Summary of NFPA

Inspection, Test & Maintenance Requirements


Table of Contents
System

Page

Clean Agent System

CO2

Fire Alarm

Fire Monitor

11

Fire Pump

12

Fire Service Mains

14

Low Expansion Foam

16

Foam Sprinkler

18

Hydrant

21

Pre-action Deluge

22

Sprinkler

25

Standpipe and Hose

28

Page 1 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
Clean Agent Systems
Semi-Annual:
Item
Agent quantity and pressure of refillable containers
shall be checked.
Factory charged, non-refillable containers shall
have the agent quantity checked.

Activity

Standard

Table

Paragraph

Inspect

NFPA 2001

7.1.3

Inspect

NFPA 2001

7.1.5

Annual:
Activity

Standard

Table

Paragraph

System shall be thoroughly Inspected.

Item

Inspect

NFPA 2001

7.1.1

Examine system hoses for damage.


Hazard enclosure inspection unless a documented
administrative control program exists that addresses
barrier integrity.
System alarm, detection and release controls

Inspect

NFPA 2001

7.3

Inspect

NFPA 2001

7.4, 7.5.3

Test

NFPA 72

Table 14.4.5

Activity

Standard

Table

Paragraph

Test

NFPA 2001

7.3.2.1, 7.3.2.2

Inspect

NFPA 2001

7.2.2

Test

NFPA 2001

7.2.1

Activity

Standard

Table

Paragraph

Inspect

NFPA 2001

7.1.3.1

Inspect

NFPA 2001

7.1.3.2

Inspect

NFPA 2001

7.5.3

Five Years:
Item
System hoses
Cylinders in Continuous Operation Without
Discharging
Cylinders shall not be recharged without retesting if
more than 5 years have elapsed since the date of
the last test and inspection.

Any time:
Item
Halocarbon Clean Agent Cylinders that show more
than 5% net loss in agent weight or loss in pressure
(adjusted for temperature) of more than 10% shall
be refilled or replaced.
Inert gas clean agent cylinders containing agent
under pressure (not liquefied) showing a loss in
pressure (adjusted for temperature) of more than
5% shall be refilled or replaced.
Any penetrations made in the enclosure protected
by a clean agent system shall be sealed
immediately.

Based on NFPA 2001, 2012 Edition


Notes:
1.
See also F.E. Moran Plant Services ITM Requirements for NFPA 72 Fire Alarm Systems on
separate sheet.
2.

Refer to manufacturers test and maintenance procedures provided to the owner for testing and
maintenance of the system. This document shall provide for periodic test, inspection and
maintenance of the system.

Page 2 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
CO2 Systems
Weekly:
Item
Low Pressure Systems Liquid Level Gauge

Activity

Standard

Table

Inspect

NFPA 12

Activity

Standard

Table

Inspect

NFPA 12

Activity

Standard

Table

Weigh

NFPA 12

Paragraph
4.8.3.6.1

Monthly:
Item
System Operational Condition

Paragraph
4.8.1

Semi-Annual:
Item
High Pressure CO2 Cylinders

Paragraph
4.8.3.5.1

Annual:
Item

Activity

Standard

Table

CO2 System Readiness and Operability


High pressure CO2 cylinders in place, secure, free
of damage or corrosion. Verify hydrostatic test
date.
Low pressure CO2 tank, check for signs of damage
or corrosion, verify amount of CO2 in tank.
All system isolation valves are in their normal open
positions.
Hazard size and scope is unchanged.

Test

NFPA 12

4.8.3.2, A.4.8.1

Paragraph

Inspect

NFPA 12

Inspect

NFPA 12

4.8.3.2

Inspect/Test

NFPA 12

A4.8.1

Inspect

NFPA 12

4.8.3.2 (2)

System Time Delays


System pressure release devices (dampers, door
closures, etc.) operate fully.
Selector valves operate and reset properly.

Test

NFPA 12

4.8.3.2 (3)

Test

NFPA 12

4.8.3.2, A.4.8.3

Test

NFPA 12

4.8.3.2, A.4.8.3

Equipment shutdowns operate correctly.


Manual release operates correctly and within
specifications.
System piping is secure, free of damage, properly
supported and connected to the CO2 supply.
Nozzles are free of damage, properly supported,
oriented and free of contamination.
Check system control unit and battery backup in
accordance with NFPA 72.
Audible/ Visible Alarms

Test

NFPA 12

4.8.3.2, A.4.8.3

Test

NFPA 12

4.8.3.2, A.4.8.3

Inspect

NFPA 12

4.8.3.2, A.4.8.3

Inspect

NFPA 12

4.8.3.2, A.4.8.3

Test

NFPA 72

Table 14.4.2.2

Warning signage properly installed and displayed.


Emergency manual control present, accessible,
labeled & Operable.
System Detectors

Test

NFPA 12

4.8.3.2 (4 & 5)

Inspect

NFPA 12

4.8.3.2 (6)

Inspect

NFPA 12

4.5.4.6

Test

NFPA 72

Table 14.4.2.2

Five Years:

Page 3 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
Item
System Hoses
High pressure CO2 cylinders shall not be
recharged without a hydrostatic test and remarking
if more than 5 years have elapsed from the date of
the last test.

Activity

Standard

Table

Test

NFPA 12

Paragraph
4.8.2.3

Test

NFPA 12

4.6.5.2

Activity

Standard

Table

Test

NFPA 12

Activity

Standard

Table

Inspect

NFPA 12

4.8.3.5.2

Inspect

NFPA 12

4.8.3.6.2

Inspect

NFPA 12

4.8.3.4

Test

NFPA 12

4.8.3.2.2

Twelve Years:
Item
High pressure CO2 cylinders in continuous service
shall be discharged, hydrostatically tested and
reinstalled.

Paragraph
4.6.5.2.2

Any time:
Item
High pressure CO2 cylinders that show more than
10% net loss in agent weight shall be refilled or
replaced.
Low pressure CO2 tank that shows more than 10%
net loss in agent shall be refilled unless amount of
agent meets minimum gas requirements.
Any penetrations made in the enclosure protected
by a total flooding CO2 system shall be sealed
immediately.
Discharge-test the system when maintenance/AHJ
indicates their advisability.

Paragraph

Based on NFPA 12, 2011 Edition


Notes:
1.
See also F.E. Moran Plant Services ITM Requirements for NFPA 72 Fire Alarm Systems on
separate sheet.
2.

Refer to manufacturers test and maintenance procedures provided to the owner for testing and
maintenance of the system. This document shall provide for periodic test, inspection and
maintenance of the system.

