COMMUNICATION CONNECTIVITY DIAGRAM FOR 220/33 kV POOLING SUBSTATION


AT MUTTALA VILLAGE RAYALA WIND POWER A/C GREENKO.- EXTENSION
A

A
TO REMOTE HMI

CONTROL ROOM OF RAYALA WIND POWER (GREENKO) 220/33kV POOLING SUBSTATION AT MUTTALA
INVERTER

GPS RECEIVER

DR / EWS

VPN

INVERTER

STANDBY HMI

MAIN HMI

A4 LASERJET PRINTER

CONTROL ROOM OF APTRANSCO 220kV POOLING STATION AT MUTTALA

SLDC

DOT MATRIX PRINTER

INVERTER

DOT MATRIX PRINTER

GATEWAY

A4 LASERJET PRINTER

HYDERABAD
REMOTE STATION

VPN

INVERTER

MAIN HMI

GPS RECEIVER

DR / EWS

STANDBY HMI

ROUTER

SAS CUM SUX PANEL


-KD1 (AA1KD1)

-P1
Event Printer

55

-KA5A (AA1KA5A)

GPS Receiver
SNTP

-KA1A (AA1KA1A)

-KA2A (AA1KA2A)

2003

SYS600 / HMI / MMC 600

DR/EWS

2001

COM500 / SYS500

-KC2 (AA1KC2)

// 1

59

Printer
Server

172.16.0.163

SYS600 / HMI / MMC 600

OPC
AA1OPC1
1

-P3
LASER-PRINTER

-KA5B (AA1KA5B)

2002

DR

SAS CUM SUX PANEL

DR/EWS

-KD2 (AA1KD2)

OPC
AA1OPC2
1

56

IEC61850

RJ45 to FO
Converter

-KA4A (AA1KA4A)

LIU-G1

7 10 8 9

-TJ2 (AA1TJ2)

111213141516

Root / 1

Station Ethernet Switch

5
6

172.16.201.0

7 8 9 10111213141516

62

-KA4B (AA1KA4B)

RTU TO
IEC 61850

IEC61850

STATION ETHERNET SWITCH-1

5
6

172.16.202.0

1
2

STATION ETHERNET SWITCH-2

71

MODBUS
172.16.212.15

RTU TO
IEC 61850

-TJ22 (AA1TJ22)
7 8

7 8 9 10111213141516

24

Station Ethernet Switch

5
6

172.16.211.0

1
2

STATION ETHERNET SWITCH-1

9 10111213141516

3 4

MODBUS RTU TO IEC 61850


PROTOCOL CONVERTER

Station Ethernet Switch

5
6

172.16.212.0

STATION ETHERNET SWITCH-2

LIU-S3, S4&G2, STATION ETHERNET SWITCH#1&2


AND CONVERTERS ARE MOUNTED IN SAS PANEL

LIU-S1, S2&G1, STATION ETHERNET SWITCH#1&2,


ROUTER AND CONVERTERS ARE MOUNTED IN SAS PANEL

LIU-S1

-TJ21 (AA1TJ21) 3

Backup / 2

Station Ethernet Switch

1
2

Control Unit

FO to RJ45
Converter

LIU-G2

MODBUS RTU TO IEC 61850


PROTOCOL CONVERTER

3 4

Bay
172.16.212.4

//

1
2

3 4

172.16.212.14

16

IEC61850

//

-TJ1 (AA1TJ1)

17

-AL1QSUXA2 (AA1AL1QSUXA2)

MODBUS
172.16.202.16

IEC61850

Workstation

GPS Receiver
SNTP

// 2

-KA4 (AA1KA4)

172.16.0.114

172.16.0.162

58

SAS2

IEC61850 C

18

// 2

-KA2B (AA1KA2B)

SYS600 / HMI / MMC 600

-P4
Event Printer

OPC
AA1OPC3
1

2003

172.16.0.115

OPC
AA1OPC3

SAS1

172.16.0.112

// 1

-KA1B (AA1KA1B)

GW

IEC61850 C

//

-KA3B (AA1KA3B)

