Вы находитесь на странице: 1из 32

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

Electrical Transient Analyzer Program


Short-Circuit Analysis
IEC 60909 Standard
3-Phase Fault Currents

Number of Buses:

Number of Branches:

Number of Machines:

Swing

V-Control

Load

Total

81

83

XFMR2

XFMR3

Reactor

Line/Cable

Impedance

Tie PD

Total

74

81

Synchronous
Generator

Power
Grid

Synchronous
Motor

Induction
Machines

Lumped
Load

Total

59

61

System Frequency:

50.00 Hz

Unit System:

Metric

Project Filename:

STOCK YARD 2_2

Output Filename:

C:\ETAP 1250\STOCK YARD 2\Short Circuit 2.1.SI1

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

Adjustments
Apply
Tolerance

Individual

Adjustments

/Global

Transformer Impedance:

Yes

Individual

Reactor Impedance:

Yes

Individual

Overload Heater Resistance:

No

Transmission Line Length:

No

Cable Length:

No

Apply
Temperature Correction

Percent

Individual

Adjustments

/Global

Transmission Line Resistance:

Yes

Individual

Cable Resistance:

Yes

Individual

Degree C

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Bus Input Data

Bus
ID

Type

Initial Voltage
Nom. kV

Base kV

Sub-sys

%Mag.

Ang.

Bus1

Load

0.400

0.400

100.00

0.00

Bus2

Load

0.400

0.400

100.00

0.00

Bus3

Load

0.400

0.400

100.00

0.00

Bus4

Load

0.400

0.400

100.00

0.00

Bus5

Load

0.400

0.400

100.00

0.00

Bus6

Load

0.400

0.400

100.00

0.00

Bus7

Load

0.400

0.400

100.00

0.00

Bus8

Load

0.400

0.400

100.00

0.00

Bus9

Load

0.400

0.400

100.00

0.00

Bus10

Load

0.400

0.400

100.00

0.00

Bus11

Load

0.400

0.400

100.00

0.00

Bus12

Load

0.400

0.400

100.00

0.00

Bus13

Load

0.400

0.400

100.00

0.00

Bus14

Load

0.400

0.400

100.00

0.00

Bus15

Load

0.400

0.400

100.00

0.00

Bus16

Load

0.400

0.400

100.00

0.00

Bus17

Load

0.400

0.400

100.00

0.00

Bus18

Load

0.400

0.400

100.00

0.00

Bus19

Load

0.400

0.400

100.00

0.00

Bus20

Load

0.400

0.400

100.00

0.00

Bus21

Load

0.400

0.400

100.00

0.00

Bus22

Load

0.400

0.400

100.00

0.00

Bus23

Load

0.400

0.400

100.00

0.00

Bus24

Load

0.400

0.400

100.00

0.00

Bus25

Load

0.400

0.400

100.00

0.00

Bus26

Load

0.400

0.400

100.00

0.00

Bus27

Load

0.400

0.400

100.00

0.00

Bus28

Load

0.400

0.400

100.00

0.00

Bus29

Load

0.400

0.400

100.00

0.00

Bus30

Load

0.400

0.400

100.00

0.00

Bus31

Load

0.400

0.400

100.00

0.00

Bus32

Load

0.400

0.400

100.00

0.00

Bus33

Load

0.400

0.400

100.00

0.00

Bus34

Load

0.400

0.400

100.00

0.00

Bus35

Load

0.400

0.400

100.00

0.00

Page:

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Bus
ID

Type

Initial Voltage
Nom. kV

Base kV

Sub-sys

%Mag.

Ang.

Bus36

Load

0.400

0.400

100.00

0.00

Bus37

Load

0.400

0.400

100.00

0.00

Bus38

Load

0.400

0.400

100.00

0.00

Bus39

Load

0.400

0.400

100.00

0.00

Bus41

Load

0.400

0.400

100.00

0.00

Bus42

Load

0.400

0.400

100.00

0.00

Bus43

Load

6.000

6.000

100.00

0.00

Bus44

Load

6.000

6.000

100.00

0.00

Bus45

Load

6.000

6.000

100.00

0.00

Bus47

Load

0.400

0.400

100.00

0.00

Bus48

Load

0.400

0.400

100.00

0.00

Bus49

Load

0.400

0.400

100.00

0.00

Bus50

Load

0.400

0.400

100.00

0.00

Bus51

Load

0.400

0.400

100.00

0.00

Bus52

Load

0.400

0.400

100.00

0.00

Bus53

Load

0.400

0.400

100.00

0.00

Bus54

Load

0.400

0.400

100.00

0.00

Bus55

Load

0.400

0.400

100.00

0.00

Bus56

Load

0.400

0.400

100.00

0.00

Bus57

Load

0.400

0.400

100.00

0.00

Bus58

Load

0.400

0.400

100.00

0.00

Bus59

Load

0.400

0.400

100.00

0.00

Bus60

Load

0.400

0.400

100.00

0.00

Bus61

Load

0.400

0.400

100.00

0.00

Bus62

Load

0.400

0.400

100.00

0.00

Bus63

Load

0.400

0.400

100.00

0.00

Bus64

Load

0.400

0.400

100.00

0.00

Bus65

Load

0.400

0.400

100.00

0.00

Bus66

Load

0.400

0.400

100.00

0.00

Bus67

Load

0.400

0.400

100.00

0.00

Bus68

Load

0.400

0.400

100.00

0.00

Bus69

Load

0.400

0.400

100.00

0.00

Bus70

Load

0.400

0.400

100.00

0.00

Bus71

Load

0.400

0.400

100.00

0.00

Bus72

Load

0.400

0.400

100.00

0.00

Bus73

Load

0.400

0.400

100.00

0.00

Bus74

Load

0.400

0.400

100.00

0.00

Page:

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Bus
ID

Type

Initial Voltage
Nom. kV

Base kV

Sub-sys

%Mag.

Ang.

Bus75

Load

6.000

6.000

100.00

0.00

Bus76

Load

0.400

0.400

100.00

0.00

Bus77

Load

0.400

0.400

100.00

0.00

Bus78

Load

Bus79

SWNG

0.400

0.400

100.00

0.00

20.000

20.000

100.00

0.00

Bus80
LVMDB 1

Load

0.400

0.400

100.00

0.00

Load

0.400

0.400

100.00

0.00

LVMDB 2

Load

0.400

0.400

100.00

0.00

MV KDL 1

Load

20.000

20.000

100.00

0.00

MV KDL 2

SWNG

20.000

20.000

100.00

0.00

MVMDB 1

Load

6.000

6.000

100.00

0.00

83 Buses Total
All voltages reported by ETAP are in % of bus Nominal kV.
Base kV values of buses are calculated and used internally by ETAP .

Page:

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:

Study Case: SC

Filename:

STOCK YARD 2_2

Page:

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

Line/Cable Input Data


Ohms or Siemens/1000 m per Conductor (Cable) or per Phase (Line)
Line/Cable
ID

Length
Library

Size

Adj. (m)

% Tol.

#/Phase

T (C)

