Вы находитесь на странице: 1из 1

4

h
1
= h
4
= 267 kJ/kg
1 2
h
2
= 413 kJ/kg
3
h
3
= 448 kJ/kg
Saturated Liquid Line
Saturated Vapour Line
Subcooled by 10

K
(58 10 = 48
0
C)
Superheated with 10 K
(7 + 10 = 17
0
C)
Isentropic
compression,
S
2
= S
3
.
58
0
C
58 10 = 48
0
C
P
e
= 0.35
P
c
= 1.5
7 + 10 = 17
0
C
7
0
C
Compressor Power
= m
r
(h
3
h
2
)
= 2.3(448 413) kW
= 80.5 kW
Rate of Heat of Rejection
= m
r
(h
3
h
4
)
= 2.3(448 267) kW
= 416.3 kW
Refrigerating Capacity
= m
r
(h
2
h
1
)
= 2.3(413 267) kW
= 335.8 kW
Coefficient of Performance,
COP = m
r
(h
2
h
1
)/m
r
(h
3
h
2
)
= 2.3(413 267)/2.3(448 413)
= 335.8/80.5 = 4.17