172.16.0.111

20

IEC -104
PROTOCOL

IEC61850 C

Server

REMOTE HMI

GATEWAY

172.16.0.113

172.16.0.160Printer

AA1OPC2

2001

REDUNDANT HMIS WORKING


IN HOT/STANDBY MODE

IEC61850 C

22

-P2
LASER-PRINTER

OPC

172.16.0.103

172.16.0.161

Bay Control Unit 172.16.201.3 IEC61850

OPC
AA1OPC1

GW

COM500 / SYS500

-KC1 (AA1KC1)

IEC61850 C

25

-KA3A (AA1KA3A)

2002

SYS600 / HMI / MMC 600

IEC61850 C

-AL1QSUXA1 (AA1AL1QSUXA1)

SAS2

172.16.0.102

172.16.0.110

IEC61850

SAS1

172.16.0.101

172.16.201.7

DR

ROUTER

//

TO REMOTE STATION ON
IEC -104 PROTOCOL

TO SLDC ON IEC -104

REDUNDANT HMIS WORKING IN


HOT/STANDBY MODE

TO SLDC ON IEC -101

DIGITAL PLCC

LIU-S2

LIU-S4

LIU-S3

F
220kV BCR A1

220kV BCR A3
LIU-B1
BAY ETHERNET SWITCH# 1
WILL MOUNTED IN B6-CR2

BAY ETHERNET SWITCH# 2


WILL MOUNTED IN D5-CRP

-TJ3 (AA1TJ3)
9

1 3 12 11

18 20

5 7

-TJ4 (AA1TJ4)

9
6
8

14
16

172.16.1.0

13 15

14
16

172.16.2.0

18 20

5 7

13 15

9
6
8

-D1Q06A1 (AA1D1Q06A1)

Bay Control Unit

172.16.2.13

9
14
16

13 15

6
8

-D1Q07A1 (AA1D1Q07A1)
Bay Control Unit

IEC61850

172.16.3.13

1 3 12 11

Bay Ethernet Switch

6
8

18 20

18 20

BAY-D10 INC-2

220kV BUS BAR

BAY-B2 LINE

-D1QBBFP1 (AA1D1QBBFP1)
172.16.4.20Protection

IEC61850
IEC61850

AVR
-D1Q01FP2 (AA1D1Q01FP2)
EBERLE AVR

172.16.1.15

-H1Q05FP1 (AA1H1Q05FP1)

23

Protection
device
Transformer
Main-2

IEC61850

172.16.2.17

AVR

IEC61850

EBERLE AVR

B6-CR2
BAY-B6 TRAFO-1

-D1Q06FP1 (AA1D1Q06FP1)
Protection
device
Transformer
Main-1

172.16.1.17

172.16.3.15

41

26

Protection
device
Transformer
Main-2

IEC61850

172.16.4.17

1 3 12 11

Bay Ethernet Switch

6
8

13 15 17 19

172.16.24.0

18 20

5 7

BUS SECTIONALIZER
-D1QBB1FP (AA1D1QBB1FP)

-D02FP (AA1D02FP)

72

40

P442 MAIN2
DISTANCE
PROTECTION

Protection
device
Busbar&Breaker
Failure

IEC61850

BAY ETHERNET SWITCH# 4


WILL MOUNTED IN B3-CR2

50

9
6
8

14
16

1 3 12 11

Bay Ethernet Switch

13 15 17 19

9
14
16

172.16.26.0

5 7

13 15 17 19

-TJ24 (AA1TJ24)

57
6
8

BAY-B4 BUS COUPLER


-D1Q04A1 (AA1D1Q04A1)

Bay Control Unit 172.16.24.15 IEC61850

172.16.23.15

IEC61850

-D1Q02FP1 (AA1D1Q02FP1)
Protection
device Line
Distance 21L
Main-1

IEC61850

74

172.16.23.17

14
16

172.16.27.0

B3-CR1

220kV BUS BAR

BAY-B3 LINE

-D1QBBFP2 (AA1D1QBBFP2)

-D1Q03A1 (AA1D1Q03A1)

32

30

Protection
172.16.26.20

IEC61850

device Busbar

Bay
172.16.27.15

68

Control Unit

172.16.26.17

-D03FP (AA1D03FP)

73

IEC61850

Protection
device
Busbar&Breaker
Failure

Protection
device
Busbar&Breaker
Failure

B2-CR2
37

-D1Q01FP (AA1D1Q01FP)

