/
MARRIAGE BEAD TO VERTICAL
PANEL JOINT
MIN. 16 GA. GALVANIZED
BASE ANGLE
NOTE: SEE DETAIL CI-TL-01-200/300 AND CI-TL-02-200/300 FOR TYPICAL
TRIM LAP INSTRUCTIONS
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
BASE DETAIL -
OVERHANG W/ ANGLE
200 / 300 SERIES PANELS
OUTSIDE CORNER TRIM
POP RIVETS
3
4
" PHIL. PAN HEAD
INSIDE CORNER TRIM
CONTINUOUS
BUTYL SEALANT
W
I
L
L

V
A
R
Y

W
I
T
H
F
I
E
L
D

C
O
N
D
I
T
I
O
N
WILL VARY WITH
FIELD CONDITION
FIELD CUT
HORIZONTAL SUPPORT
F.I.P. INSULATION
AS REQUIRED
(BY OTHERS)
1
4
" - 14 THROUGH FASTENERS
W/ 1
1
8
" BONDED WASHER
(AS REQUIRED FOR WIND LOAD)
ATTACHMENT CLIP
(BY OTHERS)
CONTINUOUS
BUTYL SEALANT
OUTSIDE CORNER
WITH PROFILED TRIM
200 / 300 SERIES PANELS
POP RIVETS
1
4
" - 14 "LOW PROFILE"
THROUGH FASTENER
WITH 1
1
8
" BONDED WASHER
(AS REQUIRED FOR WIND LOAD)
INSIDE CORNER TRIM
W
I
L
L

V
A
R
Y

W
I
T
H
F
I
E
L
D

C
O
N
D
I
T
I
O
N
WILL VARY WITH
FIELD CONDITION
FIELD CUT
OUTSIDE CORNER TRIM
F.I.P. INSULATION
AS REQUIRED
(BY OTHERS)
3
4
" PHIL. PAN HEAD
ATTACHMENT CLIP
(BY OTHERS)
CONTINUOUS
BUTYL SEALANT
HORIZONTAL SUPPORT
CONTINUOUS
BUTYL SEALANT
OUTSIDE CORNER
WITH FLAT TRIM
200 / 300 SERIES PANELS
OUTSIDE CORNER TRIM
POP RIVETS
F.I.P. INSULATION
AS REQUIRED
(BY OTHERS)
EXPANSION FASTENER
INSIDE CORNER TRIM
W
I
L
L

V
A
R
Y

W
I
T
H
F
I
E
L
D

C
O
N
D
I
T
I
O
N
WILL VARY WITH
FIELD CONDITION
FIELD CUT
NOTE: VERIFY WIND LOADS WITH KINGSPAN PRIOR TO USING EXPANSION FASTENERS
FOR PANEL ATTACHMENT
3
4
" PHIL. PAN HEAD
ATTACHMENT CLIP
(BY OTHERS)
CONTINUOUS
BUTYL SEALANT
HORIZONTAL SUPPORT
CONTINUOUS
BUTYL SEALANT
MIN. 4"
OUTSIDE CORNER
MITER CUT
200 / 300 SERIES PANELS
3
4
" PHIL. PAN HEAD
OUTSIDE CORNER TRIM
CONTINUOUS
BUTYL SEALANT
HORIZONTAL SUPPORT
INSIDE CORNER TRIM
POP RIVETS
WILL VARY WITH
FIELD CONDITION
W
I
L
L

V
A
R
Y

W
I
T
H
F
I
E
L
D

C
O
N
D
I
T
I
O
N
FIELD CUT
F.I.P. INSULATION
AS REQUIRED
(BY OTHERS)
1
4
" - 14 THROUGH FASTENERS
W/ 1
1
8
" BONDED WASHER
(AS REQUIRED FOR WIND LOAD)
BUTYL SEALANT APPLIED
AT FASTENER LOCATIONS
CONTINUOUS
BUTYL SEALANT
INSIDE CORNER
WITH PROFILED TRIM
200 / 300 SERIES PANELS
3
4
" PHIL. PAN HEAD
INSIDE CORNER TRIM
POP RIVETS
WILL VARY WITH
FIELD CONDITION
W
I
L
L