Page 4 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
Fire Alarm
Daily:
Item

Activity

Standard

Table

Paragraph

Power Supply public emergency alarm reporting


systems-wired system-voltage test

Test

NFPA 72

14.4.5

Table 14.4.2.2
No. 7d

Activity

Standard

Table

Paragraph

Inspect

NFPA 72

14.3.1

Inspect

NFPA 72

14.3.1

Test

NFPA 72

14.4.5

Activity

Standard

Table

Paragraph

Lead Acid Batteries

Inspect

NFPA 72

14.3.1

Primary (dry cell) Batteries

Inspect

NFPA 72

14.3.1

Test

NFPA 72

14.4.5

Table 14.4.2.2
No. 5
Table 14.4.2.2
No. 5
Table 14.4.2.2

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Inspect/Test

NFPA 72

14.4.5

Weekly:
Item
Control Equipment: fire alarm systems unmonitored
for alarm, supervisory and trouble signals (fuses,
interfaced equipment, lamps and LEDs and Primary
(main) power supply)
Fire Alarm Control Unit trouble signals
Engine-driven generator public emergency alarm
reporting systems

Monthly:
Item

Engine Driven Generator-Central Station Facilities


and Fire Alarm Systems
Batteries-Central Station Facilities-Lead Acid type30 Minute Discharge Test
Batteries-Central Station Facilities-Lead Acid typeLoad Voltage Test
Batteries-Central Station Facilities-Sealed Lead
Acid type- Charger Test
Batteries-Central Station Facilities-Sealed Lead
Acid type- 30 Minute Discharge Test
Batteries-Central Station Facilities-Sealed Lead
Acid type- Load Voltage Test
Batteries-Fire Alarm Systems-Primary (dry cell)
type- Age Test
Supervising Station Fire Alarm Systems-Receivers
(DACR, DARR, McCulloh, Two-way RF multiplex,
RASSR, RARSR, Private Microwave)
Single- and Multiple-station smoke alarms

Table 14.4.2.2
No. 5
Table 14.4.2.2
No. 5, 6b
Table 14.4.2.2
No. 5, 6d
Table 14.4.2.2
5
Table 14.4.2.2
No. 5, 6d
Table 14.4.2.2
No. 5, 6a
Table 14.4.2.2
No. 19
14.4.6

Quarterly:
Activity

Standard

Table

Paragraph

Radiant Energy Fire Detector

Item

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Supervisory Signal Devices

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Waterflow Devices

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Test

NFPA 72

14.4.5

Table 14.4.2.2
No. 1

Test

NFPA 72

14.4.5

Table 14.4.2.2
No. 5, 6c

Control Equipment not connected to a Supervising


Station-Functions, Fuses, Interfaced Equipment,
Lamps/LEDs, Primary (main) power supply,
Transponders
Batteries-Central Station Facilities-Nickel Cadmium
type- Charger Test

Quarterly (cont.):

Page 5 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
Batteries-Central Station Facilities-Sealed Lead
Acid type- Charger Test
Power Supply-Public Fire Alarm Reporting
Systems-Lead Acid type batteries-2 Hour Discharge
Test
Power Supply-Public Fire Alarm Reporting
Systems-Lead Acid type batteries-Load Voltage
Test
Power Supply-Public Fire Alarm Reporting
Systems-Nickel Cadmium type batteries-Load
Voltage Test
Power Supply-Public Fire Alarm Reporting
Systems-Sealed Lead Acid type batteries-Load
Voltage Test
Supervisory Signal Devices (Pressure Supervisory;
Water level; Water temperature, Room temperature
indicating devices and Other suppression system
supervisory initiating devices.)

Test

NFPA 72

14.4.5

Table 14.4.2.2
No. 5, 6d
Table 14.4.2.2
No. 5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Table 14.4.2.2
No. 5, 6b

Test

NFPA 72

14.4.5

Table 14.4.2.2
No. 5, 6c

Test

NFPA 72

14.4.5

Table 14.4.2.2
No. 5, 6b

Test

NFPA 72

14.4.5

Table 14.4.2.2
No. 14

Semi-Annual:
Activity

Standard

Table

Paragraph

Batteries-Nickel Cadmium

Item

Inspect

NFPA 72

14.3.1

Batteries-Sealed Lead Acid

Inspect

NFPA 72

14.3.1

Transient Suppressors

Inspect

NFPA 72

14.3.1

Table 14.4.2.2
No. 5
Table 14.4.2.2
No. 5
Table 14.4.2.2

Fire Alarm Control Unit Trouble Signals

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

In-building Emergency Voice/Alarm


Communications Equipment
Remote Annunciators

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Air Sampling Detectors

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Duct Smoke Detectors

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Electromechanical Releasing Devices

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Fire Extinguishing Systems(s) or Suppression


System(s) Switches
Manual Fire Alarm Boxes

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Heat Detectors

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Smoke Detectors (excludes 1 & 2 family dwellings)

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Guard Tour Equipment

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Fire Extinguisher Monitoring Device/Systems

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Carbon Monoxide Monitoring Device/Systems

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Interface Equipment

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Alarm Notification Appliances-Supervised

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Exit Marking Audible Notification Appliances

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Supervising Station Fire Alarm SystemsTransmitters (DACT, DART, McCulloh, RAT)


Special Procedures

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Supervising Station Fire Alarm Systems-Receivers

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Public Fire Alarm Reporting System Transmission


Equipment-Publicly accessible fire alarm box

Inspect

NFPA 72

14.3.1

Table 14.4.2.2
No. 8a

Semi-Annual (cont.):

Page 6 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
Public Fire Alarm Reporting System Transmission
Equipment-Master Box Manual operation

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Valve Supervisory Switches

Test

NFPA 72

14.4.5

Waterflow Devices

Test

NFPA 72

14.4.5

Public Emergency Alarm Reporting System


Transmission Equipment-publicly accessible fire
alarm box
Public Emergency Alarm Reporting System
Transmission Equipment Master Box Manual
operation
Mass notification system protected premise, nonsupervised systems installed prior to adoption of
this code (Control unit functions and no diagnostic
failures are indicated, Audible/visible functional test,
secondary power, Verify content of prerecorded
messages, verify activation of correct prerecorded
message based on a selected event, verify
activation of correct prerecorded message based on
a targeted area, verify control unit security
mechanism is functional.)

Test

NFPA 72

14.4.5

Table 14.4.2.2
No. 5, 6b
Table 14.4.2.2
No. 5, 6b
Table 14.4.2.2
No. 5, 6b
Table 14.4.2.2
No. 5, 6b
Table 14.4.2.2
No. 5, 6c
Table 14.4.2.2
No. 5, 6d
Table 14.4.2.2
No. 5, 6b
Table 14.4.2.2
No. 14
Table 14.4.2.2
No. 14
Table 14.4.2.2
No. 14
Table 14.4.2.2

Test

NFPA 72

14.4.5

Table 14.4.2.2

Test

NFPA 72

14.4.5

Table 14.4.2.2
No. 27

Mass Notification system, non-supervised systems


installed prior to adoption of NFPA 72 2010 Edition
(Control Equipment Fuses, Interfaces,
Lamps/LEDs, Primary (main) power supply,
Secondary power batteries (Lead Acid, NickelCadmium, Primary (dry cell), Sealed Lead Acid),
Initiating Devices, Notification Appliances
Batteries-Central Station Facilities-Lead Acid typeSpecific Gravity
Batteries-Fire Alarm Systems-Lead Acid type-30
Minute Discharge test
Batteries-Fire Alarm Systems-Lead Acid type-Load
Voltage Test
Batteries-Fire Alarm Systems-Lead Acid typeSpecific Gravity
Batteries-Fire Alarm Systems-Nickel Cadmium
type-Load Voltage Test
Batteries-Fire Alarm Systems-Sealed Lead Acid
type-Load Voltage Test
Power Supplies-Public Fire Alarm Reporting
Systems-Lead acid type batteries specific gravity
Radiant Energy Fire Detectors

Annual:
Item

Activity

Standard

Table

Paragraph

Control Equipment Fuses, Interfaced Equipment,


Lamps and LEDs, Primary (main) power supply
Fiber Optic Cable Connections

Inspect

NFPA 72

14.3.1

Inspect

NFPA 72

14.3.1

Table 14.4.2.2
No. 1, 7, 18, 19
Table 14.4.2.2

Public Fire Alarm Reporting System Transmission


Equipment Auxiliary Box
Public Fire Alarm Reporting System Transmission
Equipment Master Box Auxiliary operation

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Page 7 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
Annual (cont.):
Mass Notification system, supervised systems
Control Equipment Fuses, Interfaces, Lamps/LEDs,
Primary (main) power supply, Secondary power
batteries (Lead Acid, Nickel-Cadmium, Primary (dry
cell), Sealed Lead Acid), Initiating Devices,
Notification Appliances
Mass notification system Antenna