79

BBB R1

Bay Control Unit 172.16.26.13 IEC61850

-D1Q04FP1 (AA1D1Q04FP1)

15

1 3 12 11

20 181917 1513 7 5

B4-CR1

12

Bay Ethernet Switch

18 20

IEC61850

BAY-B2 LINE

172.16.3.17

14
16

172.16.4.19

BAY-B7 TRAFO-2

Protection
device
Transformer
Main-1

5 7

-D1Q01A1 (AA1D1Q01A1)

Bay Control Unit 172.16.23.13 IEC61850

device Busbar

172.16.23.0

49

BAY-B1 BUSSECTION

14

B7-CR2
-D1Q07FP1 (AA1D1Q07FP1)

IEC61850

78

172.16.27.17P442

MAIN2
DISTANCE
PROTECTION

B3-CR2
-D1Q04FP2 (AA1D1Q04FP2)

BAY-B3 LINE

75

-D1Q03FP1 (AA1D1Q03FP1)

Protection
device
Busbar&Breaker
Failure

13

IEC61850

IEC61850

77

172.16.27.19Protection

device Line
Distance 21L
Main-1

MFM RS485 Multi-drop Looping MODBUS Protocol

-D1Q06FP (AA1D1Q06FP)

-D1Q07FP (AA1D1Q07FP)

70

Protection
device
Busbar&Breaker
Failure

-H1Q10FP1 (AA1H1Q10FP1)

-D1Q07A2 (AA1D1Q07A2)

34

-D1Q02A1 (AA1D1Q02A1)

42

39

1 3 12 11

LIU-B8

LIU-B7 & LIU-B8 WILL MOUNTED IN PANEL


BAY ETHERNET SWITCH# 3
-TJ18 (AA1TJ18) WILL MOUNTED IN B4-CR1

B1-CR1

B2-CR1

172.16.4.13

Bay Ethernet Switch

BBB R1

Bay Control Unit

IEC61850

14
16

D10-CRP
-H1Q10A1 (AA1H1Q10A1)

36

LIU-B7

BAY ETHERNET SWITCH# 2


-TJ17 (AA1TJ17) WILL MOUNTED IN B1-CR1

BAY ETHERNET SWITCH# 1


-TJ16 (AA1TJ16) WILL MOUNTED IN B2-CR2

11

172.16.4.0

5 7 13 15 17 19

BAY-B7 TRAFO-2

27

17 19

B7-CR1

-H1Q05A1 (AA1H1Q05A1)

IEC61850

5 7

-TJ6 (AA1TJ6)

10

172.16.3.0

18 20

BAY-D5 INC-1

28

1 3 12 11

Bay Ethernet Switch

17 19

D5-CRP

BAY-B6 TRAFO-1

LIU-B6

LIU-B5& LIU-B6 WILL MOUNTED IN PANEL

BAY ETHERNET SWITCH# 4


WILL MOUNTED IN D10-CRP

-TJ5 (AA1TJ5)

1 3 12 11

Bay Ethernet Switch

17 19

B6-CR1

172.16.1.13

BAY ETHERNET SWITCH# 3


WILL MOUNTED IN B7-CR2

LIU-B5

69

Protection
device
Busbar&Breaker
Failure

TVM
-D1Q02FP (AA1D1Q02FP)
MFM RS485 Multi-drop Looping MODBUS Protocol

B6-CR1

D5-CRP

B7-CR1

D10-CRP

BBB-R1

TVM

TVM

TVM

TVM

TVM

MFM

MFM

TVM
-D1Q03FP (AA1D1Q03FP)

76

LIU-BB2

LIU-BB1

Protection
device
Busbar&Breaker
Failure

BBB-R1

MFM

TVM

J
80

Protection
device
Busbar&Breaker
Failure

LIU-BB2 WILL MOUNTED IN PANEL

LIU-BB1 WILL MOUNTED IN PANEL

ABB PRESENT SCOPE OF SUPPLY

K
33kV BCR C2

33kV BCR C1
LIU-B3& LIU-B4 WILL MOUNTED IN PANEL

LIU-B3
-TJ7 (AA1TJ7)