CABLE SPARE 1A

1.0NCUN4

4.0

10.0

75

5.59866

0.09300

0.0000575

CABLE SPARE 1B

1.0NCUN4

4.0

10.0

75

5.59866

0.09300

0.0000575

Cable1

22NCUS1

185

500.0

75

0.12208

0.12000

0.0000000

LV01W001

1.0NCUN1

400

12.0

11

75

0.06056

0.08900

0.0000000

LV01W003

1.0NCUN4

240

391.0

75

0.09252

0.07200

0.0001565

LV01W004

1.0NCUN4

400

250.0

75

0.06104

0.07100

0.0001687

LV01W005

1.0NCUN4

185

398.0

75

0.12208

0.07300

0.0001442

LV01W006

1.0NCUN4

70

288.0

75

0.32619

0.07500

0.0001307

LV01W007

1.0NCUN4

2.5

391.0

75

9.00364

0.09900

0.0000490

LV01W009

1.0NCUN4

2.5

250.0

75

9.00364

0.09900

0.0000490

LV01W010

1.0NCUN4

4.0

398.0

75

5.59866

0.09300

0.0000575

LV01W011

1.0NCUN4

6.0

246.0

75

3.73880

0.08900

0.0000663

LV01W012

1.0NCUN4

6.0

293.0

75

3.73880

0.08900

0.0000663

LV01W013

1.0NCUN4

10

401.0

75

2.22230

0.08400

0.0000807

LV01W014

1.0NCUN4

16

260.0

75

1.39251

0.08000

0.0000971

LV01W015

1.0NCUN4

6.0

260.0

75

3.73880

0.08900

0.0000663

LV01W016

1.0NCUN4

6.0

247.0

75

3.73880

0.08900

0.0000663

LV01W017

1.0NCUN4

95

151.0

75

0.23558

0.07300

0.0001433

LV01W018

1.0NCUN4

95

149.0

75

0.23558

0.07300

0.0001433

LV01W020

1.0NCUN4

4.0

143.0

75

5.59866

0.09300

0.0000575

LV01W022

1.0NCUN4

2.5

43.0

75

9.00364

0.09900

0.0000490

LV01W023

1.0NCUN4

95

14.0

75

0.23558

0.07300

0.0001433

LV01W024

1.0NCUN4

70

14.0

75

0.32619

0.07500

0.0001307

LV01W025

1.0NCUN4

240

14.0

75

0.09252

0.07200

0.0001565

LV01W029

1.0NCUN4

240

587.0

75

0.09252

0.07200

0.0001565

LV01W030

1.0NCUN4

2.5

242.0

75

9.00364

0.09900

0.0000490

LV01W031

1.0NCUN4

4.0

587.0

75

5.59866

0.09300

0.0000575

LV01W032

1.0NCUN4

2.5

242.0

75

9.00364

0.09900

0.0000490

LV01W033

1.0NCUN4

4.0

587.0

75

5.59866

0.09300

0.0000575

LV01W034

1.0NCUN4

2.5

391.0

75

9.00364

0.09900

0.0000490

LV01W035

1.0NCUN4

2.5

250.0

75

9.00364

0.09900

0.0000490

LV01W036

1.0NCUN4

2.5

288.0

75

9.00364

0.09900

0.0000490

LV01W037

1.0NCUN3

2.5

250.0

75

9.00364

0.09900

0.0000490

LV01W038

1.0NCUN4

6.0

11.0

75

3.73880

0.08900

0.0000663

LV01W039

1.0NCUN4

6.0

11.0

75

3.73880

0.08900

0.0000663

LV01WO19

1.0NCUN4

95

140.0

75

0.23558

0.07300

0.0001433

LV01WO28

1.0NCUN4

150

242.0

75

0.15165

0.07300

0.0001442

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:

Study Case: SC

Filename:

STOCK YARD 2_2

Page:

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

Ohms or Siemens/1000 m per Conductor (Cable) or per Phase (Line)


Line/Cable

Length
Size

Adj. (m)

LV02W001

1.0NCUN1

400

12.0

11

75

0.06056

0.08900

0.0000000

LV02W003

1.0NCUN4

240

329.0

75

0.09252

0.07200

0.0001565

LV02W004

1.0NCUN4

300

391.0

75

0.07630

0.07100

0.0001643

LV02W005

1.0NCUN4

400

250.0

75

0.06104

0.07100

0.0001687

LV02W006

1.0NCUN4

185

396.0

75

0.12208

0.07300

0.0001442

LV02W007

1.0NCUN4

150

432.0

75

0.15165

0.07300

0.0001442

LV02W008

1.0NCUN4

2.5

391.0

75

9.00364

0.09900

0.0000490

LV02W009

1.0NCUN4

2.5

329.0

75

9.00364

0.09900

0.0000490

LV02W011

1.0NCUN4

2.5

250.0

75

9.00364

0.09900

0.0000490

LV02W012

1.0NCUN4

4.0

396.0

75

5.59866

0.09300

0.0000575

LV02W013

1.0NCUN4

6.0

258.0

75

3.73880

0.08900

0.0000663

LV02W014

1.0NCUN4

10

329.0

75

2.22230

0.08400

0.0000807

LV02W015

1.0NCUN4

10

406.0

75

2.22230

0.08400

0.0000807

LV02W016

1.0NCUN4

10

432.0

75

2.22230

0.08400

0.0000807

LV02W017

1.0NCUN4

25

349.0

75

0.88415

0.08200

0.0000889

LV02W018

1.0NCUN4

25

403.0

75

0.88415

0.08200

0.0000889

LV02W019

1.0NCUN4

10

260.0

75

2.22230

0.08400

0.0000807

LV02W020

1.0NCUN4

10

418.0

75

2.22230

0.08400

0.0000807

LV02W021

1.0NCUN4

2.5

36.0

75

9.00364

0.09900

0.0000490

LV02W022

1.0NCUN4

95

14.0

75

0.23558

0.07300

0.0001433

LV02W023

1.0NCUN4

70

14.0

75

0.32619

0.07500

0.0001307

LV02W024

1.0NCUN4

300

230.0

75

0.07630

0.07100

0.0001643

LV02W025

1.0NCUN4

95

198.0

75

0.23558

0.07300

0.0001433

LV02W028

1.0NCUN4

185

413.0

75

0.12208

0.07300

0.0001442

LV02W029

1.0NCUN4

240

1084.0

75

0.09252

0.07200

0.0001565

LV02W030

1.0NCUN4

2.5

413.0

75

9.00364

0.09900

0.0000490

LV02W031

1.0NCUN4

6.0

1084.0

75

3.73880

0.08900

0.0000663

LV02W032

1.0NCUN4

2.5

413.0

75

9.00364

0.09900

0.0000490

LV02W033

1.0NCUN4

6.0

1084.0

75

3.73880

0.08900

0.0000663

LV02W034

1.0NCUN4

2.5

391.0

75

9.00364

0.09900

0.0000490

LV02W035

1.0NCUN4

2.5

250.0

75

9.00364

0.09900

0.0000490

LV02W036

1.0NCUN4

2.5

432.0

75

9.00364

0.09900

0.0000490

LV02W037

1.0NCUN4

2.5

250.0

75

9.00364

0.09900

0.0000490

MV01W001

11NCUS1

240

11.0

75

0.09347

0.10900

0.0001734

MV01W002

11NCUS3

25

195.0

75

0.88415

0.12900

0.0000679

MV01W003

11NCUS3

25

444.0

75

0.88415

0.12900

0.0000679

MV01004

11NCUS3

25

502.0

75

0.88415

0.12900

0.0000679

ID

Library

Line / Cable resistances are listed at the specified temperatures.

% Tol.

#/Phase

T (C)

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

2-Winding Transformer Input Data

Transformer
ID

Rating
MVA

Prim. kV

Sec. kV

Z Variation
%Z

X/R

% Tap Setting

Adjusted

+ 5%

- 5%

% Tol.

Prim.

Sec.

%Z

T1

3.000

20.000

0.400

10.00

6.00

10.0000

T2

3.000

20.000

0.400

10.00

6.00

10.0000

T3

3.500

20.000

6.000

10.00

8.50

10.0000

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

Branch Connections
CKT/Branch

Connected Bus ID

ID

Type

From Bus

% Impedance, Pos. Seq., 100 MVAb


To Bus

T1

2W XFMR

MV KDL 1

Bus78

51.61

309.65

313.92

T2

2W XFMR

MV KDL 1

Bus76

51.61

309.65

313.92

T3

2W XFMR

MV KDL 2

Bus75

32.92

279.85

281.78

CABLE SPARE 1A

Cable

LVMDB 1

Bus61

3499.16

58.13

3499.65

CABLE SPARE 1B

Cable

LVMDB 1

Bus62

3499.16

58.13

3499.65

Cable1

Cable

Bus79

MV KDL 1

1.53

1.50

2.14

LV01W001

Cable

Bus76

LVMDB 2

4.13

6.07

7.34

LV01W003

Cable

LVMDB 2

Bus22

1130.43

879.75

1432.42

LV01W004

Cable

LVMDB 2

Bus23

476.89

554.69

731.51

LV01W005

Cable

LVMDB 2

Bus24

1518.41

907.94

1769.16

LV01W006

Cable

LVMDB 2

Bus25

5871.44

1350.00

6024.64

LV01W007

Cable

LVMDB 2

Bus26

220026.40

2419.31

220039.70

LV01W009

Cable

LVMDB 2

Bus29

140681.80

1546.88

140690.30

LV01W010

Cable

LVMDB 2

Bus30

139266.70

2313.38

139285.90

LV01W011

Cable

LVMDB 2

Bus41

57484.02

1368.38

57500.30

LV01W012

Cable

LVMDB 2

Bus42

68466.74

1629.81

68486.13

LV01W013

Cable

LVMDB 2

Bus65

55696.29

2105.25

55736.06

LV01W014

Cable

LVMDB 2

Bus66

22628.31

1300.00

22665.63

LV01W015

Cable

LVMDB 2

Bus67

60755.47

1446.25

60772.68

LV01W016

Cable

LVMDB 2

Bus68

57717.70

1373.94

57734.05

LV01W017

Cable

LVMDB 2

Bus36

2223.31

688.94

2327.60

LV01W018

Cable

LVMDB 2

Bus37

2193.86

679.81

2296.77

LV01W020

Cable

LVMDB 2

Bus39

50038.02

831.19

50044.92

LV01W022

Cable

LVMDB 2

Bus69

24197.27

266.06

24198.73

LV01W023

Cable

LVMDB 2

Bus70

206.13

63.88

215.80

LV01W024

Cable

LVMDB 2

Bus71

285.42

65.63

292.86

LV01W025

Cable

LVMDB 2

Bus72

80.95

63.00

102.58

LV01W029

Cable

Bus63

Bus21

1697.09

1320.75

2150.47

LV01W030

Cable

Bus64

Bus27

136180.00

1497.38

136188.20

LV01W031

Cable

Bus64

Bus28

205400.80

3411.94

205429.20

LV01W032

Cable

LVMDB 2

Bus31

136180.00

1497.38

136188.20

LV01W033

Cable

LVMDB 2

Bus32

205400.80

3411.94

205429.20

LV01W034

Cable

LVMDB 2

Bus33

220026.40

2419.31

220039.70

LV01W035

Cable

LVMDB 2

Bus34

140681.80

1546.88

140690.30

LV01W036

Cable

LVMDB 2

Bus35

162065.50

1782.00

162075.30

LV01W037

Cable

LVMDB 2

Bus80

140681.80

1546.88

140690.30

LV01W038

Cable

LVMDB 2

Bus73

2570.42

61.19

2571.15

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

CKT/Branch

Connected Bus ID

ID
LV01W039

Type
Cable

From Bus
LVMDB 2

10

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

% Impedance, Pos. Seq., 100 MVAb


To Bus

Bus74

Page:

R
2570.42

X
61.19

Z
2571.15

LV01WO19

Cable

LVMDB 2

Bus38

2061.35

638.75

2158.04

LV01WO28

Cable

Bus63

Bus20

2293.71

1104.13

2545.62

LV02W001

Cable

Bus78

LVMDB 1

4.13

6.07

7.34

LV02W003

Cable

LVMDB 1

Bus2

951.18

740.25

1205.29

LV02W004

Cable

LVMDB 1

Bus1

932.32

867.53

1273.51

LV02W005

Cable

LVMDB 1

Bus5

476.89

554.69

731.51

LV02W006

Cable

LVMDB 1

Bus6

1510.78

903.37

1760.27

LV02W007

Cable

LVMDB 1

Bus7

4094.56

1971.00

4544.25

LV02W008

Cable

LVMDB 1

Bus8

220026.40

2419.31

220039.70

LV02W009

Cable

LVMDB 1

Bus9

185137.30

2035.69

185148.50

LV02W011

Cable

LVMDB 1

Bus12

140681.80

1546.88

140690.30

LV02W012

Cable

LVMDB 1

Bus13

138566.80

2301.75

138585.90

LV02W013

Cable

LVMDB 1

Bus48

60288.12

1435.13

60305.20

LV02W014

Cable

LVMDB 1

Bus49

45695.96

1727.25

45728.59

LV02W015

Cable

LVMDB 1

Bus50

56390.75

2131.50

56431.02

LV02W016

Cable

LVMDB 1

Bus51

60001.98

2268.00

60044.83

LV02W017

Cable

LVMDB 1

Bus52

19285.51

1788.63

19368.27

LV02W018

Cable

LVMDB 1

Bus53

22269.51

2065.38

22365.08

LV02W019

Cable

LVMDB 1

Bus54

36112.30

1365.00

36138.09

LV02W020

Cable

LVMDB 1

Bus55

58057.48

2194.50

58098.93

LV02W021

Cable

LVMDB 1

Bus56

20258.18

222.75

20259.41

LV02W022

Cable

LVMDB 1

Bus57

206.13

63.88

215.80

LV02W023

Cable

LVMDB 1

Bus58

285.42

65.63

292.86

LV02W024

Cable

LVMDB 1

Bus59

1096.84

1020.63

1498.24

LV02W025

Cable

LVMDB 1

Bus60

2915.33

903.37

3052.09

LV02W028

Cable

Bus77

Bus4

1575.64

942.16

1835.83

LV02W029

Cable

Bus77

Bus3

1566.99

1219.50

1985.61

LV02W030

Cable

Bus47

Bus10

232406.40

2555.44

232420.40

LV02W031

Cable

Bus47

Bus11

253303.60

6029.75

253375.30

LV02W032

Cable

LVMDB 1

Bus15

232406.40

2555.44

232420.40

LV02W033

Cable

LVMDB 1

Bus16

253303.60

6029.75

253375.30

LV02W034

Cable

LVMDB 1

Bus17

220026.40

2419.31

220039.70

LV02W035

Cable

LVMDB 1

Bus18

140681.80

1546.88

140690.30

LV02W036

Cable

LVMDB 1

Bus19

243098.20

2673.00

243112.90

LV02W037

Cable

LVMDB 1

Bus14

140681.80

1546.88

140690.30

MV01W001

Cable

Bus75

MVMDB 1

0.29

0.33

0.44

MV01W002

Cable

MVMDB 1

Bus43

47.89

6.99

48.40

MV01W003

Cable

MVMDB 1

Bus44

109.05

15.91

110.20

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

CKT/Branch

Connected Bus ID

ID

Type

From Bus

Cable

MVMDB 1

Bus45

MCCBLV0101

Tie Breaker

LVMDB 1

Bus77

MCCBLV0109

Tie Breaker

LVMDB 1

Bus47

MCCBLV0201

Tie Breaker

LVMDB 2

Bus63

MCCBLV0207

Tie Breaker

LVMDB 2

Bus64

11

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

% Impedance, Pos. Seq., 100 MVAb


To Bus

MV01004

Page:

R
123.29

X
17.99

Z
124.60

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

12

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

Power Grid Input Data

Power Grid

Connected Bus

ID

ID

% Impedance
100 MVA Base

Rating
MVASC

kV

KDL 1

Bus79

24.000

20.000

81.71507

408.57530

0.20

KDL 2

MV KDL 2

27.989

20.000

35.55101

355.51010

0.10

Total Connected Power Grids ( = 2 ): 51.989 MVA

X"

R/X

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

13

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

Induction Machine Input Data

Induction Machine
ID
S/R1

Connected Bus
Type

Qty

Motor

ID
Bus43

% Impedance
(Motor Base)

Rating
HP/kW
620.00

kVA

kV

718.65

6.000

Amp
69.15

PF
92.29

R
2.52

X"
15.18

mFact.
R/X"

MW/PP

0.17

0.31

S/R2

Motor

Bus44

620.00

718.65

6.000

69.15

92.29

2.52

15.18

0.17

0.31

S/R3

Motor

Bus45

620.00

718.65

6.000

69.15

92.29

2.52

15.18

0.17

0.31

CONV NC5

Motor

Bus1

200.00

234.44

0.380

356.19

91.83

3.74

16.24

0.23

0.10

CONV NC8

Motor

Bus2

160.00

188.00

0.380

285.63

91.73

3.98

16.18

0.25

0.08

NC9_1

Motor

Bus3

132.00

169.24

0.380

257.14

91.66

4.20

16.13

0.26

0.07

NC9_2

Motor

Bus4

132.00

169.24

0.380

257.14

91.66

4.20

16.13

0.26

0.07

CONV BCR2

Motor

Bus5

355.00

413.80

0.380

628.70

92.06

3.19

16.36

0.20

0.18

CONV BCR2-1

Motor

Bus6

132.00

169.24

0.380

257.14

91.66

4.20

16.13

0.26

0.07

TRANSFER CONV 2

Motor

Bus7

55.00

75.24

0.380

114.30

91.31

5.54

15.72

0.35

0.03

MOTOR BREAK NC5

Motor

Bus8

1.00

1.87

0.380

2.84

81.75

12.47

11.05

1.13

0.00

MOTOR BREAK NC8

Motor

Bus9

1.00

1.87

0.380

2.84

81.75

12.47

11.05

1.13

0.00

MOTOR BREAK NC9_2

Motor

Bus10

1.00

1.87

0.380

2.84

81.75

12.47

11.05

1.13

0.00

MOTOR BREAK NC9_1

Motor

Bus11

1.00

1.87

0.380

2.84

81.75

12.47

11.05

1.13

0.00

MOTOR BREAK BCR2

Motor

Bus12

1.00

1.87

0.380

2.84

81.75

12.47

11.05

1.13

0.00

MOTOR BREAK BCR2-1

Motor

Bus13

1.00

1.87

0.380

2.84

81.75

12.47

11.05

1.13

0.00

AIR COOLING FAN BCR2

Motor

Bus14

1.00

1.87

0.380

2.84

81.75

12.47

11.05

1.13

0.00

AIR COOLING FAN NC9_2

Motor

Bus15

1.00

1.87

0.380

2.84

81.75

12.47

11.05

1.13

0.00

AIR COOLING FAN NC9_1

Motor

Bus16

1.00

1.87

0.380

2.84

81.75

12.47

11.05

1.13

0.00

FORCE COOLER NC5

Motor

Bus17

1.00

1.87

0.380

2.84

81.75

12.47

11.05

1.13

0.00

FORCE COOLER BCR2

Motor

Bus18

1.00

1.87

0.380

2.84

81.75

12.47

11.05

1.13

0.00

AIR COOLING FAN TC2

Motor

Bus19

1.00

1.87

0.380

2.84

81.75

12.47

11.05

1.13

0.00

CONV NC7_2

Motor

Bus20

132.00

169.24

0.380

257.14

91.66

4.20

16.13

0.26

0.07

CONV NC7_1

Motor

Bus21

132.00

169.24

0.380

257.14

91.66

4.20

16.13

0.26

0.07

CONV NC6

Motor

Bus22

200.00

234.44

0.380

356.19

91.83

3.74

16.24

0.23

0.10

CONV CO3

Motor

Bus23

355.00

413.80

0.380

628.70

92.06

3.19

16.36

0.20

0.18

CONV CO3-1

Motor

Bus24

132.00

169.24

0.380

257.14

91.66

4.20

16.13

0.26

0.07

TRANSFER CONV 1

Motor

Bus25

55.00

75.24

0.380

114.30

91.31

5.54

15.72

0.35

0.03

MOTOR BREAK NC6

Motor

Bus26

1.00

1.87

0.380

2.84

81.75

12.47

11.05

1.13

0.00

MOTOR BREAK NC7_1

Motor

Bus27

1.00

1.87

0.380

2.84

81.75

12.47

11.05

1.13

0.00

MOTOR BREAK NC7_2

Motor

Bus28

1.00

1.87

0.380

2.84

81.75

12.47

11.05

1.13

0.00

MOTOR BREAK CO3

Motor

Bus29

1.00

1.87

0.380

2.84

81.75

12.47

11.05

1.13

0.00

MOTOR BREAK CO3-1

Motor

Bus30

1.00

1.87

0.380

2.84

81.75

12.47

11.05

1.13

0.00

COOLING FAN NC7_2

Motor

Bus31

1.00

1.87

0.380

2.84

81.75

12.47

11.05

1.13

0.00

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

14

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

Induction Machine Input Data

Induction Machine
ID
COOLING FAN NC7_1

Connected Bus
Type

Qty

Motor

ID
Bus32

% Impedance
(Motor Base)