V
A
R
Y

W
I
T
H
F
I
E
L
D

C
O
N
D
I
T
I
O
N
FIELD CUT
1
4
" - 14 "LOW PROFILE"
THROUGH FASTENER WITH
1
1
8
" BONDED WASHER (AS
REQUIRED FOR WIND LOAD)
BUTYL SEALANT APPLIED
AT FASTENER LOCATIONS
OUTSIDE CORNER TRIM
CONTINUOUS
BUTYL SEALANT
HORIZONTAL SUPPORT
F.I.P. INSULATION
AS REQUIRED
(BY OTHERS)
CONTINUOUS
BUTYL SEALANT
INSIDE CORNER
WITH FLAT TRIM
200 / 300 SERIES PANELS
EXTERIOR CAP TRIM
POP RIVETS
1
4
" - 14 "LOW PROFILE"
THROUGH FASTENER
FRAMED OPENING
(NOT BY KINGSPAN)
INTERIOR CAP TRIM
DOOR/WINDOW FRAME
(NOT BY KINGSPAN)
FIELD DRILL
3
8
" WEEP HOLES
TO ALIGN WITH PANEL JOINTS
EXPOSED SEALANT
(NOT BY KINGSPAN)
CONTINUOUS BUTYL SEALANT W/
MARRIAGE BEAD TO VERTICAL
PANEL JOINT
CONTINUOUS
BUTYL SEALANT
NOTE: SEE DETAIL CI-TL-01-200/300, CI-TL-02-200/300, AND CI-TL-04-200/300
FOR TYPICAL TRIM LAP INSTRUCTIONS
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
FRAMED OPENING
TWO-PIECE HEAD
200 / 300 SERIES PANELS
EXTERIOR CAP TRIM
POP RIVETS
1
4
" - 14 "LOW PROFILE"
THROUGH FASTENER
EXPOSED SEALANT
(NOT BY KINGSPAN)
DRIP FLASHING
FRAMED OPENING
(NOT BY KINGSPAN)
DOOR/WINDOW FRAME
(NOT BY KINGSPAN)
CONTINUOUS BUTYL SEALANT W/
MARRIAGE BEAD TO VERTICAL
PANEL JOINT
CONTINUOUS
BUTYL SEALANT
NOTE: SEE DETAIL CI-TL-01-200/300, CI-TL-02-200/300, AND CI-TL-04-200/300
FOR TYPICAL TRIM LAP INSTRUCTIONS
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
FRAMED OPENING
HEAD W/ "DRIP EDGE"
200 / 300 SERIES PANELS
INTERIOR CAP TRIM
POP RIVETS
1
4
" - 14 "LOW PROFILE"
THROUGH FASTENER
WASHER
CONTINUOUS BUTYL SEALANT
FRAMED OPENING
(NOT BY KINGSPAN)
EXTERIOR CAP TRIM
DOOR/WINDOW FRAME
(NOT BY KINGSPAN)
EXPOSED SEALANT
(NOT BY KINGSPAN)
POP RIVETS
CONTINUOUS BUTYL SEALANT
NOTE: SEE DETAIL CI-TL-01-200/300, CI-TL-02-200/300, AND CI-TL-04-200/300
FOR TYPICAL TRIM LAP INSTRUCTIONS
FRAMED OPENING
TWO PIECE JAMB
200 / 300 SERIES PANELS
FRAMED OPENING
(NOT BY KINGSPAN)
CONTINUOUS BUTYL SEALANT
DOOR/WINDOW FRAME
(NOT BY KINGSPAN)
EXPOSED SEALANT
(NOT BY KINGSPAN)
POP RIVETS
CONTINUOUS BUTYL SEALANT
1
4
" - 14 "LOW PROFILE"
THROUGH FASTENER
WASHER
CONTINUOUS BUTYL SEALANT
CAP TRIM
1
4
" - 14 "LOW PROFILE"
FASTENER (AS REQUIRED)
NOTE: SEE DETAIL CI-TL-01-200/300, CI-TL-02-200/300, AND CI-TL-04-200/300
FOR TYPICAL TRIM LAP INSTRUCTIONS
FRAMED OPENING
ONE PIECE JAMB
200 / 300 SERIES PANELS
EXTERIOR CAP TRIM
POP RIVETS
1
4
" - 14 "LOW PROFILE"
THROUGH FASTENER
FRAMED OPENING
(NOT BY KINGSPAN)
DOOR/WINDOW FRAME
(NOT BY KINGSPAN)
EXPOSED SEALANT
(NOT BY KINGSPAN)
CONTINUOUS BUTYL SEALANT W/
MARRIAGE BEAD TO VERTICAL
PANEL JOINT
1
4
" - 14 "LOW PROFILE"
FASTENER (AS REQUIRED)
CONTINUOUS BUTYL
SEALANT
NOTE: SEE DETAIL CI-TL-01-200/300, CI-TL-02-200/300, AND CI-TL-04-200/300
FOR TYPICAL TRIM LAP INSTRUCTIONS
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
FRAMED OPENING
ONE PIECE SILL
200 / 300 SERIES PANELS
CAP TRIM
PHIL. PAN HEAD FASTENERS
CONTINUOUS BUTYL SEALANT
CAP TRIM
PHIL. PAN HEAD FASTENERS
CONTINUOUS BUTYL SEALANT
CONTRACTOR MAY REMOVE A PORTION
OF THE FOAM CORE AND INSERT TREATED
LUMBER TO REINFORCE LARGE OPENINGS
CAP TRIM
CONTRACTOR MAY REMOVE A PORTION
OF THE FOAM CORE AND INSERT TREATED
LUMBER TO REINFORCE LARGE OPENINGS
DOOR CASING
(NOT BY KINGSPAN)
THROUGH BOLT AS
REQUIRED FOR ATTACHMENT
OF DOOR CASING
(NOT BY KINGSPAN)
CONTINUOUS
BUTYL SEALANT
FRAMED OPENING
PARTITION
200 / 300 SERIES PANELS
EXTERIOR CAP TRIM
POP RIVETS
1
4