BAY ETHERNET SWITCH# 5


WILL MOUNTED IN D1 CRP
9

6
8

Bay Ethernet Switch

1 3 12 11

19

BAY ETHERNET SWITCH# 6


WILL MOUNTED IN D2 CRP
2

9
14
16

172.16.5.0

5 7 13 15 17 19

-TJ8 (AA1TJ8)
6
8

1 3 12 11

Bay Ethernet Switch

29

5 7 13 15 17 19

BAY ETHERNET SWITCH# 7


WILL MOUNTED IN D3 CRP
9

14
16

172.16.6.0

18 20

-TJ9 (AA1TJ9)
6
8

Bay Ethernet Switch

18 20

1 3 12 11

33

BAY ETHERNET SWITCH# 8


WILL MOUNTED IN D4 CRP
2

9
14
16

172.16.7.0

5 7 13 15 17 19

-TJ10 (AA1TJ10)

1 3 12 11

Bay Ethernet Switch

6
8

5 7 13 15

-TJ11 (AA1TJ11)

38

172.16.8.0

18 20

LIU-B5

LIU-B4

14
16

17 19 18 20

6
8

1 3 12 11

Bay Ethernet Switch


17 19

5 7

LIU-B5& LIU-B6 WILL MOUNTED IN PANEL

BAY ETHERNET SWITCH# 9


WILL MOUNTED IN D6 CRP
9

13 15

BAY ETHERNET SWITCH# 14

46

-TJ25 (AA1TJ25)WILL MOUNTED IN D12 CRP


14
16

172.16.9.0

LIU-B6

9
6
8

18 20

1 3 12 11

Bay Ethernet Switch

D1-CRP

D2-CRP

BUP Protection
BCPU

172.16.5.19

-H1Q02FP1 (AA1H1Q02FP1)

45

BUP Protection
BCPU

IEC61850

172.16.6.19

-H1Q03FP1 (AA1H1Q03FP1)

47

BUP Protection
BCPU

IEC61850

172.16.7.19

BAY-D4 FEEDER-4
-H1Q04FP1 (AA1H1Q04FP1)

52

BUP Protection
BCPU

IEC61850

172.16.8.19

13 15

BAY ETHERNET SWITCH# 15


WILL MOUNTED IN D13 CRP
9

14
16

6
8

1 3 12 11

Bay Ethernet Switch

66

17 19 18 20

5 7

13 15

14
16

172.16.15.0

17 19 18 20

Naming Convention:-

D6-CRP

D4-CRP

BAY-D3 FEEDER-3

BAY-D2 FEEDER-2

BAY-D1 FEEDER-1
-H1Q01FP1 (AA1H1Q01FP1)

D3-CRP

60

172.16.14.0

5 7

-TJ26 (AA1TJ26)

D12-CRP

BAY-D6 BUSSECTION
-H1Q06A1 (AA1H1Q06A1)

51

IEC61850

IEC61850

D13-CRP

BAY-D12 FEEDER-9
61

-H1Q12FP1 (AA1H1Q12FP1)

172.16.9.19Bay

Control
BUP Protection

BUP Protection
BCPU

172.16.14.19

D1

BAY-D13 FEEDER-10
-H1Q13FP1 (AA1H1Q13FP1)

63

BUP Protection
BCPU

IEC61850

172.16.15.19

Q01

A1/FP1

67

IEC61850

IED Reference (Example A1 for BCU IED, FP1 for Protection IED )

Bay Number
System Voltage (D1-220kV, H1-33kV)
-TJ27 (AA1TJ27)