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Mass notification system Transceivers

Inspect

NFPA 72

14.3.1

Table 14.4.2.2

Test

NFPA 72

14.4.5

Table 14.4.2.2

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Table 14.4.2.2
No. 5, 6b
Table 14.4.2.2
No. 5
Table 14.4.2.2
No. 5, 6c
Table 14.4.2.2
No. 5, 6b
Table 14.4.2.2
No. 5, 6c
Table 14.4.2.2
No. 5
Table 14.4.2.2
No. 5, 6d
Table 14.4.2.2
No. 5
Table 14.4.2.2
No. 5, 6b
Table 14.4.2.2
No. 5, 6c

Test

NFPA 72

14.4.5

Table 14.4.2.2
No. 5

Test

NFPA 72

14.4.5

Table 14.4.2.2
No. 5, 6d

Control Equipment Bldg systems connected to a


Supervising Station- Functions, Fuses, Interfaced
Equipment, Lamps and LEDs, Primary (main)
power supply and Transponders
Batteries-Central Station Facilities-Lead Acid type
Charger test
Batteries-Central Station Facilities-Nickel Cadmium
type 30 minute Discharge test
Batteries-Central Station Facilities-Nickel Cadmium
type Load Voltage test
Batteries-Fire Alarm Systems-Lead Acid type
Charger test
Batteries-Fire Alarm Systems-Nickel Cadmium type
Charger test
Batteries-Fire Alarm Systems-Nickel Cadmium type
30 minute Discharge test
Batteries-Fire Alarm Systems-Sealed lead acid
type Charger test
Batteries-Fire Alarm Systems-Sealed lead acid
type 30 minute Discharge test
Power Supply-Public Emergency Alarm Reporting
Systems-Lead Acid type batteries Charger test
Power Supply-Public Emergency Alarm Reporting
Systems-Nickel Cadmium type batteries Charger
test
Power Supply-Public Emergency Alarm Reporting
Systems-Nickel Cadmium type batteries 2 hour
Discharge test
Power Supply-Public Emergency Alarm Reporting
Systems-Sealed Lead Acid type batteries Charger
test
Power Supply-Public Emergency Alarm Reporting
Systems-Sealed Lead Acid type batteries 2 hour
Discharge test
Fiber Optic Cable Power

Test

NFPA 72

14.4.5

Table 14.4.2.2
No. 5

Test

NFPA 72

14.4.5

Control Unit Trouble Signals

Test

NFPA 72

14.4.5

In-building Fire Emergency Voice/Alarm


Communications Equipment
Remote Annunciators

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Duct Detectors

Test

NFPA 72

14.4.5

Electromechanical Releasing Device

Test

NFPA 72

14.4.5

Fire Extinguishing system(s) or suppression


system(s) switches
Fire-gas and other detectors

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Table 14.4.2.2
No. 13b
Table 14.4.2.2
No. 10
Table 14.4.2.2
No. 20
Table 14.4.2.2
No. 11
Table 14.4.2.2
No. 14
Table 14.4.2.2
No. 14
Table 14.4.2.2
No. 14
Table 14.4.2.2
No. 14

Annual (cont.):

Page 8 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
Heat Detectors

Test

NFPA 72

14.4.5

Manual Fire Alarm Boxes

Test

NFPA 72

14.4.5

System Smoke Detectors Functional Test

Test

NFPA 72

14.4.5

Single & Multiple-station smoke alarms

Test

NFPA 72

14.4.5

Single & Multiple-station heat alarms

Test

NFPA 72

14.4.5

Other supervisory initiating devices (not included


during quarterly or semi-annual testing)
Guard Tour Equipment

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Fire Extinguisher Monitoring Device/Systems

Test

NFPA 72

14.4.5

14.4.5.5
Table 14.4.2.2
No. 14
Table 14.4.2.2
No. 14
Table 14.4.2.2
No. 14
14.4.4.6
Table 14.4.2.2
No. 14
Table 14.4.2.2
No. 14
Table 14.4.2.2
No. 14
Table 14.4.2.2
No. 24
Table 14.4.2.2
No. 21a
Table 14.4.2.2

Carbon Monoxide Monitoring Detector/Systems

Test

NFPA 72

14.4.5

Interface equipment and Fire Safety Functions

Test

NFPA 72

14.4.5

Special Hazard Equipment

Test

NFPA 72

14.4.5

Audible Devices, Audible Textual notification


appliances, Visible Devices
Audible Devices, Audible Textual notification
appliances, Visible Devices
Exit Marking Notification Appliances

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Supervising Station Fire Alarm SystemsTransmitters


Special Procedures

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Test

NFPA 72

14.4.5

Table 14.4.2.2
No. 27

Test

NFPA 72

14.4.5

Table 14.4.2.2
No. 27

Public Emergency Alarm Reporting Transmission


Equipment Auxiliary Box
Public Emergency Alarm Reporting Transmission
Equipment Master Box Auxiliary Operation
Mass notification system protected premise,
supervised (Control unit functions and no diagnostic
failures are indicated, Audible/visible functional test,
secondary power, Verify content of prerecorded
messages, verify activation of correct prerecorded
message based on a selected event, verify
activation of correct prerecorded message based on
a targeted area, verify control unit security
mechanism is functional.)
Mass notification system-wide area (UFC 4-021-01)
(Control unit functions and no diagnostic failures are
indicated, Control unit reset, Control unit security,
Audible/visible functional test, Software backup,
Secondary power test, Antenna, Transceivers,
Verify content of prerecorded messages, Verify
activation of correct prerecorded message based on
a selected event, Verify activation of correct
prerecorded message based on a targeted area,
Verify control unit security mechanism is functional.)

Other:

Page 9 of 28

Table 14.4.2.2
No. 22, 23
Table 14.4.2.2
No. 17
Table 14.4.2.2
No. 15
Table 14.4.2.2
No. 15
Table 14.4.2.2
No. 16
Table 14.4.2.2
No. 18
Table 14.4.2.2
No. 25
Table 14.4.2.2
No. 8b
Table 14.4.2.2

Summary of NFPA
Inspection, Test & Maintenance Requirements
Item

Activity

Standard

Table

Paragraph

Smoke Detector sensitivity testing in other than one


and two-family dwellings

Inspect

NFPA 72

14.3.1

14.4.5.3
Table 14.4.2.2

Based on NFPA 72, 2010 Edition

Page 10 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
Fire Monitor
Semi-Annual:
Item
Monitor Nozzles

Activity

Standard

Table

Inspect

NFPA 25

7.1.1.2

Activity

Standard

Paragraph
7.2.2.6

Annual:
Item
Monitor Nozzles - (range and operation)
Monitor Nozzles

Table

Paragraph

Test

NFPA 25

7.1.1.2

7.3.3

Maintenance

NFPA 25

7.1.1.2

7.4.3

Based on NFPA 25, 2011 Edition

Page 11 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
Fire Pump
Weekly:
Item

Activity

Standard

Table

Casing Relief Valves

Inspect

NFPA 25

13.1.1.2

13.5.7.1, 13.5.7.1.1

Control Valve - (Sealed)

Inspect

NFPA 25

13.1.1.2

13.3.2.1

Test

NFPA 25

8.1.1.2

8.3.1

Diesel Fire Pump Operation - no flow condition

Paragraph

Fire Pump System

Inspect

NFPA 25

8.1.1.2

8.2.2

Pressure Relief Valves

Inspect

NFPA 25

13.1.1.2

13.5.7.2, 13.5.7.2.1

Pump house, heating ventilating louvers

Inspect

NFPA 25

8.1.1.2

8.2.2 (1)