Rating
HP/kW
1.00

kVA
1.87

kV
0.380

Amp
2.84

PF

X"

81.75

12.47

11.05

mFact.
R/X"
1.13

MW/PP
0.00

FORCE COOLER NC6

Motor

Bus33

1.00

1.87

0.380

2.84

81.75

12.47

11.05

1.13

0.00

FORCE COOLER CO3

Motor

Bus34

1.00

1.87

0.380

2.84

81.75

12.47

11.05

1.13

0.00

AIR COOLING FAN TC1

Motor

Bus35

1.00

1.87

0.380

2.84

81.75

12.47

11.05

1.13

0.00

DUST SUPPRESTION 1

Motor

Bus36

100.00

131.25

0.380

199.42

91.54

4.53

16.04

0.28

0.05

DUST SUPPRESTION 2

Motor

Bus37

100.00

131.25

0.380

199.42

91.54

4.53

16.04

0.28

0.05

POMPA ELECTRIC FIRE


FIGHT
JOKEY PUMP

Motor

Bus38

72.00

95.72

0.380

145.43

91.96

5.07

15.88

0.32

0.04

Motor

Bus39

5.50

8.63

0.380

13.11

85.82

9.52

13.68

0.70

0.00

DIVERTER GATE 1

Motor

Bus41

3.70

6.02

0.380

9.15

84.87

10.21

13.17

0.77

0.00

DIVERTER GATE 3

Motor

Bus42

3.70

6.02

0.380

9.15

84.87

10.21

13.17

0.77

0.00

DIVERTER GATE 2

Motor

Bus48

3.70

6.02

0.380

9.15

84.87

10.21

13.17

0.77

0.00

DIVERTER GATE 4

Motor

Bus49

3.70

6.02

0.380

9.15

84.87

10.21

13.17

0.77

0.00

DIVERTER GATE 6

Motor

Bus50

3.70

6.02

0.380

9.15

84.87

10.21

13.17

0.77

0.00

DIVERTER GATE 7

Motor

Bus51

3.70

6.02

0.380

9.15

84.87

10.21

13.17

0.77

0.00

MONORAIL CRANE TT02

Motor

Bus52

10.00

14.96

0.380

22.73

87.24

8.49

14.34

0.59

0.01

MONORAIL CRANE TT03

Motor

Bus53

10.00

14.96

0.380

22.73

87.24

8.49

14.34

0.59

0.01

AUTOMATIC SAMPLING 2

Motor

Bus54

5.00

7.91

0.380

12.01

85.59

9.69

13.56

0.71

0.00

PORTABLE COMPRESSOR 2

Motor

Bus55

5.00

7.91

0.380

12.01

85.59

9.69

13.56

0.71

0.00

DRY DEDUSTING SYSTEM

Motor

Bus59

110.00

141.51

0.400

204.25

91.58

4.41

16.07

0.27

0.06

WORKSHOP FEEDER

Motor

Bus60

70.00

93.33

0.400

134.71

91.89

5.12

15.86

0.32

0.04

DIVERTER GATE 5

Motor

Bus65

3.70

6.02

0.380

9.15

84.87

10.21

13.17

0.77

0.00

MONORAIL CRANE TT-01

Motor

Bus66

10.00

14.96

0.380

22.73

87.24

8.49

14.34

0.59

0.01

AUTOMATIC SAMPLING 1

Motor

Bus67

5.00

7.91

0.380

12.01

85.59

9.69

13.56

0.71

0.00

PORTABLE COMPRESSOR 1

Motor

Bus68

5.00

7.91

0.380

12.01

85.59

9.69

13.56

0.71

0.00

AIR COOLING FAN CO3

Motor

Bus80

1.00

1.87

0.400

2.70

81.75

12.47

11.05

1.13

0.00

Total Connected Induction Machines ( = 59 ): 5569.7 kVA

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

15

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

SHORT-CIRCUIT REPORT

3-Phase fault at bus: Bus63


Nominal kV
Voltage c Factor
Peak Value
Steady State

=
=
=
=

0.400
1.05
77.054
19.414

(User-Defined)
kA Method C
kA rms

Contribution
From Bus
ID

Voltage & Initial Symmetrical Current (rms)


To Bus
ID

%V
From Bus

kA
Real

kA
Imaginary

X/R
Ratio

kA
Magnitude

Bus63

Total

0.00

10.097

-35.603

3.5

37.007

Bus21

Bus63

20.15

0.523

-1.320

2.5

1.420

Bus20

Bus63

23.77

0.599

-1.282

2.1

1.415

Bus76

LVMDB 2

1.11

4.624

-22.392

4.8

22.865

Bus22

LVMDB 2

18.89

0.678

-1.881

2.8

1.999

Bus23

LVMDB 2

17.07

0.968

-3.401

3.5

3.536

Bus24

LVMDB 2

17.30

0.545

-1.379

2.5

1.482

Bus25

LVMDB 2

25.35

0.336

-0.542

1.6

0.638

Bus26

LVMDB 2

22.42

0.013

-0.008

0.7

0.015

Bus29

LVMDB 2

15.37

0.013

-0.010

0.7

0.017

Bus30

LVMDB 2

15.22

0.013

-0.010

0.7

0.017

Bus41

LVMDB 2

19.85

0.038

-0.036

0.9

0.052

Bus42

LVMDB 2

22.99

0.038

-0.034

0.9

0.051

Bus65

LVMDB 2

19.30

0.038

-0.036

1.0

0.052

Bus66

LVMDB 2

19.75

0.085

-0.101

1.2

0.132

Bus67

LVMDB 2

26.20

0.048

-0.044

0.9

0.065

Bus68

LVMDB 2

25.14

0.048

-0.045

0.9

0.066

Bus36

LVMDB 2

18.08

0.488

-1.071

2.2

1.177

Bus37

LVMDB 2

17.87

0.487

-1.074

2.2

1.179

Bus39

LVMDB 2

24.11

0.053

-0.051

1.0

0.073

Bus69

LVMDB 2

0.00

0.000

0.000

999.9

0.000

Bus70

LVMDB 2

0.00

0.000

0.000

999.9

0.000

Bus71

LVMDB 2

0.00

0.000

0.000

999.9

0.000

Bus72

LVMDB 2

0.00

0.000

0.000

999.9

0.000

Bus31

LVMDB 2

14.93

0.013

-0.010

0.7

0.017

Bus32

LVMDB 2

21.18

0.013

-0.009

0.7

0.016

Bus33

LVMDB 2

22.42

0.013

-0.008

0.7

0.015

Bus34

LVMDB 2

15.37

0.013

-0.010

0.7

0.017

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

16

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

(Cont.)
3-Phase fault at bus: Bus63
Nominal kV
Voltage c Factor
Peak Value
Steady State

=
=
=
=

0.400
1.05
77.054
19.414

(User-Defined)
kA Method C
kA rms

Contribution
From Bus
ID

Voltage & Initial Symmetrical Current (rms)