" - 14 "LOW PROFILE"
THROUGH FASTENER
FRAMED OPENING
(NOT BY KINGSPAN)
INTERIOR CAP TRIM
FIELD DRILL
3
8
" WEEP HOLES
TO ALIGN WITH PANEL JOINTS
CONTINUOUS BUTYL SEALANT W/
MARRIAGE BEAD TO VERTICAL
PANEL JOINT
CONTINUOUS
BUTYL SEALANT
HEADER TRIM
(OPTIONAL)
FASTENER
(NOT BY KINGSPAN)
EXPOSED SEALANT
(NOT BY KINGSPAN)
NOTE: SEE DETAIL CI-TL-01-200/300, CI-TL-02-200/300, AND CI-TL-04-200/300
FOR TYPICAL TRIM LAP INSTRUCTIONS
1
2
3
TRIM INSTALLATION SEQUENCE:
1 HEADER TRIM (OPTIONAL) & ALL APPLICABLE SEALANTS
2 INTERIOR CAP TRIM & ALL APPLICABLE SEALANTS PRIOR TO
INSTALLING THE PANEL AND THROUGH FASTENERS
3 EXTERIOR CAP TRIM
OVERHEAD DOOR
TWO PIECE HEADER
200 / 300 SERIES PANELS
EXTERIOR CAP TRIM
POP RIVETS
1
4
" - 14 "LOW PROFILE"
THROUGH FASTENER
DRIP FLASHING
FRAMED OPENING
(NOT BY KINGSPAN)
CONTINUOUS BUTYL SEALANT W/
MARRIAGE BEAD TO VERTICAL
PANEL JOINT
CONTINUOUS
BUTYL SEALANT
FASTENER
(NOT BY KINGSPAN)
NOTE: SEE DETAIL CI-TL-01-200/300, CI-TL-02-200/300, AND CI-TL-04-200/300
FOR TYPICAL TRIM LAP INSTRUCTIONS
HEADER TRIM
(OPTIONAL)
EXPOSED SEALANT
(NOT BY KINGSPAN)
TRIM INSTALLATION SEQUENCE:
1 HEADER TRIM (OPTIONAL) & ALL APPLICABLE SEALANTS
2 DRIP FLASHING & ALL APPLICABLE SEALANTS PRIOR TO
INSTALLING THE PANEL AND THROUGH FASTENERS
3 EXTERIOR CAP TRIM
1
2
3
OVERHEAD DOOR
HEAD W/ DRIP EDGE
200 / 300 SERIES PANELS
INTERIOR CAP TRIM
POP RIVETS
1
4
" - 14 "LOW PROFILE"
THROUGH FASTENER
CONTINUOUS BUTYL SEALANT
FRAMED OPENING
(NOT BY KINGSPAN)
EXTERIOR CAP TRIM
EXPOSED SEALANT
(NOT BY KINGSPAN)
POP RIVETS
CONTINUOUS BUTYL SEALANT
FASTENER
(NOT BY KINGSPAN)
JAMB TRIM
(OPTIONAL)
NOTE: SEE DETAIL CI-TL-01-200/300, CI-TL-02-200/300, AND CI-TL-04-200/300
FOR TYPICAL TRIM LAP INSTRUCTIONS
TRIM INSTALLATION SEQUENCE:
1 JAMB TRIM (OPTIONAL) & ALL APPLICABLE SEALANTS
2 INTERIOR CAP TRIM & ALL APPLICABLE SEALANTS PRIOR TO
INSTALLING THE PANEL AND THROUGH FASTENERS
3 EXTERIOR CAP TRIM
1
2
3
OVERHEAD DOOR
TWO-PIECE JAMB
200 / 300 SERIES PANELS
14 GA. GALVANIZED HIDDEN CLIP
(1 PER PANEL, PER GIRT)
1
4
" - 14 HEX HEAD FASTENERS
STACK TRIM
HORIZONTAL SUPPORT
CONTINUOUS 3" X 3" ANGLE
(GAUGE TO MATCH GIRT)
(NOT BY KINGSPAN)
POP RIVETS
STACK FLASHING
CONTINUOUS BUTYL
SEALANT BELOW BASE
FLASHING
CONTINUOUS BUTYL SEALANT W/
MARRIAGE BEAD TO VERTICAL
PANEL JOINT
CONTINUOUS BUTYL SEALANT W/
MARRIAGE BEAD TO VERTICAL
PANEL JOINT
FASTEN AS REQUIRED
(NOT BY KINGSPAN)
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
STACK JOINT
200 / 300 SERIES PANELS
CONTINUOUS CLEAT
WRAP MEMBRANE
(NOT BY KINGSPAN)
PARAPET BLOCKING
(NOT BY KINGSPAN)
MEMBRANE ROOF &
PARAPET BACKER
(NOT BY KINGSPAN)
FASTENER TO PARAPET
BACKER (NOT BY KINGSPAN)
PARAPET CAP
14 GA. GALVANIZED HIDDEN CLIP
(1 PER PANEL, PER GIRT)
1
4
" - 14 HEX HEAD FASTENERS
CONTINUOUS
BUTYL SEALANT
SEALANT MARRIAGE BEAD TO
VERTICAL PANEL JOINT
1
4
" - 14 "LOW PROFILE"
FASTENER
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
PARAPET
WITH FLUSH TRIM
200 / 300 SERIES PANELS
POP RIVET
WRAP MEMBRANE
(NOT BY KINGSPAN)
PARAPET BLOCKING
(NOT BY KINGSPAN)
PARAPET BACKER
(NOT BY KINGSPAN)
FASTENER TO PARAPET
BACKER (NOT BY KINGSPAN)
PARAPET CAP
14 GA. GALVANIZED HIDDEN CLIP
(1 PER PANEL, PER GIRT)
1
4
" - 14 HEX HEAD FASTENERS
SEALANT MARRIAGE BEAD TO
VERTICAL PANEL JOINT
CONTINUOUS
BUTYL SEALANT
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
PARAPET
WITH PROFILED TRIM
200 / 300 SERIES PANELS
M
I
N
.