Paragraph

Monthly:
Activity

Standard

Table

Control Valve - (Locked)

Item

Inspect

NFPA 25

13.1.1.2

13.3.2.1.1

Control Valve - (Tamper Switches)

Inspect

NFPA 25

13.1.1.2

13.3.2.1.1

Test

NFPA 25

13.1.1.2

8.3.1

Electric Fire Pump Operation - no flow condition

Quarterly:
Item
Pressure Reducing Valves

Activity

Standard

Table

Inspect

NFPA 25

13.1.1.2

Activity

Standard

Table

Paragraph
13.5.1.1

Annual:
Item

Paragraph

Circulation Relief

Test

NFPA 25

13.1.1.2

13.5.7.1.2

Control Valves Position & Operation

Test

NFPA 25

13.1.1.2

13.3.3.1

Fire Pump alarm signals

Test

NFPA 25

8.1.1.2

8.3.3.5

Fire Pump Operation - flow test

Test

NFPA 25

8.1.1.2

8.3.3

Hydraulic

Maintenance

NFPA 25

8.1.1.2

8.5

Mechanical Transmission

Maintenance

NFPA 25

8.1.1.2

8.5

Motor

Maintenance

NFPA 25

8.1.1.2

8.5

Test

NFPA 25

13.1.1.2

13.5.7.2.2

Maintenance

NFPA 25

13.1.1.2

13.3.4

Activity

Standard

Table

Inspect

NFPA 25

13.1.1.2

Pressure Relief Valves


Control Valves

5 year:
Item
Check Valves - interior

Paragraph
13.4.2.1

Varies:
Activity

Standard

Table

Electrical System

Item

Maintenance

NFPA 25

8.1.1.2

8.5

Controller, Various Components

Maintenance

NFPA 25

8.1.1.2

8.5

Diesel Engine System, Various Components

Maintenance

NFPA 25

8.1.1.2

8.5

Page 12 of 28

Paragraph

Summary of NFPA
Inspection, Test & Maintenance Requirements
Based on NFPA 25, 2011 Edition
Note 1: The Inspection, Test and Maintenance requirements of fire pump systems can vary by type and
manufacturer. The manufacturers recommended maintenance should be utilized to develop
the maintenance program for fire pump systems. If the manufacturers maintenance
information is not available, an alternative maintenance program can be established.
Alternative maintenance requirements can be found in NFPA 25, Table 8.1.2.

Page 13 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
Fire Service Mains
After Use:
Item
Mainline Strainers

Activity

Standard

Table

Paragraph

Inspect

NFPA 25

7.1.1.2

7.2.2.3

Daily:
Item
Valve Enclosure (During Cold Weather, w/o alarms)

Activity

Standard

Table

Paragraph

Inspect

NFPA 25

13.1.1.2

13.4.3.1, 13.4.4.1.1

Activity

Standard

Table

Paragraph

Weekly:
Item
Control Valve - (Sealed)

Inspect

NFPA 25

13.1.1.2

13.3.2.1

Valve Enclosure(During Cold Weather, w/ alarms)

Inspect

NFPA 25

13.1.1.2

13.4.4.1.1.1

Monthly:
Activity

Standard

Table

Paragraph

Control Valve - (Locked)

Item

Inspect

NFPA 25

13.1.1.2

13.3.2.1.1

Control Valve - (Tamper Switches)

Inspect

NFPA 25

13.1.1.2

13.3.2.1.1

Quarterly:
Item
Hose Houses

Activity

Standard

Table

Paragraph

Inspect

NFPA 25

7.1.1.2

7.2.2.7

Activity

Standard

Table

Paragraph

Test

NFPA 25

13.1.1.2

13.3.3.5

Semi-Annual:
Item
Control Valve Supervisory

Annual:
Item
Control Valves
Control Valves Position and Operation

Activity

Standard

Table

Paragraph

Maintenance

NFPA 25

13.1.1.2

13.3.4

Test

NFPA 25

13.1.1.2

13.3.3.1

Maintenance

NFPA 25

7.1.1.2

7.2.2.7

Mainline Strainers

Inspect

NFPA 25

7.1.1.2

7.2.2.3

Mainline Strainers

Maintenance

NFPA 25

7.1.1.2

7.2.2.3

Piping (exposed)

Maintenance

NFPA 25

7.1.1.2

7.2.2.1

Activity

Standard

Table

Paragraph

Test

NFPA 25

7.1.1.2

7.3.1

Activity

Standard

Table

Paragraph

Inspect

NFPA 25

7.1.1.2

7.2.2.2

Hose Houses

5 Year:
Item
Piping (Exposed & Underground) (Flow Test)

Other:
Item
Piping (underground)

Based on NFPA 25, 2011 Edition

Page 14 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
See also F.E. Moran Plant Services ITM Requirements for Fire Hydrants on separate sheet.

Page 15 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
Low Expansion Foam Systems
Weekly:
Item
Control Valve - (Sealed)

Activity

Standard

Table

Inspect

NFPA 25

13.1.1.2

Paragraph
13.3.2.1

Monthly:
Activity

Standard

Table

Control Valve - (Locked)

Item

Inspect

NFPA 25

13.1.1.2

Paragraph
13.3.2.1.1

Control Valve - (Tamper Switches)


Discharge Device (Spray Nozzle) Location &
Position
Proportioning Systems All

Inspect

NFPA 25

13.1.1.2

13.3.2.1.1

Inspect

NFPA 25

11.1.1.2

11.2.5

Inspect

NFPA 25

11.1.1.2

11.2.9

Activity

Standard

Table

Foam Concentrate Strainer(s)

Inspect

NFPA 25

11.1.1.2

11.2.7.2

Foam Concentrate Strainer(s)

Maintenance

NFPA 25

11.1.1.2

Section 11.4

Inspect

NFPA 25

11.1.1.2

11.2.1

Test

NFPA 25

11.1.1.2

11.3.1.3

Activity

Standard

Table

Test

NFPA 25

13.1.1.2

Activity

Standard

Table

Quarterly:
Item

Waterflow Devices
Waterflow Devices (Water Motor Gongs, etc.)

Paragraph

Semi-Annual:
Item
Control Valve - (Tamper Switches)

Paragraph
13.3.3.5

Annual:
Item
Above Ground piping

Paragraph

Inspect

NFPA 11

11.2.3, 11.2.4

Complete foam-water system

Test

NFPA 11

11.3.3

Control Valve - Position and Operation

Test

NFPA 25

13.1.1.2

13.3.3.1

Foam Concentrate

Test

NFPA 11

11.2.10

Foam Water Solution

Test

NFPA 11

11.1.1.2

11.3.5

Inspect

NFPA 11

11.1.1.2

11.2.5

Test

NFPA 11

11.1.1.2

11.2.9

Strainers Mainline

Maintenance

NFPA 11

11.1.1.2

Ch. 10

Water Control Valves

Maintenance

NFPA 25

13.1.1.2

13.3.4

Activity

Standard

Table

Inspect

NFPA 11

Discharge Device Location & Position (Sprinklers)


Proportioning Systems - All

5 Year:
Item
Underground piping

Paragraph
11.3.3

Based on NFPA 11, 2005 and NFPA 25, 2011 Editions


While the requirements of NFPA 25 for the inspection, test and maintenance of foam deluge and foam sprinkler
systems do not specifically apply to Low Expansion Foam Systems, these systems often utilize the same types of
proportioning and control equipment. This being the case, serious consideration should be given to incorporating the
requirements of NFPA 25 into any maintenance program for Low Expansion Foam Systems.