To Bus
ID

%V
From Bus

kA
Real

kA
Imaginary

X/R
Ratio

kA
Magnitude

Bus35

LVMDB 2

17.37

0.013

-0.009

0.7

0.016

Bus80

LVMDB 2

14.04

0.012

-0.009

0.7

0.015

Bus73

LVMDB 2

0.00

0.000

0.000

999.9

0.000

Bus74

LVMDB 2

0.00

0.000

0.000

999.9

0.000

Bus38

LVMDB 2

12.66

0.357

-0.814

2.3

0.889

Bus27

Bus64

14.93

0.013

-0.010

0.7

0.017

Bus28

Bus64

21.18

0.013

-0.009

0.7

0.016

CONV NC7_1

Bus21

105.26

0.523

-1.320

2.5

1.420

CONV NC7_2

Bus20

105.26

0.599

-1.282

2.1

1.415

MV KDL 1

Bus76

48.37

4.624

-22.392

4.8

22.865

CONV NC6

Bus22

105.26

0.678

-1.881

2.8

1.999

CONV CO3

Bus23

105.26

0.968

-3.401

3.5

3.536

CONV CO3-1

Bus24

105.26

0.545

-1.379

2.5

1.482

TRANSFER CONV 1

Bus25

105.26

0.336

-0.542

1.6

0.638

MOTOR BREAK NC6

Bus26

105.26

0.013

-0.008

0.7

0.015

MOTOR BREAK CO3

Bus29

105.26

0.013

-0.010

0.7

0.017

MOTOR BREAK CO3-1

Bus30

105.26

0.013

-0.010

0.7

0.017

DIVERTER GATE 1

Bus41

105.26

0.038

-0.036

0.9

0.052

DIVERTER GATE 3

Bus42

105.26

0.038

-0.034

0.9

0.051

DIVERTER GATE 5

Bus65

105.26

0.038

-0.036

1.0

0.052

MONORAIL CRANE TT-01

Bus66

105.26

0.085

-0.101

1.2

0.132

AUTOMATIC SAMPLING 1

Bus67

105.26

0.048

-0.044

0.9

0.065

PORTABLE COMPRESSOR 1

Bus68

105.26

0.048

-0.045

0.9

0.066

DUST SUPPRESTION 1

Bus36

105.26

0.488

-1.071

2.2

1.177

DUST SUPPRESTION 2

Bus37

105.26

0.487

-1.074

2.2

1.179

JOKEY PUMP

Bus39

105.26

0.053

-0.051

1.0

0.073

COOLING FAN NC7_2

Bus31

105.26

0.013

-0.010

0.7

0.017

COOLING FAN NC7_1

Bus32

105.26

0.013

-0.009

0.7

0.016

FORCE COOLER NC6

Bus33

105.26

0.013

-0.008

0.7

0.015

FORCE COOLER CO3

Bus34

105.26

0.013

-0.010

0.7

0.017

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

17

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

(Cont.)
3-Phase fault at bus: Bus63
Nominal kV
Voltage c Factor
Peak Value
Steady State

=
=
=
=

0.400
1.05
77.054
19.414

(User-Defined)
kA Method C
kA rms

Contribution
From Bus
ID

Voltage & Initial Symmetrical Current (rms)


To Bus
ID

%V
From Bus

kA
Real

kA
Imaginary

X/R
Ratio

kA
Magnitude

AIR COOLING FAN TC1

Bus35

105.26

0.013

-0.009

0.7

0.016

AIR COOLING FAN CO3

Bus80

100.00

0.012

-0.009

0.7

0.015

POMPA ELECTRIC FIRE


FIGHT
MOTOR BREAK NC7_1

Bus38

105.26

0.357

-0.814

2.3

0.889

Bus27

105.26

0.013

-0.010

0.7

0.017

MOTOR BREAK NC7_2

Bus28

105.26

0.013

-0.009

0.7

0.016

LVMDB 2

Bus63

0.00

8.975

-33.001

3.7

34.200

Bus64

LVMDB 2

0.00

0.026

-0.018

0.7

0.032

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current
TD (S)

Ib sym

0.01

34.120

Ib asym
41.810

24.164

Idc

0.02

33.056

35.199

12.094

0.03

32.026

32.550

5.814

0.04

31.041

31.167

2.795

0.05

30.108

30.144

1.464

0.06

29.653

29.661

0.716

0.07

29.209

29.211

0.350

0.08

28.778

28.779

0.171

0.09

28.360

28.360

0.084

0.10

27.955

27.955

0.044

0.15

27.206

27.206

0.001

0.20

26.500

26.500

0.000

0.25

25.840

25.840

0.000

0.30

25.837

25.837

0.000

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

18

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

3-Phase fault at bus: Bus77


Nominal kV
Voltage c Factor
Peak Value
Steady State

=
=
=
=

0.400
1.05
78.457
19.414

(User-Defined)
kA Method C
kA rms

Contribution
From Bus
ID

Voltage & Initial Symmetrical Current (rms)


To Bus
ID

%V
From Bus

kA
Real

kA
Imaginary

X/R
Ratio

kA
Magnitude

Bus77

Total

0.00

9.988

-36.211

3.6

37.563

Bus4

Bus77

17.86

0.547

-1.369

2.5

1.475

Bus3

Bus77

18.85

0.520

-1.342

2.6

1.439

Bus61

LVMDB 1

0.00

0.000

0.000

999.9

0.000

Bus62

LVMDB 1

0.00

0.000

0.000

999.9

0.000

Bus78

LVMDB 1

1.10

4.664

-22.284

4.8

22.767

Bus2

LVMDB 1

13.42

0.538

-1.600

3.0

1.688

Bus1

LVMDB 1

16.97

0.638

-1.916

3.0

2.019

Bus5

LVMDB 1

17.07

0.968

-3.401

3.5

3.536

Bus6

LVMDB 1

17.23

0.544

-1.380

2.5

1.483

Bus7

LVMDB 1

19.39

0.296

-0.575

1.9

0.647

Bus8

LVMDB 1

22.42

0.013

-0.008

0.7

0.015

Bus9

LVMDB 1

19.44

0.013

-0.009

0.7

0.016

Bus12

LVMDB 1

15.37

0.013

-0.010

0.7

0.017

Bus13

LVMDB 1

15.16

0.013

-0.010

0.7

0.017

Bus48

LVMDB 1

20.67

0.038

-0.035

0.9

0.052

Bus49

LVMDB 1

16.25

0.038

-0.038

1.0

0.054

Bus50

LVMDB 1

19.50

0.038

-0.036

1.0

0.052

Bus51

LVMDB 1

20.56

0.038

-0.035

0.9

0.052

Bus52

LVMDB 1

17.14

0.084

-0.105

1.3

0.134

Bus53

LVMDB 1

19.43

0.084

-0.101

1.2

0.132

Bus54

LVMDB 1

16.86

0.048

-0.052

1.1

0.071

Bus55

LVMDB 1

25.21

0.048

-0.045

0.9

0.066

Bus56

LVMDB 1

0.00

0.000

0.000

999.9

0.000

Bus57

LVMDB 1

0.00

0.000

0.000

999.9

0.000

Bus58

LVMDB 1

0.00

0.000

0.000

999.9

0.000

Bus59

LVMDB 1

11.46

0.374

-1.097

2.9

1.159

Bus60

LVMDB 1

15.44

0.326

-0.694

2.1

0.767

Bus15

LVMDB 1

23.43

0.013

-0.008

0.6

0.015

Bus16

LVMDB 1

25.05

0.013

-0.008

0.6

0.015

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

19

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

(Cont.)
3-Phase fault at bus: Bus77
Nominal kV
Voltage c Factor
Peak Value
Steady State

=
=
=
=

0.400
1.05
78.457
19.414

(User-Defined)
kA Method C
kA rms

Contribution
From Bus
ID

Voltage & Initial Symmetrical Current (rms)


To Bus
ID

%V
From Bus

kA
Real

kA
Imaginary

X/R
Ratio

kA
Magnitude

Bus17

LVMDB 1

22.42

0.013

-0.008

0.7

0.015

Bus18

LVMDB 1

15.37

0.013

-0.010

0.7

0.017

Bus19

LVMDB 1

24.28

0.013

-0.008

0.6

0.015

Bus14

LVMDB 1

15.37

0.013

-0.010

0.7

0.017

Bus10

Bus47

23.43

0.013

-0.008

0.6

0.015

Bus11

Bus47

25.05

0.013

-0.008

0.6

0.015

NC9_2

Bus4

105.26

0.547

-1.369

2.5

1.475

NC9_1

Bus3

105.26

0.520

-1.342

2.6

1.439

MV KDL 1

Bus78

48.16

4.664

-22.284

4.8

22.767

CONV NC8

Bus2

105.26

0.538

-1.600

3.0

1.688

CONV NC5

Bus1

105.26

0.638

-1.916

3.0

2.019

CONV BCR2

Bus5

105.26

0.968

-3.401

3.5

3.536

CONV BCR2-1

Bus6

105.26

0.544

-1.380

2.5

1.483

TRANSFER CONV 2

Bus7

105.26

0.296

-0.575

1.9

0.647

MOTOR BREAK NC5

Bus8

105.26

0.013

-0.008

0.7

0.015

MOTOR BREAK NC8

Bus9

105.26

0.013

-0.009

0.7

0.016

MOTOR BREAK BCR2

Bus12

105.26

0.013

-0.010

0.7

0.017

MOTOR BREAK BCR2-1

Bus13

105.26

0.013

-0.010

0.7

0.017

DIVERTER GATE 2

Bus48

105.26

0.038

-0.035

0.9

0.052

DIVERTER GATE 4

Bus49

105.26

0.038

-0.038

1.0

0.054

DIVERTER GATE 6

Bus50

105.26

0.038

-0.036

1.0

0.052

DIVERTER GATE 7

Bus51

105.26

0.038

-0.035

0.9

0.052

MONORAIL CRANE TT02

Bus52

105.26

0.084

-0.105

1.3

0.134

MONORAIL CRANE TT03

Bus53

105.26

0.084

-0.101

1.2

0.132

AUTOMATIC SAMPLING 2

Bus54

105.26

0.048

-0.052

1.1

0.071

PORTABLE COMPRESSOR 2

Bus55

105.26

0.048

-0.045

0.9

0.066

DRY DEDUSTING SYSTEM

Bus59

100.00

0.374

-1.097

2.9

1.159

WORKSHOP FEEDER

Bus60

100.00

0.326

-0.694

2.1

0.767

AIR COOLING FAN NC9_2

Bus15

105.26

0.013

-0.008

0.6

0.015

AIR COOLING FAN NC9_1

Bus16

105.26

0.013

-0.008

0.6

0.015

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

20

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

(Cont.)
3-Phase fault at bus: Bus77
Nominal kV
Voltage c Factor
Peak Value
Steady State