3
"
T
R
I
M

L
A
P
M
I
N
.

3
"
T
R
I
M

L
A
P
(2) BEADS
BUTYL SEALANT
TRIM END LAP
200 / 300 SERIES PANELS
M
I
N
.

3
"
T
R
I
M

L
A
P
M
I
N
.

3
"
T
R
I
M

L
A
P
(2) BEADS
BUTYL SEALANT
FIELD NOTCH HEM(S)
AS REQUIRED
(NOT BY KINGSPAN)
TRIM LAP WITH HEM
200 / 300 SERIES PANELS
(2) BEADS
BUTYL SEALANT
N
O
M
.

1
4
"
G
A
P
8" LONG LAP STRIP
TRIM END LAP WITH
LAP STRIP
200 / 300 SERIES PANELS
I
N
T
E
R
I
O
R

C
A
P

T
R
I
M

A
T

H
E
A
D
E
X
T
E
R
I
O
R

C
A
P

T
R
I
M

A
T

H
E
A
D
E
X
T
E
R
I
O
R

C
A
P

T
R
I
M

A
T

J
A
M
B
FIELD NOTCH AND OVERLAP
TRIMS, POP RIVET AND SEAL AS
NECESSARY (NOT BY KINGSPAN)
FIELD MITER AND OVERLAP
TRIMS, POP RIVET AS
NECESSARY (NOT BY KINGSPAN)
FIELD CUT/NOTCH CAP
TRIM AT CORNERS TO
ALLOW FOR LAP
(NOT BY KINGSPAN)
E
X
T
E
R
I
O
R

C
A
P

T
R
I
M

A
T

S
I
L
L
FIELD MITER AND OVERLAP
TRIMS, POP RIVET AND SEAL AS
NECESSARY (NOT BY KINGSPAN)
FIELD CUT/NOTCH CAP
TRIM AT CORNERS TO
ALLOW FOR LAP
(NOT BY KINGSPAN)
EXPOSED SEALANT
(NOT BY KINGSPAN)
SEALANT END DAM
FIELD DRILL
3
8
" WEEP HOLES
(NOT BY KINGSPAN)
TRIM INSTALLATION SEQUENCE:
1 INTERIOR JAMB TRIM
2 INTERIOR HEAD TRIM WITH TABS DOWN
3 SILL TRIM WITH TABS UP
4 EXTERIOR JAMB TRIM
5 EXTERIOR HEAD TRIM
6 EXTERIOR SEALANTS AS REQUIRED
INTERIOR JAMB TRIM
1
INTERIOR HEAD TRIM
WITH TABS BENT DOWN
2
SILL TRIM WITH TABS
BENT UP
3
EXTERIOR HEAD TRIM W/
5
EXTERIOR JAMB TRIM
4
6
TRIM LAP AT
FRAMED OPENING
200 / 300 SERIES PANELS