Page 16 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
Foam Sprinkler
Weekly:
Item
Control Valve - (Sealed)

Activity

Standard

Table

Inspect

NFPA 25

13.1.1.2

Activity

Standard

Table

Paragraph
13.3.2.1

Monthly:
Item

Paragraph

Control Valve - (Locked)

Inspect

NFPA 25

13.1.1.2

13.3.2.1.1

Control Valve - (Tamper Switches)

Inspect

NFPA 25

13.1.1.2

13.3.2.1.1

Discharge Device Location (Spray nozzle)

Inspect

NFPA 25

11.1.1.2

11.2.5

Discharge Device Position (Spray nozzle)


Foam Concentrate Pump Operation
Proportioning Systems (all)

Inspect

NFPA 25

11.1.1.2

11.2.5

Maintenance

NFPA 25

11.1.1.2

11.4.6.1, 11.4.7.1

Inspect

NFPA 25

11.1.1.2

11.2.9

Quarterly:
Item

Activity

Standard

Table

Inspect

NFPA 25

11.1.1.2

Foam Concentrate Strainer(s)

Inspect

NFPA 25

11.1.1.2

11.2.7.2

Foam Concentrate Strainer(s)

Maintenance

NFPA 25

11.1.1.2

Section 11.4

Inspect

NFPA 25

11.1.1.2

11.2.1

Test

NFPA 25

11.1.1.2

11.3.1.3

Activity

Standard

Table

Test

NFPA 25

13.1.1.2

Activity

Standard

Table

Test

NFPA 25

11.1.1.2

Drainage in System Area

Waterflow Devices
Waterflow Devices (Water Motor Gongs, etc.)

Paragraph
11.2.8

Semi-Annual:
Item
Control Valve - (Tamper Switches)

Paragraph
13.3.3.5

Annual:
Item
Backflow Preventers

Paragraph
Chapter 13

Complete Foam-Water System

Test

NFPA 25

11.1.1.2

11.3.3

Control Valve - Position and Operation

Test

NFPA 25

13.1.1.2

13.3.3.1

Maintenance

NFPA 25

13.1.1.2

13.3.4
11.3.2.6

Control Valves
Discharge Device Location
Discharge Device Location (Sprinkler)
Discharge Device Obstruction
Discharge Device Position

Test

NFPA 25

11.1.1.2

Inspect

NFPA 25

11.1.1.2

11.2.5

Test

NFPA 25

11.1.1.2

11.3.2.6

Test

NFPA 25

11.1.1.2

11.3.2.6

Discharge Device Position (Sprinkler)

Inspect

NFPA 25

11.1.1.2

11.2.5

Fitting Corrosion

Inspect

NFPA 25

11.1.1.2

11.2.3

Fitting Damage

Inspect

NFPA 25

11.1.1.2

11.2.3

Maintenance

NFPA 25

11.1.1.2

11.2.10

Foam Concentrate Strainer(s)

Test

NFPA 25

11.1.1.2

11.2.7.2

Foam-water Solution

Test

NFPA 25

11.1.1.2

11.3.5

Foam Concentrate Sample

Annual (Cont.)

Page 17 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
Hangers/Supports
Manual Actuation Device(s)

Inspect

NFPA 25

11.1.1.2

11.2.4

Test

NFPA 25

11.1.1.2

11.3.4

Pipe Corrosion

Inspect

NFPA 25

11.1.1.2

11.2.3

Pipe Damage

Inspect

NFPA 25

11.1.1.2

11.2.3

Test

NFPA 25

11.1.1.2

Maintenance

NFPA 25

10.1.1.2

Inspect

NFPA 25

11.2.9
10.2.7, 10.2.1.4,
10.2.1.6
13.4.3.1.2

Proportioning Systems - (all)


Strainers
Valve Enclosure Low Temp Alarms
Water Supply
Water Supply Piping

Maintenance

NFPA 25

11.1.1.2

11.2.6.1

Test

NFPA 25

11.1.1.2

Chapter 10

5 Year:
Item

Activity

Standard

Table

Check Valves
In-Line Balanced Pressure Type Proportioning
Systems - Balancing Valve Diaphragm
In-Line Balanced Pressure Type Proportioning
Systems - Foam Concentrate Pumps
Pressure Vacuum Vents
Standard Balanced Pressure Type Proportioning
Systems - Balancing Valve Diaphragm
Standard Balanced Pressure Type Proportioning
Systems - Foam Concentrate Pump
Standard Pressure Type Proportioning Systems Ball Drip (Automatic Type) Drain Valves

Inspect

NFPA 25

13.1.1.2

13.4.2.1

Maintenance

NFPA 25

11.1.1.2

11.4.7.3

Maintenance

NFPA 25

11.1.1.2

11.4.7.2

Maintenance

NFPA 25

11.1.1.2

11.4.8

Maintenance

NFPA 25

11.1.1.2

11.4.6.3

Maintenance

NFPA 25

11.1.1.2

11.4.6.2

Maintenance

NFPA 25

11.1.1.2

11.4.3.1

Strainers - Baskets & Screen

Maintenance

NFPA 25

10.1.1.2

Test

NFPA 25

11.1.1.2

10.2.1.4, 10.2.1.7,
A.10.2.7
7.3.1

Activity

Standard

Table

Paragraph

Maintenance

NFPA 25

11.1.1.2

11.4.4.1

Maintenance

NFPA 25

11.1.1.2

11.4.4.2

Maintenance

NFPA 25

11.1.1.2

11.4.7.4

Maintenance

NFPA 25

11.1.1.2

11.4.5.1

Maintenance

NFPA 25

11.1.1.2

11.4.5.2

Maintenance

NFPA 25

11.1.1.2

11.4.6.4

Maintenance

NFPA 25

11.1.1.2

11.4.3.2

Maintenance

NFPA 25

11.1.1.2

11.4.3.3

Water Supply Flow Test

Paragraph

10 Year:
Item
Bladder Type Proportioning Systems Sight Glass
Bladder Type Proportioning Systems Hydrostatic Test
In-Line Balanced Pressure Type Proportioning
Systems - Foam Concentrate Tank
Line Type Proportioning Systems Foam Concentrate tank - corrosion and pickup
tubes
Line Type Proportioning Systems Foam Concentrate tank - Drain and Flush
Standard Balanced Pressure Type Proportioning
Systems - Foam Concentrate Tank
Standard Pressure Type Proportioning Systems Foam Concentrate Tank Drain & Flush
Standard Pressure Type Proportioning Systems Tank Corrosion and Hydrostatic Test

Page 18 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
Based on NFPA 25, 2011 Edition
Refer to NFPA 25 Chapter 9 for Water Storage Tank & Fire Pump Inspection, Testing and Maintenance
Requirements.
Refer to NFPA 25 Chapter 10 for Mainline Strainers Inspection, Testing and Maintenance Requirements.
Refer to NFPA 25 Chapter 13 for Valves, Valve Components & Trim Inspection, Testing and Maintenance
Requirements. See FEMPSD Summary of NFPA Inspection, Test & Maintenance Requirements for
Sprinkler Systems.
Refer to NFPA 72 Chapter 10 for Fire Alarm Systems Inspection, Testing and Maintenance Requirements.