=
=
=
=

0.400
1.05
78.457
19.414

(User-Defined)
kA Method C
kA rms

Contribution
From Bus
ID

Voltage & Initial Symmetrical Current (rms)


To Bus
ID

%V
From Bus

kA
Real

kA
Imaginary

X/R
Ratio

kA
Magnitude

FORCE COOLER NC5

Bus17

105.26

0.013

-0.008

0.7

0.015

FORCE COOLER BCR2

Bus18

105.26

0.013

-0.010

0.7

0.017

AIR COOLING FAN TC2

Bus19

105.26

0.013

-0.008

0.6

0.015

AIR COOLING FAN BCR2

Bus14

105.26

0.013

-0.010

0.7

0.017

MOTOR BREAK NC9_2

Bus10

105.26

0.013

-0.008

0.6

0.015

MOTOR BREAK NC9_1

Bus11

105.26

0.013

-0.008

0.6

0.015

Bus47

LVMDB 1

0.00

0.026

-0.016

0.6

0.030

LVMDB 1

Bus77

0.00

8.921

-33.500

3.8

34.667

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current
TD (S)

Ib sym

0.01

34.506

Ib asym
42.403

24.645

Idc

0.02

33.365

35.553

12.279

0.03

32.262

32.797

5.903

0.04

31.206

31.335

2.838

0.05

30.204

30.241

1.477

0.06

29.716

29.725

0.721

0.07

29.240

29.243

0.352

0.08

28.778

28.779

0.172

0.09

28.330

28.330

0.084

0.10

27.896

27.896

0.044

0.15

27.092

27.092

0.001

0.20

26.335

26.335

0.000

0.25

25.628

25.628

0.000

0.30

25.624

25.624

0.000

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

21

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

3-Phase fault at bus: LVMDB 1


Nominal kV
Voltage c Factor
Peak Value
Steady State

=
=
=
=

0.400
1.05
78.457
19.414

(User-Defined)
kA Method C
kA rms

Contribution
From Bus
ID

Voltage & Initial Symmetrical Current (rms)


To Bus
ID

%V
From Bus

kA
Real

kA
Imaginary

X/R
Ratio

kA
Magnitude

LVMDB 1

Total

0.00

9.988

-36.211

3.6

37.563

Bus61

LVMDB 1

0.00

0.000

0.000

999.9

0.000

Bus62

LVMDB 1

0.00

0.000

0.000

999.9

0.000

Bus78

LVMDB 1

1.10

4.664

-22.284

4.8

22.767

Bus2

LVMDB 1

13.42

0.538

-1.600

3.0

1.688

Bus1

LVMDB 1

16.97

0.638

-1.916

3.0

2.019

Bus5

LVMDB 1

17.07

0.968

-3.401

3.5

3.536

Bus6

LVMDB 1

17.23

0.544

-1.380

2.5

1.483

Bus7

LVMDB 1

19.39

0.296

-0.575

1.9

0.647

Bus8

LVMDB 1

22.42

0.013

-0.008

0.7

0.015

Bus9

LVMDB 1

19.44

0.013

-0.009

0.7

0.016

Bus12

LVMDB 1

15.37

0.013

-0.010

0.7

0.017

Bus13

LVMDB 1

15.16

0.013

-0.010

0.7

0.017

Bus48

LVMDB 1

20.67

0.038

-0.035

0.9

0.052

Bus49

LVMDB 1

16.25

0.038

-0.038

1.0

0.054

Bus50

LVMDB 1

19.50

0.038

-0.036

1.0

0.052

Bus51

LVMDB 1

20.56

0.038

-0.035

0.9

0.052

Bus52

LVMDB 1

17.14

0.084

-0.105

1.3

0.134

Bus53

LVMDB 1

19.43

0.084

-0.101

1.2

0.132

Bus54

LVMDB 1

16.86

0.048

-0.052

1.1

0.071

Bus55

LVMDB 1

25.21

0.048

-0.045

0.9

0.066

Bus56

LVMDB 1

0.00

0.000

0.000

999.9

0.000

Bus57

LVMDB 1

0.00

0.000

0.000

999.9

0.000

Bus58

LVMDB 1

0.00

0.000

0.000

999.9

0.000

Bus59

LVMDB 1

11.46

0.374

-1.097

2.9

1.159

Bus60

LVMDB 1

15.44

0.326

-0.694

2.1

0.767

Bus15

LVMDB 1

23.43

0.013

-0.008

0.6

0.015

Bus16

LVMDB 1

25.05

0.013

-0.008

0.6

0.015

Bus17

LVMDB 1

22.42

0.013

-0.008

0.7

0.015

Bus18

LVMDB 1

15.37

0.013

-0.010

0.7

0.017

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

22

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

(Cont.)
3-Phase fault at bus: LVMDB 1
Nominal kV
Voltage c Factor
Peak Value
Steady State

=
=
=
=

0.400
1.05
78.457
19.414

(User-Defined)
kA Method C
kA rms

Contribution
From Bus
ID

Voltage & Initial Symmetrical Current (rms)


To Bus
ID

%V
From Bus

kA
Real

kA
Imaginary

X/R
Ratio

kA
Magnitude

Bus19

LVMDB 1

24.28

0.013

-0.008

0.6

0.015

Bus14

LVMDB 1

15.37

0.013

-0.010

0.7

0.017

Bus10

Bus47

23.43

0.013

-0.008

0.6

0.015

Bus11

Bus47

25.05

0.013

-0.008

0.6

0.015

Bus4

Bus77

17.86

0.547

-1.369

2.5

1.475

Bus3

Bus77

18.85

0.520

-1.342

2.6

1.439

MV KDL 1

Bus78

48.16

4.664

-22.284

4.8

22.767

CONV NC8

Bus2

105.26

0.538

-1.600

3.0

1.688

CONV NC5

Bus1

105.26

0.638

-1.916

3.0

2.019

CONV BCR2

Bus5

105.26

0.968

-3.401

3.5

3.536

CONV BCR2-1

Bus6

105.26

0.544

-1.380

2.5

1.483

TRANSFER CONV 2

Bus7

105.26

0.296

-0.575

1.9

0.647

MOTOR BREAK NC5

Bus8

105.26

0.013

-0.008

0.7

0.015

MOTOR BREAK NC8

Bus9

105.26

0.013

-0.009

0.7

0.016

MOTOR BREAK BCR2

Bus12

105.26

0.013

-0.010

0.7

0.017

MOTOR BREAK BCR2-1

Bus13

105.26

0.013

-0.010

0.7

0.017

DIVERTER GATE 2

Bus48

105.26

0.038

-0.035

0.9

0.052

DIVERTER GATE 4

Bus49

105.26

0.038

-0.038

1.0

0.054

DIVERTER GATE 6

Bus50

105.26

0.038

-0.036

1.0

0.052

DIVERTER GATE 7

Bus51

105.26

0.038

-0.035

0.9

0.052

MONORAIL CRANE TT02

Bus52

105.26

0.084

-0.105

1.3

0.134

MONORAIL CRANE TT03

Bus53

105.26

0.084

-0.101

1.2

0.132

AUTOMATIC SAMPLING 2

Bus54

105.26

0.048

-0.052

1.1

0.071

PORTABLE COMPRESSOR 2

Bus55

105.26

0.048

-0.045

0.9

0.066

DRY DEDUSTING SYSTEM

Bus59

100.00

0.374

-1.097

2.9

1.159

WORKSHOP FEEDER

Bus60

100.00

0.326

-0.694

2.1

0.767

AIR COOLING FAN NC9_2

Bus15

105.26

0.013

-0.008

0.6

0.015

AIR COOLING FAN NC9_1

Bus16

105.26

0.013

-0.008

0.6

0.015

FORCE COOLER NC5

Bus17

105.26

0.013

-0.008

0.7

0.015

FORCE COOLER BCR2

Bus18

105.26

0.013

-0.010

0.7

0.017

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

23

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

(Cont.)
3-Phase fault at bus: LVMDB 1
Nominal kV
Voltage c Factor
Peak Value
Steady State

=
=
=
=

0.400
1.05
78.457
19.414

(User-Defined)
kA Method C
kA rms

Contribution
From Bus
ID

Voltage & Initial Symmetrical Current (rms)


