DETAIL SPECIFICATION OF 220 KV CURRENT TRANSFORMER (220 KV

FEEDER- I, II, III, IV)


Required quantity -06 Sets
TYPE: O.D.D.T

FREQUENCY: 50 Hz

ISULATION LEVEL: 460/1050 KV

CORE NO.

CORE-I
RELAYING
---------PS

CORE-II
RELAYING
------------PS

H.S.V: 245 KV

CORE-II
METERING
60VA
0.2

CORE-IV
RELAYING
---------PS

BURDEN
ACURRACY
CLASS
ISF
--------------3 Max
-----ALF
---------------------------------------------CURRENT
600/1
600/1
600/1
1000/1
RATIO/ TURNS
RATIO
MIN. KNEE
1250 V
1250 V
-------------1000 V
POINT
VOLTAGE(Vk)
MAX.
70 mA at Vk
70 mA at Vk
70 mA at Vk
EXCITATION
30 mA at Vk/2 30 mA at Vk/2 ----------30 mA at Vk/2
CURRENT
Max. SEC WDG 4 Ohm
4 Ohm
4 Ohm
RESISTANCE AT
----------75 C
RATED CONTINUOUS THERMAL CURRENT
120% OF RATED CURRENT
SHORT TIME CURRENT
Irms 40KA (rms)/1 SEC
RATED DYNAMIC CURRENT- 100 KA

CORE-V
RELAYING
-----------PS
----------------1000/1

1000 V

70 mA at Vk
30 mA at Vk/2
4 Ohm

DETAIL SPECIFICATION OF 245 KV SF6 BREAKERS


Required quantity - 04sets
RATED VOLTAGE
NORMAL CURRENT
FREQUENCY
POWER FREQUENCY WITHSTAND VOLTAGE
LIGHTING IMPULSE WITHSTAND VOLTAGE
FIRST POLE TO CLEAR FACTOR
SHORT TIME WITHSTAND CURRENT
DURATION OF SHORT CIRCUIT
SHORT CIRCUIT BREAKING CURRENT
SYMMETRICAL
ASYMMETRICAL
SHORT CIRCUIT MAKING CURRENT
OUT-OF-PHASE BREAKING CURRENT
LINE CHARGING BREAKING CURRENT
OPERATING SEQUENCE
REFERENCE STANDARD

245 KV
3150 A
50Hz
460 KV
1050 KVp
1.3
40 KA
3 Sec
40 KA
49 KA
100 KAp
10 KA
125 A
O-0.3 s-CO-min-CO
IEC 62271-100

DETAIL SPECIFICATION OF 220 KV VOLTAGE TRANSFORMER


Required quantity-03nos
TYPE
FREQUENCY
MS LEVEL
SYSTEM VOLTAGE
METHOD OF CONNECTION
NO. OF PHASE
TYPE OF TRANSFORMER
SEC. WINDING NO.
OUTPUT
ACURRACY CLASS
VOLTAGE FACTOR
VOLTAGE RATIO

CPOEGLV
50Hz
460/1050 KV

FORM

MC

245 KV
BETWEEN LINE AND EARTH IN AN EFFECTIVELY
EARTHED NEUTRAL SYSTEM
01(ONE)
EARTHED
01
02
MEASURING
PROTECTIVE
500 VA
500 VA
0.2
3P
1.5/30 Sec
1.2 CONTINUOUS
220000/3 V / 110/3
V

220000/3 V / 110/3
V

DETAIL SPECIFICATION OF 220 KV CURRENT TRANSFORMER (UNIT-I, II, III, IV)


Required quantity-06 Sets
TYPE: O.D.D.T

FREQUENCY: 50 Hz

ISULATION LEVEL: 460/1050 KV

CORE NO.

CORE-I
RELAYING
---------PS

CORE-II
METERING
60VA
0.5

H.S.V: 245 KV

CORE-III
PROTECTION
60VA
5P

CORE-IV
RELAYING
---------PS

BURDEN
ACURRACY
CLASS
ISF
------3 Max
------------------ALF
-----------------10
--------------CURRENT
600/1
600/1
600/1
1000/1
RATIO/ TURNS
RATIO
MIN. KNEE
800 V
1000 V
POINT
------------------------VOLTAGE(Vk)
MAX.
70 mA at Vk
70 mA at Vk
70 mA at Vk
EXCITATION
30 mA at Vk/2 30 mA at Vk/2 ----------30 mA at Vk/2
CURRENT
Max. SEC WDG 4 Ohm
4 Ohm
RESISTANCE AT
----------------------75 C
RATED CONTINUOUS THERMAL CURRENT
120% OF RATED CURRENT
SHORT TIME CURRENT
Irms 40KA (rms)/1 SEC
RATED DYNAMIC CURRENT- 100 KA

CORE-V
RELAYING
-----------PS
----------------1000/1

1000 V

70 mA at Vk
30 mA at Vk/2
4 Ohm

DETAIL SPECIFICATION OF 400 KV CURRENT TRANSFORMER


Required quantity -06 Sets
SL. NO/YR-20040949/2004

FREQ-50Hz

REF-STD IS : 2705-1992

HSV/NSV- 420/400KV
RATIO
CORE NO.
RATED
PRIMARY
CURRENT(A)
RATED SEC.
CURRENT(A)
OUTPUT(VA)
ACCURACY
CLASS
I.S.F/A.L.F
RESIST. AT
75C Ohms
KPV(V)
EXC. AT KPV
(mA)

IEC-44-1

2000-1000/1-1
I
II

2000-1000-500-/ 1-1-1
IV

III

2000
1

----------PS

----------PS

40
0.5

-----------PS

----------PS

--------

----------

-----------

----------

2000-1000
10-5
2000-1000
30-60

---------

----------

--------------------

--------------------------

2000-1000-500/1
10-5-2.5
4000-2000-1000
30-60-120