Page 19 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
Hydrant
After Use:
Item

Activity

Standard

Table

Paragraph

Hydrant - (Dry Barrel and Wall)

Inspect

NFPA 25

7.1.1.2

7.2.2.4

Hydrant - (Wet Barrel)

Inspect

NFPA 25

7.1.1.2

7.2.2.5

Mainline Strainers

Inspect

NFPA 25

7.1.1.2

7.2.2.3

Quarterly:
Item
Hose Houses

Activity

Standard

Table

Paragraph

Inspect

NFPA 25

7.1.1.2

7.2.2.7

Semi-Annual:
Item
Monitor Nozzles

Activity

Standard

Table

Paragraph

Inspect

NFPA 25

7.1.1.2

7.2.2.6

Activity

Standard

Table

Paragraph

Annual:
Item
Hose Houses

Maintenance

NFPA 25

7.1.1.2

7.2.2.7

Hydrant - (Dry Barrel and Wall)

Inspect

NFPA 25

7.1.1.2

7.2.2.4

Hydrant - (Wet Barrel)

Inspect

NFPA 25

7.1.1.2

7.2.2.5

Hydrant - (Flow Test)

Test

NFPA 25

7.1.1.2

7.3.2

Monitor Nozzles (Range & Operation)

Test

NFPA 25

7.1.1.2

7.3.3

NFPA 25

7.1.1.2

7.4.2

NFPA 25

7.1.1.2

7.2.2.3

Monitor Nozzles

Maintenance
Inspect/
Maintenance
Maintenance

NFPA 25

7.1.1.2

7.4.3

Piping (exposed)

Inspect

NFPA 25

7.1.1.2

7.2.2.1

Activity

Standard

Table

Paragraph

Inspect

NFPA 25

7.1.1.2

7.2.2.2

Hydrant
Mainline Strainers

Other:
Item
Piping (underground)

Based on NFPA 25, 2011 Edition


See also F.E. Moran Plant Services ITM Requirements for Fire Service Mains & Control Valves on
separate sheets.

Page 20 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
Pre-action Deluge
Daily:
Item

Activity

Standard

Table

Paragraph

Valve Enclosure (during cold weather, w/o alarms)

Inspect

NFPA 25

10.1.1.2

13.4.3.1

Activity

Standard

Table

Paragraph

Control Valve - (sealed)

Inspect

NFPA 25

13.1.1.2

Gauges

Inspect

NFPA 25

5.1.1.2

Valve Enclosure(during cold weather, w/ alarms)

Inspect

NFPA 25

13.1.1.2

13.3.2.1
5.2.4.2, 5.2.4.3,
5.2.4.4
13.4.4.1.1.1

Paragraph

Weekly:
Item

Monthly:
Activity

Standard

Table

Gauges Air Pressure, Monitored 24/7

Item

Inspect

NFPA 25

5.1.1.2

5.2.4.3

Control Valve - (locked)

Inspect

NFPA 25

13.1.1.2

13.3.2.1.1

Control Valve - (tamper switches)

Inspect

NFPA 25

13.1.1.2

13.3.2.1.1

Pre-action/Deluge Valve - Exterior

Inspect

NFPA 25

13.1.1.2

13.4.3.1.6

UHSWSS Detectors

Inspect

NFPA 25

10.1.1.2

10.4.2

Activity

Standard

Table

Paragraph

Inspect

NFPA 25

10.1.1.2

10.2.8

NFPA 25

10.1.1.2

10.2.4. &
10.2.4.1

Quarterly:
Item
Drainage
Fittings

Inspect

Fittings - Rubber Gasket

Inspect

NFPA 25

10.1.1.2

10.2.4.1, A.10.2.4.1

Hydraulic Nameplate
Main Drain (when sole source of water is through
Backflow Preventer &/or Pressure Reducing Valves)

Inspect

NFPA 25

5.1.1.2

Test

NFPA 25

13.1.1.2

Pre-action Valve - Low Air Pressure Alarms

Test

NFPA 25

13.1.1.2

Pre-action Valve Priming Water

Test

NFPA 25

13.1.1.2

Inspect

NFPA 25

10.1.1.2

Test

NFPA 25

10.1.1.2

5.2.6
13.3.3.4, 13.2.5,
13.2.5.1
13.4.3.2.13,
13.4.3.2.14
13.4.3.2.1
10.2.1.1, 10.2.1.2,
10.2.4.2
13.2.6

Paragraph

Supports
Waterflow Alarms - Mechanical

Semi-Annual:
Activity

Standard

Table

Control Valve - (tamper switches)

Item

Test

NFPA 25

13.1.1.2

Waterflow Alarms (vane and pressure switches)

Test

NFPA 25

Activity

Standard

13.3.3.5
5.3.3.2 & 13.2.6

Annual:
Item
Control Valve - Position and Operation
Control Valves

Table

Paragraph

Test

NFPA 25

13.1.1.2

13.3.3.1

Maintenance

NFPA 25

13.1.1.2

13.3.4, 10.2.1.4

Annual (cont.)

Page 21 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
Flushing

Test

NFPA 25

Hangers

10.1.1.2

10.2.1.3, Sect. 10.3

Inspect

NFPA 25

10.1.1.2

10.2.4.2

Main Drain

Test

NFPA 25

10.1.1.2

13.3.3.4

Manual Release

Test

NFPA 25

10.1.1.2

10.2.1.3 & 10.3.6

Maintenance

NFPA 25

10.1.1.2

Nozzles

Inspect

NFPA 25

10.1.1.2

Nozzles

Test

NFPA 25

10.1.1.2

Inspect

NFPA 25

10.1.1.2

Nozzle Strainers - Flush

Inspect

NFPA 25

13.1.1.2

10.2.1.6, 10.2.7.2
10.2.1.1, 10.2.1.2,
10.2.1.6, 10.2.5.1 &
10.2.5.2
10.2.1.3, 10.2.1.6,
Sect. 10.3
10.2.1.1, 10.2.1.2,
10.2.4, 10.2.4.1
10.2.2, 13.4.3.1.7

Maintenance

NFPA 25

13.1.1.2

10.2.2, 13.4.3.3.2

Pre-action/Deluge Valves - Full Flow Trip Test

Test

NFPA 25

13.1.1.2

Strainers

Test

NFPA 25

10.1.1.2

Strainers

Maintenance

NFPA 25

10.1.1.2

Test

NFPA 25

10.1.1.2

10.2.2, 13.4.3.2.2
10.2.1.3, 10.2.1.7,
10.2.7
10.2.1.4, 10.2.1.6,
10.2.7
Section 10.4

Inspect

NFPA 25

Water Spray System

Test

NFPA 25

10.1.1.2

Water Spray System

Maintenance

NFPA 25

10.1.1.2

Pipe
Pre-action/Deluge Valve - (internal reset) Interior
Pre-action/Deluge Valves

UHSWSS Systems
Valve Enclosure Low Temp Alarms

13.4.3.1.2
Sect. 10.3 &
Ch. 13
10.2.1.4, Ch. 13

5 Year:
Item

Activity

Standard

Table

Check Valves

Inspect

NFPA 25

13.1.1.2

13.4.2.1

Pre-action/Deluge Valve - (external reset) Interior

Inspect

NFPA 25

13.1.1.2

13.4.3.1.7

Pre-action/Deluge Valve - (external reset) Interior

Maintenance

NFPA 25

Inspect

NFPA 25

13.1.1.2

13.4.3.1.8

Test

NFPA 25

5.1.1.2

Maintenance

NFPA 25

10.1.1.2

5.3.2.1, 5.3.2.2
10.2.1.4, 10.2.1.7,
A.10.2.7

Pre-action/Deluge Valve - Strainers, Filters & Orifices


Gauges - Check Calibration or Replace
Strainers - Baskets & Screen

Paragraph

13.4.3.3.2.1

After System Activation or Flow Test:


Activity

Standard

Table

Paragraph

Hangers

Item

Inspect

NFPA 25

10.1.1.2

Pipe

Inspect

NFPA 25

10.1.1.2

Strainers

Inspect

NFPA 25

10.1.1.2

Nozzles

Inspect

NFPA 25

10.1.1.2

10.2.4.2
10.2.4.1, 10.2.1.1,
10.2.1.2, 10.2.4
10.2.7
10.2.1.1, 10.2.1.2,
10.2.1.6, 10.2.5.1,
10.2.5.2

Activity

Standard

Table

Each Shift:
Item

Page 22 of 28

Paragraph

Summary of NFPA
Inspection, Test & Maintenance Requirements
UHSWSS Controllers

Inspect

NFPA 25

10.1.1.2

10.4.3

Inspect

NFPA 25

10.1.1.2

10.4.4

Each Shift (cont.):


UHSWSS Valves

Based on NFPA 25, 2011 Edition

Page 23 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
Sprinkler
Daily:
Item

Activity

Standard

Table

Valve Enclosure (during cold weather, w/o alarms)

Inspect

NFPA 25

13.1.1.2

Paragraph

Activity

Standard

Table

Control Valve - (sealed)

Inspect

NFPA 25

5.1.1.2

Gauges Dry, Pre-action & Deluge Systems

Inspect

NFPA 25

13.1.1.2

Valve Enclosure(during cold weather, w/ alarms)

Inspect

NFPA 25

13.1.1.2

Activity

Standard

Table

Inspect

NFPA 25

13.1.1.2

13.4.1.1

13.4.3.1, 13.4.4.1.1

Weekly:
Item

Paragraph
13.3.2.1
5.2.4.2, 5.2.4.3,
5.2.4.4
13.4.4.1.1.1

Monthly:
Item
Alarm Valve - Exterior

Paragraph

Control Valve - (locked)

Inspect

NFPA 25

13.1.1.2

13.3.2.1.1

Control Valve - (tamper switches)

Inspect

NFPA 25

13.1.1.2

13.3.2.1.1

Dry-Pipe - Exterior

Inspect

NFPA 25

13.1.1.2

13.4.4.1.4

Gauges - Wet Pipe Systems

Inspect

NFPA 25

5.1.1.2

5.2.4.1

Pre-Action Valve - Exterior

Inspect

NFPA 25

13.1.1.2

13.4.3.1.6

Quarterly:
Activity

Standard

Table

Waterflow Alarm Devices - Mechanical

Item

Test

NFPA 25

5.1.1.2

5.3.3.1

Dry Pipe Valve Quick-Opening Device

Test

NFPA 25

13.1.1.2

13.4.4.2.4

Dry Pipe Valve - Priming Water

Test

NFPA 25

13.1.1.2

13.4.4.2.1
13.4.4.2.6

Dry Pipe Valve - Low Air Press. Alarms

Paragraph

Test

NFPA 25

13.1.1.2

Fire Department Connection

Inspect

NFPA 25

13.1.1.2

13.7.1

Hose Valves

Inspect

NFPA 25

13.5.6.1.1

Hydraulic Nameplate
Main Drain (when sole source of water is through a
Backflow Preventer and/or Pressure Reducing
Valves)
Pre-action Valve - Priming Water

Inspect

NFPA 25

5.1.1.2

5.2.6

Test

NFPA 25

13.1.1.2

13.2.5, 13.2.5.1,
13.3.3.4

Test

NFPA 25

13.1.1.2

13.4.3.2.1

Pre-action Valve - Low Air Pressure Alarms

Test

NFPA 25

13.1.1.2

13.4.3.2.13

Pressure Reducing & Relief Valves


Supervisory Signal Devices (except Valve
Supervisory Switches)
Valve Supervisory Devices

Inspect

NFPA 25

13.1.1.2

13.5.1.1

Inspect

NFPA 25

5.1.1.2

5.2.5

Inspect

NFPA 25

5.1.1.2

5.2.5

Waterflow Devices (vane type, press switch, etc.)

Inspect

NFPA 25

13.1.1.2

5.2.5

Semi-Annual:
Item
Control Valve - (tamper switches)

Activity

Standard

Table

Test

NFPA 25

13.1.1.2

Semi-Annual (cont.):

Page 24 of 28

Paragraph
13.3.3.5

Summary of NFPA
Inspection, Test & Maintenance Requirements
Supervisory Signal Devices (except Valve
Supervisory Switches)
Waterflow Devices (vane & pressure switch)

Test

NFPA 25

13.1.1.2

13.3.3.5

Test

NFPA 25

5.1.1.2

5.3.3.2, 13.2.6

Activity

Standard

Table

Test

NFPA 25

5.1.1.2

Annual:
Item
Antifreeze Solution
Backflow Prevention Assemblies
Building (prior to freezing weather)
Control Valves
Control Valves Position & Operation
Dry Pipe Valves & Quick Opening Devices
Dry Pipe Valve - Interior

Paragraph
5.3.4

Test

NFPA 25

13.1.1.2

13.6.2

Inspect

NFPA 25

5.1.1.2

4.1.1.1

Maintenance

NFPA 25

13.1.1.2

13.3.4

Test

NFPA 25

13.1.1.2

13.3.3.1

Maintenance

NFPA 25

13.1.1.2

13.4.4.3

Inspect

NFPA 25

13.1.1.2

13.4.4.1.5

Dry Pipe Valve - Trip Test

Test

NFPA 25

13.1.1.2

13.4.4.2.2

Hangers/Seismic Bracing

Inspect

NFPA 25

5.1.1.2

5.2.3

Hose

Inspect

NFPA 1962

Ch. 4 & 7

Hose Assembly/Rack Pressure Reducing Valve

Inspect

NFPA 25

13.1.1.2

13.5.3.1

Hose Connection Pressure Reducing Valve

Inspect

NFPA 25

13.1.1.2

13.5.2.1

Hose Valves (Class I & III)

Test

NFPA 25

13.5.6.2

Maintenance

NFPA 25

5.1.1.2

Test

NFPA 25

13.1.1.2

Pipe and Fittings

Inspect

NFPA 25

5.1.1.2

13.4.4.3.2
13.2.5, 13.2.5.1,
13.3.3.4
5.2.2

Pre-Action Valve - (internal reset type) Interior

Inspect

NFPA 25

13.1.1.2

13.4.3.1.7

Test

NFPA 25

13.1.1.2

13.4.3.2.2
13.4.3.3.2

Low Point Drains Prior to Freezing (dry pipe sys)


Main Drain

Pre-Action Valve - Full Flow Trip Test


Pre-action/Deluge Valves

Maintenance

NFPA 25

13.1.1.2

Press. Reducing & Relief Valves Circulation Relief

Test

NFPA 25

13.1.1.2

13.5.7.1.2

Pressure Relief Valves

Test

NFPA 25

13.1.1.2

13.5.7.2.2

Spare Sprinklers

Inspect

NFPA 25

5.1.1.2

5.2.1.4

Sprinklers

Inspect

NFPA 25

5.1.1.2

Strainers

Maintenance

NFPA 25

10.1.1.2

5.2.1
10.2.7, 10.2.1.4,
10.2.1.6

Inspect

NFPA 25

Valve Enclosure Alarms (at beginning of heating


season)

13.4.3.2.14

3 Year:
Activity

Standard

Table

Dry Pipe Valve - Full Flow Trip Test

Item

Test

NFPA 25

13.1.1.2

Paragraph
13.4.4.2.2.2

Hose Valves (class II)

Test

NFPA 25

13.5.6.2

Activity

Standard

Table

5 Year:
Item

Paragraph

Alarm Valve - Interior

Inspect

NFPA 25

13.1.1.2

13.4.1.2

Alarm Valve - Strainers, Filters & Orifices

Inspect

NFPA 25

13.1.1.2

13.4.1.2

5 Year (cont.):

Page 25 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
Check Valve - Interior

Inspect

NFPA 25

13.1.1.2

13.4.2.1

Dry Pipe Valve - Strainers, Filters & Orifices

Inspect

NFPA 25

13.1.1.2

13.4.4.1.6

Gauges

Test

NFPA 25

5.1.1.2

5.3.2

Hose Connections Pressure Reducing Valves

Test

NFPA 25

13.1.1.2

13.5.2.2

Hose Racks Pressure Reducing & Relief Valves

Test

NFPA 25

13.1.1.2

13.5.3.2

Hoses

Test

NFPA 1962

Obstruction Investigation

Inspect

NFPA 25

5.1.1.2

14.2

Pre-Action Valve - (external reset type) Interior

Inspect

NFPA 25

13.1.1.2

13.4.3.1.7

Pre-Action Valve - Strainers, Filters & Orifices

Inspect

NFPA 25

13.1.1.2

13.4.3.1.8

Sprinkler - Extra High Temp.