To Bus
ID

%V
From Bus

kA
Real

kA
Imaginary

X/R
Ratio

kA
Magnitude

AIR COOLING FAN TC2

Bus19

105.26

0.013

-0.008

0.6

0.015

AIR COOLING FAN BCR2

Bus14

105.26

0.013

-0.010

0.7

0.017

MOTOR BREAK NC9_2

Bus10

105.26

0.013

-0.008

0.6

0.015

MOTOR BREAK NC9_1

Bus11

105.26

0.013

-0.008

0.6

0.015

NC9_2

Bus4

105.26

0.547

-1.369

2.5

1.475

NC9_1

Bus3

105.26

0.520

-1.342

2.6

1.439

Bus47

LVMDB 1

0.00

0.026

-0.016

0.6

0.030

Bus77

LVMDB 1

0.00

1.067

-2.711

2.5

2.914

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current
TD (S)

Ib sym

0.01

34.506

Ib asym
42.403

24.645

Idc

0.02

33.365

35.553

12.279

0.03

32.262

32.797

5.903

0.04

31.206

31.335

2.838

0.05

30.204

30.241

1.477

0.06

29.716

29.725

0.721

0.07

29.240

29.243

0.352

0.08

28.778

28.779

0.172

0.09

28.330

28.330

0.084

0.10

27.896

27.896

0.044

0.15

27.092

27.092

0.001

0.20

26.335

26.335

0.000

0.25

25.628

25.628

0.000

0.30

25.624

25.624

0.000

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

24

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

3-Phase fault at bus: LVMDB 2


Nominal kV
Voltage c Factor
Peak Value
Steady State

=
=
=
=

0.400
1.05
77.054
19.414

(User-Defined)
kA Method C
kA rms

Contribution
From Bus
ID

Voltage & Initial Symmetrical Current (rms)


To Bus
ID

%V
From Bus

kA
Real

kA
Imaginary

X/R
Ratio

kA
Magnitude

LVMDB 2

Total

0.00

10.097

-35.603

3.5

37.007

Bus76

LVMDB 2

1.11

4.624

-22.392

4.8

22.865

Bus22

LVMDB 2

18.89

0.678

-1.881

2.8

1.999

Bus23

LVMDB 2

17.07

0.968

-3.401

3.5

3.536

Bus24

LVMDB 2

17.30

0.545

-1.379

2.5

1.482

Bus25

LVMDB 2

25.35

0.336

-0.542

1.6

0.638

Bus26

LVMDB 2

22.42

0.013

-0.008

0.7

0.015

Bus29

LVMDB 2

15.37

0.013

-0.010

0.7

0.017

Bus30

LVMDB 2

15.22

0.013

-0.010

0.7

0.017

Bus41

LVMDB 2

19.85

0.038

-0.036

0.9

0.052

Bus42

LVMDB 2

22.99

0.038

-0.034

0.9

0.051

Bus65

LVMDB 2

19.30

0.038

-0.036

1.0

0.052

Bus66

LVMDB 2

19.75

0.085

-0.101

1.2

0.132

Bus67

LVMDB 2

26.20

0.048

-0.044

0.9

0.065

Bus68

LVMDB 2

25.14

0.048

-0.045

0.9

0.066

Bus36

LVMDB 2

18.08

0.488

-1.071

2.2

1.177

Bus37

LVMDB 2

17.87

0.487

-1.074

2.2

1.179

Bus39

LVMDB 2

24.11

0.053

-0.051

1.0

0.073

Bus69

LVMDB 2

0.00

0.000

0.000

999.9

0.000

Bus70

LVMDB 2

0.00

0.000

0.000

999.9

0.000

Bus71

LVMDB 2

0.00

0.000

0.000

999.9

0.000

Bus72

LVMDB 2

0.00

0.000

0.000

999.9

0.000

Bus31

LVMDB 2

14.93

0.013

-0.010

0.7

0.017

Bus32

LVMDB 2

21.18

0.013

-0.009

0.7

0.016

Bus33

LVMDB 2

22.42

0.013

-0.008

0.7

0.015

Bus34

LVMDB 2

15.37

0.013

-0.010

0.7

0.017

Bus35

LVMDB 2

17.37

0.013

-0.009

0.7

0.016

Bus80

LVMDB 2

14.04

0.012

-0.009

0.7

0.015

Bus73

LVMDB 2

0.00

0.000

0.000

999.9

0.000

Bus74

LVMDB 2

0.00

0.000

0.000

999.9

0.000

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

25

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

(Cont.)
3-Phase fault at bus: LVMDB 2
Nominal kV
Voltage c Factor
Peak Value
Steady State

=
=
=
=

0.400
1.05
77.054
19.414

(User-Defined)
kA Method C
kA rms

Contribution
From Bus
ID

Voltage & Initial Symmetrical Current (rms)


To Bus
ID

%V
From Bus

kA
Real

kA
Imaginary

X/R
Ratio

kA
Magnitude

Bus38

LVMDB 2

12.66

0.357

-0.814

2.3

0.889

Bus27

Bus64

14.93

0.013

-0.010

0.7

0.017

Bus28

Bus64

21.18

0.013

-0.009

0.7

0.016

Bus21

Bus63

20.15

0.523

-1.320

2.5

1.420

Bus20

Bus63

23.77

0.599

-1.282

2.1

1.415

MV KDL 1

Bus76

48.37

4.624

-22.392

4.8

22.865

CONV NC6

Bus22

105.26

0.678

-1.881

2.8

1.999

CONV CO3

Bus23

105.26

0.968

-3.401

3.5

3.536

CONV CO3-1

Bus24

105.26

0.545

-1.379

2.5

1.482

TRANSFER CONV 1

Bus25

105.26

0.336

-0.542

1.6

0.638

MOTOR BREAK NC6

Bus26

105.26

0.013

-0.008

0.7

0.015

MOTOR BREAK CO3

Bus29

105.26

0.013

-0.010

0.7

0.017

MOTOR BREAK CO3-1

Bus30

105.26

0.013

-0.010

0.7

0.017

DIVERTER GATE 1

Bus41

105.26

0.038

-0.036

0.9

0.052

DIVERTER GATE 3

Bus42

105.26

0.038

-0.034

0.9

0.051

DIVERTER GATE 5

Bus65

105.26

0.038

-0.036

1.0

0.052

MONORAIL CRANE TT-01

Bus66

105.26

0.085

-0.101

1.2

0.132

AUTOMATIC SAMPLING 1

Bus67

105.26

0.048

-0.044

0.9

0.065

PORTABLE COMPRESSOR 1

Bus68

105.26

0.048

-0.045

0.9

0.066

DUST SUPPRESTION 1

Bus36

105.26

0.488

-1.071

2.2

1.177

DUST SUPPRESTION 2

Bus37

105.26

0.487

-1.074

2.2

1.179

JOKEY PUMP

Bus39

105.26

0.053

-0.051

1.0

0.073

COOLING FAN NC7_2

Bus31

105.26

0.013

-0.010

0.7

0.017

COOLING FAN NC7_1

Bus32

105.26

0.013

-0.009

0.7

0.016

FORCE COOLER NC6

Bus33

105.26

0.013

-0.008

0.7

0.015

FORCE COOLER CO3

Bus34

105.26

0.013

-0.010

0.7

0.017

AIR COOLING FAN TC1

Bus35

105.26

0.013

-0.009

0.7

0.016

AIR COOLING FAN CO3

Bus80

100.00

0.012

-0.009

0.7

0.015

POMPA ELECTRIC FIRE


FIGHT
MOTOR BREAK NC7_1

Bus38

105.26

0.357

-0.814

2.3

0.889

Bus27

105.26

0.013

-0.010

0.7

0.017

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

26

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

(Cont.)
3-Phase fault at bus: LVMDB 2
Nominal kV
Voltage c Factor
Peak Value
Steady State

=
=
=
=

0.400
1.05
77.054
19.414

(User-Defined)
kA Method C
kA rms

Contribution
From Bus
ID

Voltage & Initial Symmetrical Current (rms)


To Bus
ID

%V
From Bus

kA
Real

kA
Imaginary

X/R
Ratio

kA
Magnitude

MOTOR BREAK NC7_2

Bus28

105.26

0.013

-0.009

0.7

0.016

CONV NC7_1

Bus21

105.26

0.523

-1.320

2.5

1.420

CONV NC7_2

Bus20

105.26

0.599

-1.282

2.1

1.415

Bus63

LVMDB 2

0.00

1.122

-2.602

2.3

2.834

Bus64

LVMDB 2

0.00

0.026

-0.018

0.7

0.032

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current
TD (S)

Ib sym

0.01

34.120

Ib asym
41.810

24.164

Idc

0.02

33.056

35.199

12.094

0.03

32.026

32.550

5.814

0.04

31.041

31.167

2.795

0.05

30.108

30.144

1.464

0.06

29.653

29.661

0.716

0.07

29.209

29.211

0.350

0.08

28.778

28.779

0.171

0.09

28.360

28.360

0.084

0.10

27.955

27.955

0.044

0.15

27.206

27.206

0.001

0.20

26.500

26.500

0.000

0.25

25.840

25.840

0.000

0.30

25.837

25.837

0.000

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

27

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

3-Phase fault at bus: MV KDL 1


Nominal kV
Voltage c Factor
Peak Value
Steady State

=
=
=
=

20.000
1.10
2.437
0.690

(User-Defined)
kA Method C
kA rms

Contribution
From Bus
ID

Voltage & Initial Symmetrical Current (rms)