BAY ETHERNET SWITCH# 16


WILL MOUNTED IN D14 CRP
9

BAY ETHERNET SWITCH# 11


-TJ13 (AA1TJ13) WILL MOUNTED IN D8 CRP

BAY ETHERNET SWITCH# 10


-TJ12 (AA1TJ12) WILL MOUNTED IN D7 CRP
9
6
8

Bay Ethernet Switch

1 3 12 11

9
14
16

172.16.10.0

5 7 13 15 17 19

21
6
8

Bay Ethernet Switch

1 3 12 11

5 7 13 15 17 19

9
14
16

172.16.11.0

18 20

31
6
8

Bay Ethernet Switch

1 3 12 11

18 20

5 7 13 15 17 19

35

9
14
16

172.16.12.0

6
8

BAY ETHERNET SWITCH# 13


-TJ15 (AA1TJ15) WILL MOUNTED IN D11 CRP

BAY ETHERNET SWITCH# 12


-TJ14 (AA1TJ14) WILL MOUNTED IN D9 CRP

6
8

1 3 12 11

Bay Ethernet Switch


5 7

13 15

1 3 12 11

64

172.16.16.0

43

172.16.13.0

18 20

Bay Ethernet Switch


5 7

13 15

14
16

LEGEND:-

17 19 18 20

14
16

GPS Antenna

D14-CRP

17 19 18 20

BAY-D14 FEEDER-11

D8-CRP

D7-CRP
-H1Q07FP1 (AA1H1Q07FP1)
BUP Protection
BCPU

172.16.10.19

D9-CRP

BAY-D8 FEEDER-6

BAY-D7 FEEDER-5

-H1Q08FP1 (AA1H1Q08FP1)

44

BUP Protection
BCPU

IEC61850

172.16.11.19

D11-CRP

BAY-D9 FEEDER-7
-H1Q09FP1 (AA1H1Q09FP1)

48

BUP Protection
BCPU

IEC61850

172.16.12.19

-H1Q14FP1 (AA1H1Q14FP1)

BAY-D11 FEEDER-8
-H1Q11FP1 (AA1H1Q11FP1)

53

BUP Protection
BCPU

IEC61850

172.16.13.19

BUP Protection
BCPU

172.16.16.19

Note:- (Existing System)


1. Please refer the SAS schematic drawing For more detail on the inverter distribution.
2. Supply of REG-DA IED is in GREENKO/PNU Engineering Scope.

65

IEC61850

LIU

Light Interface Unit

MFM

Multi Function Meter

TVM

Tri-Vector Meter

3. Supply of any interfacing equipments beyond Router at both ends( Station and remore) of GREENKO are excluded from ABB scope of supply.

54

IEC61850

CAT5E Cable

Note:- (ABB Present Scope of Supply for Extension bays)

12 Core Armored Fiber optic Cable


Unarmored fiber optic cabel

1. ABB Scope of supply for Extension is shown in the box with green background color. Remaining equipments are existing at substation

2101cable for GPS


CO-Axial

ABB PRESENT SCOPE OF SUPPLY FOR EXTENSION BAYS


BAY-D1

BAY-D2

BAY-D3

BAY-D4

BAY-D7

BAY-D8

BAY-D9

BAY-D11

TVM

TVM

TVM

TVM

TVM

TVM

TVM

TVM

BAY-D6

BAY-D6

MFM

MFM

BAY-D12

BAY-D13

BAY-D14

TVM

TVM

TVM
Based on: SALEORDER NO:3100052376

ABB PRESENT SCOPE OF SUPPLY

Title

Prepared: M. PREM KUMAR


Approved: R. KANNAN

MFM RS485 Multi-drop Looping MODBUS Protocol

Project

RAYALA WIND POWER COMPANY PRIVATE LIMITED,

10

11

12

13

14

15

16

Rev

GREENKO, 220/33KV POOLING SUBSTATION AT MUTTALA VILLAGE,


ANANTAPUR DIST, ANDHRA PRADESH.

Twisted Pair Serial cable for RS485 Communication

MFM RS485 Multi-drop Looping MODBUS Protocol

Rev

ABB 2012
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Y:\GREENKO_MUTTALA_EXTN\1.Base Design\1.IET Workspace\GREENKO_MUTTALA\MUTTALA\AA1\SCD - AA1.vsd / 14-05-05

Bay Ethernet Switch

6
8

Bay Control Unit

LIU-B2

LIU-B1& LIU-B2 WILL MOUNTED IN PANEL

220kV BCR A2

220kV BCR A2

17

19

Doc. des.: COMMUNICATION CONNECTIVITY


DIAGRAM

Ref. des.:

Resp. dept.: PSN-SASE

Rev. ind.: 01

20

21

22

Lang.: English:
Sheet: 01

Doc. No.: YNIM302292-CZM

ABB
18

COMMUNICATION CONNECTIVITY DIAGRAM FOR 220/33KV


POOLING SUBSTATION AT MUTTALA VILLAGE RAYALA
WIND POWER COMPANY A/C GREENKO - EXTENSION

No. of sh.: 01

23

24