Test

NFPA 25

5.1.1.2

5.3.1.1.1.4

Sprinkler Harsh Environment


Sprinkler System Pressure Reducing & Relief
Valves

Test

NFPA 25

5.3.1.1.2

Test

NFPA 25

13.1.1.2

13.5.1.2
10.2.1.4,
10.2.1.7, A.10.2.7

Strainers - Baskets & Screen

Maintenance

NFPA 25

10.1.1.2

Activity

Standard

Table

Replace/Test

NFPA 25

5.1.1.2

10 Year & every 10 Years thereafter:


Item
Dry System Sprinklers

Paragraph
5.3.1.1.1.6

20 Year & every 10 Years thereafter:


Item
Sprinklers - Fast Response

Activity

Standard

Table

Replace/Test

NFPA 25

5.1.1.2

Paragraph

Activity

Standard

Table

Paragraph

Replace/Test

NFPA 25

5.1.1.2

5.3.1.1.1

Paragraph

5.3.1.1.1.3

50 Year & every 10 Years thereafter:


Item
Sprinklers

75 Year and every 5 Years thereafter:


Item
Sprinkler - 75 Years

Activity

Standard

Table

Replace/Test

NFPA 25

2.1.1.2

5.3.1.1.1.5

Replace

NFPA 25

5.1.1.2

5.3.1.1.1.1

Sprinkler- Made Prior to 1920

Miscellaneous:
Item
Obstruction
Sprinklers- Made Prior to 1920

Activity

Standard

Table

Investigate

NFPA 25

5.1.1.2

14.3

Replace

NFPA 25

5.1.1.2

5.3.1.1.1.1

Based on NFPA 25, 2011 and 1962, 2008 Editions

Page 26 of 28

Paragraph

Summary of NFPA
Inspection, Test & Maintenance Requirements
Standpipe and Hose Systems
Weekly:
Item

Activity

Standard

Table

Control Valve - (sealed)

Inspect

NFPA 25

13.1.1.2

Paragraph
13.3.2.1

Gauges

Inspect

NFPA 25

6.1.1.2

6.2.2

Monthly:
Item

Activity

Standard

Table

Control Valve - (locked)

Inspect

NFPA 25

13.1.1.2

Paragraph
13.3.2.1.1

Control Valve - (tamper switches)

Inspect

NFPA 25

13.1.1.2

13.3.2.1.1

Activity

Standard

Table

Quarterly:
Item

Paragraph

Fire Department Connection

Inspect

NFPA 25

13.1.1.2

13.7.1

Fire Department Connection

Maintenance

NFPA 25

13.7.2, 13.7.3

Inspect

NFPA 25

13.1.1.2

13.5.6.1

Test

NFPA 25

13.1.1.2

13.4.4.2.6

Test

NFPA 25

13.1.1.2

13.2.5, 13.2.5.1,
13.3.3.4

Inspect

NFPA 25

13.1.1.2

13.5.1.1

Test

NFPA 25

13.1.1.2

13.2.6

Activity

Standard

Table

Test

NFPA 25

13.1.1.2

Activity

Standard

Table

Paragraph

Cabinet

Inspect

NFPA 25

6.1.1.2

NFPA 1962

Fire Hose
Fire Hose - Other Than Occupant Hose (service
test)
Hose Connections

Inspect

NFPA 25

6.1.1.2

NFPA 1962

Test

NFPA 1962

4.1.2

Maintenance

NFPA 25

6.1.1.2

Table 6.1.2

Hose Connection/Pressure Regulating Devices

Inspect

NFPA 25

13.1.1.2

13.5.2.1

Hose Nozzles

Inspect

NFPA 25

6.1.1.2

NFPA 1962

Hose Racks

Inspect

NFPA 25

13.1.1.2

13.5.3.1

Hose Storage Device

Inspect

NFPA 25

6.1.1.2

NFPA 1962

Hose Storage Device

Test

NFPA 25

6.1.1.2

NFPA 1962

Inspect

NFPA 25

6.1.1.2

Test

NFPA 25

13.1.1.2

Occupant Fire Hose & Nozzles

Inspect

NFPA 1962

6.2.3
13.2.5, 13.2.5.1,
13.3.3.4
4.3

Piping

Inspect

NFPA 25

6.1.1.2

6.2.1

Hose Valves
Low Air Pressure Alarms
Main Drain (when sole source of water is through a
Backflow Preventer and/or Pressure Reducing
Valves)
Pressure Regulating Devices and Connections
Waterflow Alarms

Semi-Annual:
Item
Control Valve (tamper switches)

Paragraph
13.3.3.5

Annual:
Item

Hydraulic Placard
Main Drain

Page 27 of 28

Summary of NFPA
Inspection, Test & Maintenance Requirements
Annual (cont.):
Pressure Reducing Valves
Valves (all types)

Inspect

NFPA 25

13.1.1.2

13.5.2.1, 13.5.3.1

Maintenance

NFPA 25

13.1.1.2

13.3.4

5 year:
Item

Activity

Standard

Table

Paragraph

Fire Hose (service test) and Every 3 Yrs. Thereafter

Test

NFPA 25

6.1.1.2

NFPA 1962

Flow Test Most Remote Hose Connection

Test

NFPA 25

6.1.1.2

6.3.1

Hydrostatic Test (dry systems or pipe)

Test

NFPA 25

6.1.1.2

6.3.2

Pressure Control Valve

Test

NFPA 25

13.1.1.2

13.5.3.2

Pressure Reducing Valve

Test

NFPA 25

13.1.1.2

13.5.2.2, 13.5.3.2

Prior to going in service:


Item

Activity

Standard

Table

Inspect

NFPA 1962

Activity

Standard

Table

Fire Hose (service test)

Inspect/Test

NFPA 1962

Fire Hose (service test)

Maintenance

NFPA 25

6.1.1.2

6.4

Inspect

NFPA 25

6.1.1.2

NFPA 1962

Activity

Standard

Table

Paragraph

Test

NFPA 1962

Fire Hose (service test) - Within Prior 90 Days

Paragraph
4.1.1, 4.3.1

After each use:


Item

Hose Nozzle

Paragraph
4.3.7

After Freezing:
Item
Fire Hose (service test)

4.1.12

Based on NFPA 25, 2011 and 1962, 2008 Editions

This document and its content is property of FPI - Sentinel. Any redistribution or reproduction of part or all of
the contents in any form is prohibited other than the following: 1) This document may be printed or downloaded
to a local hard disk extracts for personal use only 2) Information in this document may not be distributed,
commercially exploited or transmitted via website or other form of electronic retrieval system.

Page 28 of 28

Вам также может понравиться