To Bus
ID

%V
From Bus

kA
Real

kA
Imaginary

X/R
Ratio

kA
Magnitude

MV KDL 1

Total

0.00

0.290

-1.120

3.9

1.157

Bus79

MV KDL 1

0.47

0.137

-0.676

4.9

0.690

Bus78

MV KDL 1

23.56

0.075

-0.226

3.0

0.238

Bus76

MV KDL 1

22.84

0.078

-0.218

2.8

0.231

KDL 1

Bus79

100.00

0.137

-0.676

4.9

0.690

LVMDB 1

Bus78

24.06

3.743

-11.310

3.0

11.914

LVMDB 2

Bus76

23.32

3.877

-10.880

2.8

11.550

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current
TD (S)

Ib sym

Ib asym

Idc

0.01

1.092

1.338

0.772

0.02

1.068

1.134

0.380

0.03

1.045

1.061

0.183

0.04

1.022

1.026

0.088

0.05

1.000

1.001

0.045

0.06

0.989

0.989

0.022

0.07

0.978

0.979

0.011

0.08

0.968

0.968

0.005

0.09

0.958

0.958

0.002

0.10

0.948

0.948

0.001

0.15

0.930

0.930

0.000

0.20

0.912

0.912

0.000

0.25

0.896

0.896

0.000

0.30

0.896

0.896

0.000

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

28

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

3-Phase fault at bus: MV KDL 2


Nominal kV
Voltage c Factor
Peak Value
Steady State

=
=
=
=

20.000
1.10
2.701
0.808

(User-Defined)
kA Method C
kA rms

Contribution
From Bus
ID

Voltage & Initial Symmetrical Current (rms)


To Bus
ID

MV KDL 2

Total

Bus75

%V
From Bus

kA
Real

kA
Imaginary

X/R
Ratio

kA
Magnitude

0.00

0.137

-1.115

8.1

1.123

MV KDL 2

28.03

0.057

-0.311

5.5

0.316

KDL 2

MV KDL 2

100.00

0.080

-0.804

10.0

0.808

MVMDB 1

Bus75

28.07

0.190

-1.036

5.5

1.053

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current
TD (S)

Ib sym

0.01

1.103

Ib asym
1.551

1.091

Idc

0.02

1.082

1.328

0.769

0.03

1.062

1.189

0.535

0.04

1.042

1.107

0.372

0.05

1.023

1.059

0.272

0.06

1.014

1.032

0.192

0.07

1.005

1.014

0.135

0.08

0.996

1.001

0.095

0.09

0.988

0.990

0.067

0.10

0.979

0.980

0.050

0.15

0.962

0.962

0.009

0.20

0.946

0.946

0.002

0.25

0.931

0.931

0.000

0.30

0.930

0.930

0.000

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

29

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

3-Phase fault at bus: MVMDB 1


Nominal kV
Voltage c Factor
Peak Value
Steady State

=
=
=
=

6.000
1.10
7.027
1.568

(User-Defined)
kA Method C
kA rms

Contribution
From Bus
ID

Voltage & Initial Symmetrical Current (rms)


To Bus
ID

%V
From Bus

kA
Real

kA
Imaginary

X/R
Ratio

kA
Magnitude

MVMDB 1

Total

0.00

0.467

-2.990

6.4

3.026

Bus75

MVMDB 1

0.06

0.168

-1.559

9.3

1.568

Bus43

MVMDB 1

2.24

0.091

-0.482

5.3

0.491

Bus44

MVMDB 1

5.06

0.103

-0.475

4.6

0.486

Bus45

MVMDB 1

5.71

0.105

-0.473

4.5

0.485

MV KDL 2

Bus75

41.79

0.168

-1.559

9.3

1.568

S/R1

Bus43

100.00

0.091

-0.482

5.3

0.491

S/R2

Bus44

100.00

0.103

-0.475

4.6

0.486

S/R3

Bus45

100.00

0.105

-0.473

4.5

0.485

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current
TD (S)

Ib sym

0.01

2.860

Ib asym
3.902

2.654

Idc

0.02

2.711

3.192

1.685

0.03

2.567

2.790

1.094

0.04

2.429

2.535

0.725

0.05

2.298

2.349

0.488

0.06

2.235

2.260

0.333

0.07

2.175

2.187

0.229

0.08

2.116

2.122

0.160

0.09

2.058

2.061

0.112

0.10

2.003

2.004

0.078

0.15

1.895

1.895

0.014

0.20

1.793

1.793

0.003

0.25

1.698

1.698

0.000

0.30

1.693

1.693

0.000

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

30

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

Short-Circuit Summary Report


3-Phase Fault Currents
Device Capacity (kA)
Bus
ID
Bus63

Bus77

LVMDB 1

Device
kV

ID

Type

0.400

Bus63

Bus

0.400

MCCBLV0201

CB

0.400

Bus77

Bus

0.400

MCCBLV0101

CB

Making
Peak

Short-Circuit Current (kA)


Ib sym

Ib asym

Idc

I"k

ip

37.007

77.054
77.054

105.000

50.000

50.000

37.007
37.563

78.457

105.000

50.000

50.000

37.563

78.457

Ib sym

Ib asym

Idc

Ik
19.414

27.955

27.955

0.044

27.896

27.896

0.044

19.414

0.400

LVMDB 1

SwtchGear

105.000

37.563

78.457

0.400

MCCBLV0101

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

19.414

0.400

MCCBLV0102

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0103

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0104

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0105

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0106

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0107

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0108

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0109

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0110

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0111

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0112

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0113

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0114

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0115

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0116

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0117

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0118

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0119

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0120

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0121

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0122

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0123

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0124

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0125

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0126

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0127

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0128

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0129

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

MCCBLV0130

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

31

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

3-Phase Fault Currents


Device Capacity (kA)
Bus
ID
LVMDB 1

LVMDB 2

MV KDL 1

Device
kV

ID

Type

Short-Circuit Current (kA)

Making
Peak

Ib sym

Ib asym

50.000

50.000

37.563

78.457

27.896

27.896

Idc

I"k

ip

Ib sym

Ib asym

Idc

0.400

MCCBLV0131

CB

105.000

0.400

MCCBLV0132

CB

105.000

50.000

50.000

37.563

78.457

27.896

27.896

0.044

0.400

ACB01

CB

105.000

100.000

124.686

37.563

78.457

34.506

42.403

24.645

0.400

LVMDB 2

SwtchGear

105.000

37.007

77.054

0.400

MCCBLV0201

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0202

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0203

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0204

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0205

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0206

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0207

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0208

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0209

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0210

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0211

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0212

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0213

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0214

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0215

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0216

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0217

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0218

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0220

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0221

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0222

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0223

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0224

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0225

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0226

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0227

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0228

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0229

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0230

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

MCCBLV0231

CB

105.000

50.000

50.000

37.007

77.054

27.955

27.955

0.044

0.400

ACB02

CB

100.000

100.000

124.686

37.007

77.054

34.120

41.810

24.164

0.400

CB2

CB

105.000

50.000

59.053

37.007

77.054

34.120

41.810

24.164

MV KDL 1

SwtchGear

1.157

2.437

20.000

16.000

Ik

0.044

19.414

0.690

ETAP

Project:

12.5.0C

Location:
Contract:
Engineer:
Filename:

Study Case: SC
STOCK YARD 2_2

Page:

32

Date:

18-07-2014

SN:

KRAKATAUEN

Revision:

Base

Config.:

Normal

3-Phase Fault Currents


Device Capacity (kA)
Bus
ID
MV KDL 1

MV KDL 2

MVMDB 1

Device
kV

ID

Type

Making
Peak

Short-Circuit Current (kA)


Ib sym

Ib asym

Idc

I"k

ip

Ib sym

Ib asym

Idc

20.000

VCB02

CB

16.000

16.000

24.172

18.119

1.157

2.437

1.092

1.338

0.772

20.000

VCB01

CB

16.000

16.000

24.172

18.119

1.157

2.437

1.092

1.338

0.772

20.000

MV KDL 2

SwtchGear

16.000

1.123

2.701

20.000

VCB 2

CB

16.000

16.000

24.172

18.119

1.123

2.701

1.103

1.551

1.091

20.000

VCB03

CB

16.000

16.000

24.172

18.119

1.123

2.701

1.103

1.551

1.091

6.000

MVMDB 1

SwtchGear

31.500

3.026

7.027

6.000

VCBMV01

CB

31.500

31.500

47.589

35.671

3.026

7.027

2.860

3.902

2.654

6.000

VCBMV02

CB

31.500

31.500

47.589

35.671

3.026

7.027

2.860

3.902

2.654

6.000

VCBMV03

CB

31.500

31.500

47.589

35.671

3.026

7.027

2.860

3.902

2.654

6.000

VCBMV04

CB

31.500

31.500

47.589

35.671

3.026

7.027

2.860

3.902

2.654

ip is calculated using method C


Ib does not include decay of non-terminal faulted indunction motors
Ik is the maximum steady state fault current
Idc is based on X/R from Method C and Ib as specified above
LV CB duty determined based on service rating.
Total through current is used for device duty.
* Indicates a device with calculated duty exceeding the device capability.
# Indicates a device with calculated duty exceeding the device marginal limit . ( 95 % times device capability)

Ik